Room Code | OR-CSEC-I |
Net Room Area Briefed | 42 |
Hours of Operation | 24 Hours |
Occupancy | 1 patient; 5 - 8 staff |
Description / Special Requirements | The Operating Room - C-Section provides an aseptic environment in which to carry out c-section surgical procedures under regional or general anaesthetic. The Operating Room c-Section will also have a bay within the room for neonatal resuscitation for two neonates The Operating Room will have direct access to a Scrub-up Room, exit bay and sterile stock/set-up area. Cardiac Protected electrical area Special Air Conditioning - HEPA filtration Additional Design Considerations: - Minimum critical dimension 6000mm on at least 1 side. - 'Laser In Use' warning lights may be required outside all exit doors to room if laser equipment is to be used - Lead shielding may be required depending on use of X-ray equipment - to be assessed by Radiation Consultant - External windows are desirable - double glazed with integral Venetian blinds |
Amendment | 20.05.2025 First Draft |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
9245 | Doors | Solid Core/ Safety glass | Paint | Double leaf, observation panel | 1600mm clear opening to patient entry/exit and scrub; obs panel with sliding cover or internal venetians | |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
9127 | Doors | Solid Core/ Safety glass | Paint | 1 1/2 leaf, observation panel | Optional; 1600mm clear opening to anaesthetic room; obs panel with sliding cover or integral venetians | |
6015 | Cornice | Plasterboard | Paint | Flush coved between wall & ceiling | ||
9001 | Doors | Solid Core | Paint | Single leaf | Optional; 1100mm clear opening to clean-up room | |
5020 | Ceiling | Plasterboard | Paint, scrub resistant | Flush set, suspended | 3000mm min height AFFL | |
3010 | Wall finish | Paint | Scrub resistant | epoxy paint or full height wall vinyl also acceptable | ||
2313 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 300mmH | ||
9006 | Doors | Solid Core/ Safety glass | Paint | Single leaf, observation panel | 920mm clear opening to sterile stock room/ setup room, obs panel with sliding cover or integral venetians |
ID | Description | Category | Group | Qty | Selection / Remarks |
1030 | Bench: resinate | Furniture/ Fitting | 1 | 1 | documentation station: computers, write-up |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
8296 | Bowl stand: single | MEQ - General | 3 | 2 | |
8297 | Bracket: suction bottle | MEQ - General | 2 | 4 | 2-baby; 2- mother |
8306 | IV pole: mobile | MEQ - General | 3 | 2 | |
8309 | Oxygen flowmeter | MEQ - General | 3 | 2 | 2- mother |
8318 | Suction adapter | MEQ - General | 3 | 2 | 2- mother |
8321 | Suction bottle | MEQ - General | 3 | 4 | 2-baby; 2- mother |
8343 | Cabinet: storage, instrument, OR, double door, recessed | MEQ - Furniture | 2 | 1 | |
8385 | Carrier stand, suction canisters | MEQ - General | 3 | 1 | |
8398 | Trolley: resuscitation | MEQ - Furniture | 3 | 1 | optional |
8408 | Kick bucket | MEQ - General | 3 | 2 | |
8411 | Stool: adjustable, OR | MEQ - Furniture | 3 | 2 | |
8412 | Stool: adjustable, OR, with backrest | MEQ - Furniture | 3 | 1 | for anaesthetist |
8593 | Bracket: patient monitor | MEQ - General | 2 | 1 | for cardiac monitor, mounted on anaesthesia pendant |
8594 | Linen carrier: dirty, single | MEQ - Furniture | 3 | 2 | |
8603 | Headlight: surgical | MEQ - General | 3 | 1 | |
8620 | Trolley: instrument | MEQ - Furniture | 3 | 3 | |
8291 | Air flowmeter | MEQ - General | 3 | 4 | 2-baby; 2- mother |
8311 | Oxygen flowmeter: low flow | MEQ - General | 3 | 2 | 2-baby |
8319 | Suction adapter: low flow | MEQ - General | 3 | 2 | 2-baby |
8401 | Footstool: 1-step | MEQ - Furniture | 3 | 1 | |
8622 | Trolley: gowns | MEQ - Furniture | 3 | 1 | |
8627 | Trolley: anaesthetic | MEQ - Furniture | 3 | 1 | |
8630 | Table: mayo | MEQ - Furniture | 3 | 1 | |
8746 | Trolley: surgical case, closed, single door | MEQ - Furniture | 3 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
8472 | Infusion pump: syringe | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
8767 | Defibrillator: with monitor | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional |
8714 | Anaesthesia unit: standard | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
8786 | Supply unit: ceiling, double arm | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | surgical pendant |
8822 | Warming cabinet: dual compartment, freestanding, 500L | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional |
8973 | Pump: suction/ aspirator, portable | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional |
8989 | Infusion pump: single channel | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
8551 | Light: surgical, dual, ceiling, with monitor arm & camera | 2 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
8758 | Sequential compression device | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
8779 | Monitor: physiologic, operating theatre/ cardiac | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | on anaesthesia pendant |
8924 | Electrosurgical unit: monopolar/ bipolar | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
8952 | Smoke evacuation system, surgical | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
8954 | Warmer unit: neonatal, with resuscitation | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
8967 | Monitor: video, medical grade, HD, 26-inch | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, mounted on the surgical light monitor arm |
9023 | Tracking system: instrument tray | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, workstation part of CSSD instrument tracking system |
9067 | Operating table: mobile, electric, general | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
9222 | Control panel: surgical, recessed | 2 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | includes slave analogue clock, elapsed time clock, temperature and humidity indicators and controls, IPS and UPS systems alarms, medical gas alarms, AGSS controls, theatre lamp controls, general lighting controls and power sockets as required |
9421 | Pump: suction/ aspirator, uterine, mobile | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
9547 | Medication dispensing system: automated, anaesthesia | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional |
9597 | Supply unit: ceiling, anaesthesia, tandem, double arm | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | anaesthesia pendant |
11400 | Computer: PC & monitor | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | for nursing & medical staff documentation |
54520 | Telephone: handset, handsfree | 3 | 1 | ___ | yes | ___ | ___ | ___ | ___ | ___ | ___ | on bench |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 2 | to nurse documentation station |
1005 | Voice / Data outlet: single | Communications | 2 | 1- telephone; 1- anaesthesia medication dispensing unit |
1379 | Audio/ Video outlet | Communications | 8 | for services pendants; 2- per anaesthetic arm, 4- surgical pendant |
1947 | Carbon Dioxide (CO2) | Medical Gases | 1 | 1- surgical pendant (optional) |
8010 | Staff/ Nurse assist call | Nurse Call | 2 | + indicator button & light; 1- to anaesthesia pendant; 1- baby wall console |
2024 | Music system | Communications | 1 | optional |
5005 | Air conditioning: special | HVAC | HEPA filtered | |
5040 | Pressure: positive | HVAC | ||
2242 | General LED: colour corrected | Lighting | variable lighting level | |
7000 | Oxygen (O2) | Medical Gases | 2 | 1- anaesthesia pendant; 1- surgical pendant |
7010 | Nitrous Oxide (N2O) | Medical Gases | 2 | 1- per anaesthetic pendant arm |
7020 | Medical Air (MA) | Medical Gases | 2 | 1- anaesthesia pendant; 1- surgical pendant |
7040 | Suction | Medical Gases | 2 | 1- anaesthesia pendant; 1- surgical pendant |
7070 | Scavenge | Medical Gases | 2 | 1- per anaesthetic pendant arm |
8080 | Emergency call | Nurse Call | 2 | + indicator button & light; 1- to anaesthesia pendant; 1- baby wall console |
8090 | Orderly/ Porter call | Nurse Call | 1 | optional; to anaesthesia pendant |
2576 | PO: Cleaner | Power | 1 | |
9030 | Cardiac protected/ IPS | Power | ||
2723 | PO: Cardiac Protected/IPS, single | Power | 24 | for services pendants; 6- per anaesthetic arm, 12- surgical arm |
2724 | Direct connection: Emergency power | Power | 2 | for pendants |
1006 | Voice / Data outlet: double | Communications | 8 | to services pendants; 2- per anaesthetic arm, 4- surgical pendant |
2578 | PO: Emergency power, double | Power | 2 | for walls |
2578 | PO: Emergency power, double | Power | 2 | 1- resuscitation trolley (optional); 1- warming cabinet (optional) |
2726 | PO: UPS, double | Power | 2 | for walls |
2760 | Direct connection: Voice/ Data | Communications | 1 | 1 - operating light camera attachment |
2760 | Direct connection: Voice/ Data | Communications | 1 | for surgical control panel (to be integrated with BMS & lighting controls) |
2761 | Direct connection: Tool Air | Medical Gases | 2 | 1 per pendant (for brakes) |
2757 | Direct connection: Uninterrupted power | Power | 2 | 1- surgical control panel, 1- operating light |
2726 | PO: UPS, double | Power | 2 | for nurse documentation station |
2726 | PO: UPS, double | Power | 1 | optional; anaesthesia medication dispensing unit |
12011 | Radiation shielding | Shielding | for walls, floor, ceiling, doors & glazing as specified by Radiation Consultant | |
1006 | Voice / Data outlet: double | Communications | 1 | 1- 26" display monitor within the surgical field (optional) |
2726 | PO: UPS, double | Power | 1 | 1- 26" display monitor within the surgical field (optional) |
6005 | Dimmable | Lighting | ||
1006 | Voice / Data outlet: double | Communications | 2 | for walls |
1379 | Audio/ Video outlet | Communications | 1 | 1- 26" display monitor within the surgical field (optional) |
6870 | Surgical Air (SA7) | Medical Gases | 2 | 2- surgical pendant |
6909 | Wave pad access | Security | 1 | 2 per door |
7020 | Medical Air (MA) | Medical Gases | 2 | to baby wall console |
7000 | Oxygen (O2) | Medical Gases | 2 | to baby wall console |
7040 | Suction | Medical Gases | 2 | to baby wall console |
2723 | PO: Cardiac Protected/IPS, single | Power | 8 | for baby wall console |
11000 | Wall panel | Services Panels | 1 | baby wall console |
1006 | Voice / Data outlet: double | Communications | 2 | to baby wall console |