Room Code | OR-CTCR-I |
Net Room Area Briefed | 10 |
Hours of Operation | Available 24 Hours |
Occupancy | Up to 2 staff |
Description / Special Requirements | Room adjacent to CT Scanning Room/s with direct visibility to the patient for remote control of equipment, and review and reporting of procedure images. The Control room may serve two procedure rooms. Acoustics: Acoustic privacy is required Additional Design Considerations: - Radiation shielding as advised by Radiation Consultant - Cable ducts from CT Scanning and Computer room may be required |
Amendment | 24.05.2023 RDS reviewed |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
7025 | Observation | Lead glass | Clear | Internal window | to procedure room | |
9004 | Doors | Solid Core/ Glass | Paint | Single leaf, observation panel | corridor side staff entry/ exit; 920mm clear opening; with sliding cover | |
6015 | Cornice | Plasterboard | Paint | Flush coved between wall & ceiling | ||
5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900AFFL | ||
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
9233 | Doors | Solid Core | Prefinished | Single leaf, with lead sheilding | to Operating Room - CT Procedure |
ID | Description | Category | Group | Qty | Selection / Remarks |
2100 | Chair: ergonomic, office | Furniture/ Fitting | 3 | 2 | |
5598 | Shelving unit: adjustable, full height | Furniture/ Fittings | 1 | 1 | manuals, educational material |
9100 | Hook: heavy duty | Metalwork | 1 | 2 | for lead aprons |
1050 | Bench: laminate | Furniture/ Fitting | 1 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
11400 | Computer: PC & monitor | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
54510 | Telephone: handset, standard | 3 | 1 | ___ | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
9092 | Control console | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | part of CT scanning unit | |
35860 | Monitor: CCTV | 3 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | part of CT scanning unit |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 5 | to control console and computers |
1040 | Intercom | Communications | 1 | with handsfree microphone to CT scanninh room |
5000 | Airconditioning | HVAC | ||
2189 | General LED | Lighting | ||
12011 | Radiation shielding | Shielding | to wall, door & glazing shared with CT scanning room as specified by Radiation Consultant | |
6076 | Special: 'X-ray In Use' lights | Lighting | 1 | over door to procedure room |
2578 | PO: Emergency power, double | Power | 1 | to wall |
2726 | PO: UPS, double | Power | 10 | to control console and computers |