Room Code | LHO-SO-I |
Net Room Area Briefed | 50 |
Hours of Operation | 24 Hours |
Occupancy | 1 - 2 intermittently |
Description / Special Requirements | The Linen Holding - Soiled, provides for the temporary holding of soiled, bagged linen in trolleys, awaiting collection by an external linen supplier. The Soiled Linen Holding Room should include a handwashing basin within the room. The Linen Holding room will have ready access to the Loading Dock area. The room should be lockable. |
Amendment | 24.10.10, - First Draft 20.04.11, - Fabric modified |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
5030 | Ceiling | Plasterboard | Prefinished | Drop-in tiles, 600x1200 mm | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900 AFFL | ||
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
9110 | Doors | Solid Core | Paint | 1 1/2 leaf | 1400mm clear opening, lockable | |
3052 | Wall finish | Vinyl | Prefinished | Wall vinyl to 1500mm AFFL | ||
4031 | Wall protection | Composite | Prefinished PVC | Corner guards to 1500AFFL | as required | |
3000 | Wall finish | Paint | Acrylic, washable | |||
6025 | Cornice | Aluminium | Powdercoat | shadow line |
ID | Description | Category | Group | Qty | Selection / Remarks |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to hand basin |
6156 | Dispenser: soap | Furniture/ Fitting | 2 | 1 | to hand basin |
23925 | Trolley: soiled linen collection | Furniture/ Fitting | 3 | 15 | qty to suit service demand |
24100 | Waste bin: paper, 20 Litre | Furniture/ Fitting | 3 | 1 | to hand basin |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
2850 | Basin: handwash, Type C | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | refer to BHWS-C (sim) |
ID | Description | Service Category | Qty | Selection / Remarks |
5015 | Ventilation | HVAC | ||
5019 | Exhaust | HVAC | ||
6000 | General fluorescent | Lighting | ||
9015 | GPO: Cleaner | Power | 1 |