| Edit it in Health Facility Briefing System (HFBS) | |||
|---|---|---|---|
|
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing | |
| Room Layout Sheet | |||
|---|---|---|---|
|
|
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
| Other Files | |||
|---|---|---|---|
|
|
Buy an editable AutoCAD DWG Room Layout Sheet (RLS) for this standard component. | $2.99 | |
| Online Room Data Sheet |
|---|
| Room Code | HTLB-I |
| Net Room Area Briefed | 12 |
| Hours of Operation | 8am to 6pm, daily |
| Occupancy | 1 |
| Description / Special Requirements | The Hot Laboratory is an area for storage and preparation of radiopharmaceuticals for use in imaging procedures. The area will include a preparation bench, cupboards and sink with touch free taps. Space will be required for dose calibration, record keeping and quality assurance activities. If pre-prepared materials are used, storage and calculation areas may be considerably smaller than for on-site preparation. Radionuclide storage areas and waste storage within the space may require sheilding, including benches and cupboards. The Hot Laboratory will be located with ready access to Nuclear Imaging Rooms and dosing areas. Additional Design Considerations - Radiation shielding to be advised by Radiation Consultant - The floors and walls should be constructed of a material that is easily decontaminated, with no gaps or crevices - Vents and traps for radioactive gases should be provided if such are used |
| Amendment | 24.10.10, - First Draft 02.05.11, - FE remarks updated 17.02.2026 Room name updated and RDS updated. Room area updated |
| ID | Fabric | Material | Finish | Specification | Selection | Remarks |
| 1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
| 3466 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 125mmH | ||
| 3000 | Wall finish | Paint | Acrylic, washable | |||
| 5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | ||
| 3022 | Wall finish | Resinate, 6mm | Prefinished | Splashback | above bench | |
| 6021 | Cornice | Tape set | Paint | Set between plasterboard wall and ceiling | ||
| 8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
| 8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
| 1709 | Doors | Solid Core | Laminate | Single leaf, with lead shielding | 920mm clear opening, lockable |
| ID | Description | Category | Group | Qty | Selection / Remarks |
| 4460 | Cupboard: wall mounted | Furniture/ Fitting | 1 | 1 | over bench, adjustable shelves |
| 6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
| 6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to sink |
| 6156 | Dispenser: soap | Furniture/ Fitting | 2 | 1 | to sink |
| 8665 | Syringe carrier: lead lined | MEQ - Nuclear Medicine | 3 | 2 | |
| 8675 | Shield: lead, brick | MEQ - Nuclear Medicine | 3 | 8 | |
| 8664 | Survey meter: scintillation | MEQ - Nuclear Medicine | 3 | 1 | |
| 8611 | Waste bin: radioactive, 20 litres | MEQ - Nuclear Medicine | 3 | 1 | |
| 8676 | Shield: syringe, 3cc | MEQ - Nuclear Medicine | 3 | 2 | for TC99 |
| 8677 | Shield: syringe, 5cc | MEQ - Nuclear Medicine | 3 | 2 | for TC99 |
| 8831 | Shield: vial, lead | MEQ - Nuclear Medicine | 3 | 5 | |
| 8986 | Shield: syringe, 2cc | MEQ - Nuclear Medicine | 3 | 2 | for TC99 |
| 9061 | Tongs: radiation protection | MEQ - Nuclear Medicine | 3 | 2 | |
| 9062 | Survey meter: contamination, G-M detector | MEQ - Nuclear Medicine | 3 | 1 | |
| 8955 | Waste bin: radioactive, beta, 20 litres | MEQ - Nuclear Medicine | 3 | 1 | |
| 8663 | Sharps disposal: lead lined | MEQ - Nuclear Medicine | 3 | 1 | in radiation shielded cupboard |
| 9064 | Dosimeter: pocket | MEQ - Nuclear Medicine | 3 | 1 | |
| 1010 | Bench: stainless steel | Metalwork | 1 | 1 | |
| 8671 | Cabinet: storage, lead lined, w shelves & drawers | MEQ - Nuclear Medicine | 2 | 1 | |
| 8680 | Shield: lead, benchtop | MEQ - Nuclear Medicine | 3 | 1 | |
| 9065 | Kit: emergency, radioactivity spillage, on trolley | MEQ - Nuclear Medicine | 3 | 1 | |
| 9188 | Shield: syringe, 5cc, acrylic, beta pharmaceuticals | MEQ - Nuclear Medicine | 3 | 1 | |
| 9816 | Forceps: vial, curved | MEQ - Nuclear Medicine | 3 | 5 | |
| 9819 | Survey meter: ion chamber | MEQ - Nuclear Medicine | 3 | 2 | |
| 9857 | Shield: vial, Y-90 | MEQ - Miscellaneous | 3 | 1 | |
| 10157 | Allowance: hot laboratory, SPECT | MEQ - Nuclear Medicine | 3 | 1 | to include additional syringe shields, vial shields, syringe carriers, tongs... etc, details and quantity depend on operational requirements |
| 10158 | Allowance: QC & calibration sources | MEQ - Nuclear Medicine | 3 | 1 | as required, depending on operational requirements |
| ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
| 9140 | Well counter: wipe testing, lead lined | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | mounted on hot cell |
| 9142 | Dose calibrator: multipurpose | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
| 9166 | Radiation area monitor: digital, wall mounted | 2 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | one inside the room and one outside the room |
| 9132 | Cabinet: storage, lead lined, sink and waste | 2 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | |
| 9867 | Laminar flow hood: radioisotope, with base cabinet, 2000mm | 2 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
| 9056 | Refrigerator: drugs, under-bench, 150L | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
| 7300 | Camera: CCTV security | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ |
| ID | Description | Service Category | Qty | Selection / Remarks |
| 5000 | Airconditioning | HVAC | ||
| 2189 | General LED | Lighting | ||
| 6055 | Special: task light, built in | Lighting | under O/H cupboards | |
| 2577 | PO: Double | Power | 2 | to walls |
| 2578 | PO: Emergency power, double | Power | 3 | 1 - refrigerator; 1 - dose calibrator/ well counter bench side; 1 - dose calibrator/ well counter behind the hood |
| 12011 | Radiation shielding | Shielding | to walls, floor, ceiling, doors & glazing as specified by Radiation Consultant | |
| 4010 | Cold water: outlet | Hydraulics | 1 | to lead-lined sink and waste cabinet (refer to manufacturer specifications) |
| 4030 | Drainage | Hydraulics | 1 | to lead-lined sink and waste cabinet (refer to manufacturer specifications) |
| 4000 | Hot water: outlet | Hydraulics | 1 | to lead-lined sink and waste cabinet (refer to manufacturer specifications) |
| 1005 | Voice / Data outlet: single | Communications | 1 | 1 - refrigerator |
| 2579 | PO: Emergency power, single | Power | 5 | 2- wall mounted radiation area monitor; 3 - radioisotope hood (from top) |
| 7022 | Compressed air | Medical Gases | 1 | to radioisotope hood (optional or gas) |
| 5019 | Exhaust | HVAC | 1 | to radioisotope hood |
| 10020 | Card access | Security | 1 | |
| 2233 | Direct connection: Emergency power | Power | 1 | to CCTV camera |
| 1006 | Voice / Data outlet: double | Communications | 2 | 1 - dose calibrator/ well counter bench side; 1 - dose calibrator/ well counter inside the hood |