Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Online Room Data Sheet |
---|
Room Code | OR-ENT-OPH-60-I |
Net Room Area Briefed | 60 |
Hours of Operation | 24 Hours |
Occupancy | 1 patient; 5 - 8 staff |
Description / Special Requirements | The Operating Room - ENT/ Ophthalmology provides an aseptic environment in which to carry out surgical procedures under local, regional or general anaesthetic. The General Operating Room may be used for General surgery and specialties including ENT, Ophthalmology, Plastic Surgery and any other procedures that do not require bulky equipment. The Operating Room will have direct access to a Scrub-up Room, exit bay and sterile stock/set-up area. Cardiac Protected electrical area Special Air Conditioning - HEPA filtration Additional Design Considerations: - Minimum critical dimension 6000mm on atleast 1 side. - 'Laser In Use' warning lights may be required outside all exit doors to room if laser equipment is to be used - Lead shielding may be required depending on use of X-ray equipment - to be assessed by Radiation Consultant - External windows are desirable - double glazed with integral Venetian blinds |
Amendment | 23.12.2024 First Draft |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
5020 | Ceiling | Plasterboard | Paint, scrub resistant | Flush set, suspended | 3000mm min height AFFL | |
6015 | Cornice | Plasterboard | Paint | Flush coved between wall & ceiling | ||
2313 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 300mmH | ||
6364 | Wall finish | Stainless steel | Powdercoat | or approved alternate | ||
2269 | Doors | Solid Core/ Lead glass | Paint | Double leaf, observation panel, lead shielding | optional, 1600mm clear opening to anaesthetic room; obs panel with integral venetians or intelligent glass | |
2269 | Doors | Solid Core/ Lead glass | Paint | Double leaf, observation panel, lead shielding | 1600mm clear opening to patient entry/exit and scrub; obs panel with internal venetians or intelligent glass, double action hinge | |
9005 | Doors | Solid Core/ Lead glass | Paint | Single leaf, observation panel, lead shielding | 920mm clear opening to sterile stock/ setup room, obs panel with internal venetians or intelligent glass; sliding door optional |
ID | Description | Category | Group | Qty | Selection / Remarks |
1030 | Bench: resinate | Furniture/ Fitting | 1 | 1 | documentation station: computers, write-up |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
8291 | Air flowmeter | MEQ - General | 3 | 2 | to services pendants |
8296 | Bowl stand: single | MEQ - General | 3 | 2 | |
8297 | Bracket: suction bottle | MEQ - General | 2 | 4 | |
8306 | IV pole: mobile | MEQ - General | 3 | 2 | |
8309 | Oxygen flowmeter | MEQ - General | 3 | 4 | to services pendants |
8318 | Suction adapter | MEQ - General | 3 | 4 | to services pendants |
8321 | Suction bottle | MEQ - General | 3 | 4 | |
8343 | Cabinet: storage, instrument, OR, double door, recessed | MEQ - Furniture | 2 | 1 | |
8385 | Carrier stand, suction canisters | MEQ - General | 3 | 1 | |
8398 | Trolley: resuscitation | MEQ - Furniture | 3 | 1 | |
8408 | Kick bucket | MEQ - General | 3 | 2 | |
8411 | Stool: adjustable, OR | MEQ - Furniture | 3 | 2 | |
8412 | Stool: adjustable, OR, with backrest | MEQ - Furniture | 3 | 1 | for anaesthetist |
8593 | Bracket: patient monitor | MEQ - General | 2 | 1 | for cardiac monitor, mounted on anaesthesia pendant |
8594 | Linen carrier: dirty, single | MEQ - Furniture | 3 | 2 | |
8603 | Headlight: surgical | MEQ - General | 3 | 1 | |
8620 | Trolley: instrument | MEQ - Furniture | 3 | 3 | |
8622 | Trolley: gowns | MEQ - Furniture | 3 | 1 | |
8627 | Trolley: anaesthetic | MEQ - Furniture | 3 | 1 | |
8630 | Table: mayo | MEQ - Furniture | 3 | 1 | |
8806 | Diagnostic set: ophthalmic, portable | MEQ - General | 3 | 1 | |
8807 | Ophthalmoscope: indirect, binocular | MEQ - Ophthalmology | 3 | 1 | |
8815 | Tonometer: IOP, handheld | MEQ - Ophthalmology | 3 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
6468 | Camera: in room | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | PTZ, optional, part of integration system |
8472 | Infusion pump: syringe | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | Qty TBC by project |
8473 | Infusion pump: rapid, blood/ solution warming, on stand | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | Qty TBC by project |
8548 | Light: surgical, single, ceiling, with two monitor arms & camera | 2 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | light configurations may change depending on OR integration system requirements |
8714 | Anaesthesia unit: standard | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
8767 | Defibrillator: with monitor | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
8786 | Supply unit: ceiling, double arm | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | surgical pendant |
8822 | Warming cabinet: dual compartment, freestanding, 500L | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional |
8941 | Integration system: OR, HD | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, includes 2 display monitors and 1 control monitor in the surgical field, 2 display monitor on the wall, and 1 control monitor on the nurse workstation |
8953 | Hypo-hyperthermia unit: general | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
8966 | Monitor: video, medical grade, HD, 19-inch | 3 | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, control monitors part of integration system |
8967 | Monitor: video, medical grade, HD, 26-inch | 3 | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, display monitors part of integration system |
8970 | Monitor: video, medical grade, HD, 55-inch | 3 | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, wall mounted part of integration system |
8973 | Pump: suction/ aspirator, portable | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
8989 | Infusion pump: single channel | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | Qty TBC by project |
9023 | Tracking system: instrument tray | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, workstation part of CSSD instrument tracking system |
9222 | Control panel: surgical, recessed | 2 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | includes slave analogue clock, elapsed time clock, temperature and humidity indicators and controls, IPS and UPS systems alarms, medical gas alarms, AGSS controls, theatre lamp controls, general lighting controls and power sockets as required |
9547 | Medication dispensing system: automated, anaesthesia | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, quantity and modules depend on service requirements; with this option anaesthetic trolley may not be required |
9597 | Supply unit: ceiling, anaesthesia, tandem, double arm | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | anaesthesia pendant |
10173 | Cabinet: server, OR integration | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional, part of integration system |
10389 | Light: surgical, single, ceiling, with monitor arm | 2 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | light configurations may change depending on OR integration system requirements |
8779 | Monitor: physiologic, operating theatre/ cardiac | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | on anaesthesia pendant |
9071 | Operating table: mobile, electric, ENT/ ophth | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
9496 | Operating microscope: ophthalmic, mobile, with assistant observation | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | or can be ceiling mounted depending on operational requirements |
9500 | Laser: ophthalmic, YAG | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
9501 | Laser: ophthalmic, retinal photocoagulation | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
9601 | Operating microscope: ENT, mobile | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | or can be ceiling mounted depending on operational requirements |
9702 | Phaco system: ophthalmic, mobile | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | can be kept in equipment store |
10411 | Laser unit: surgical, holmium | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
11400 | Computer: PC & monitor | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | for nursing & medical staff documentation |
13363 | Pump: suction/ aspirator, surgical, mobile | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
30221 | Microdebridement unit: ENT | 3 | 1 | |||||||||
54520 | Telephone: handset, handsfree | 3 | 1 | ___ | yes | ___ | ___ | ___ | ___ | ___ | ___ | on bench |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 2 | to nurse documentation station |
1005 | Voice / Data outlet: single | Communications | 2 | 1- telephone; 1- anaesthesia medication dispensing unit (optional) |
1379 | Audio/ Video outlet | Communications | 8 | for services pendants; 2- per anaesthetic arm, 4- surgical pendant |
1947 | Carbon Dioxide (CO2) | Medical Gases | 1 | 1- surgical pendant (optional) |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light; to anaesthesia pendant |
2024 | Music system | Communications | 1 | optional |
5005 | Air conditioning: special | HVAC | HEPA filtered | |
5040 | Pressure: positive | HVAC | ||
2242 | General LED: colour corrected | Lighting | variable lighting level | |
6074 | Special: 'Laser In Use' lights | Lighting | outside room entries, if laser to be used (optional) | |
7000 | Oxygen (O2) | Medical Gases | 4 | 1- per anaesthetic pendant arm; 2- surgical pendant |
7010 | Nitrous Oxide (N2O) | Medical Gases | 2 | 1- per anaesthetic pendant arm |
7020 | Medical Air (MA) | Medical Gases | 2 | 1- anaesthesia pendant; 1- surgical pendant |
7040 | Suction | Medical Gases | 4 | 1- per anaesthetic pendant arm; 2- surgical pendant |
7070 | Scavenge | Medical Gases | 2 | 1- per anaesthetic pendant arm |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light; to anaesthesia pendant |
8090 | Orderly/ Porter call | Nurse Call | 1 | optional; to wall |
2576 | PO: Cleaner | Power | 1 | |
9030 | Cardiac protected/ IPS | Power | ||
2723 | PO: Cardiac Protected/IPS, single | Power | 24 | for services pendants; 6- per anaesthetic arm, 12- surgical arm |
2724 | Direct connection: Emergency power | Power | 2 | for pendants |
2728 | PO: Single phase, high current, 32 Amp | Power | 3 | for laser on wall |
1006 | Voice / Data outlet: double | Communications | 8 | to services pendants; 2- per anaesthetic arm, 4- surgical pendant |
2756 | Cable conduit | Electrical | 1 | optional (part of integration system); for integration system server cabinet |
2578 | PO: Emergency power, double | Power | 2 | for walls |
2578 | PO: Emergency power, double | Power | 2 | 1- resuscitation trolley; 1- warming cabinet (optional) |
2726 | PO: UPS, double | Power | 2 | for walls |
2760 | Direct connection: Voice/ Data | Communications | 2 | 1- in room camera (optional, part of integration system), 1 - operating light camera attachment |
2760 | Direct connection: Voice/ Data | Communications | 1 | for surgical control panel (to be integrated with BMS & lighting controls) |
2761 | Direct connection: Tool Air | Medical Gases | 2 | 1 per pendant (for brakes) |
2757 | Direct connection: Uninterrupted power | Power | 3 | 1- surgical control panel, 2- operating lights (1 each) |
2757 | Direct connection: Uninterrupted power | Power | 1 | optional (part of integration system); ; for in room camera |
2726 | PO: UPS, double | Power | 2 | for nurse documentation station |
2726 | PO: UPS, double | Power | 2 | optional (part of integration system); for integration system server cabinet |
2726 | PO: UPS, double | Power | 1 | optional; anaesthesia medication dispensing unit |
12011 | Radiation shielding | Shielding | for walls, floor, ceiling, doors & glazing as specified by Radiation Consultant | |
1006 | Voice / Data outlet: double | Communications | 3 | optional (part of integration system); 1- 19" wall mounted control monitor, 2- 55" wall monitors (1 each) |
1006 | Voice / Data outlet: double | Communications | 3 | optional (part of integration system); for 1- 19" control monitor and 2- 26" display monitors within the surgical field (1 each) |
2726 | PO: UPS, double | Power | 3 | optional (part of integration system); 1- 19" wall mounted control monitor, 2- 55" wall monitors (1 each) |
2726 | PO: UPS, double | Power | 3 | optional (part of integration system); for 1- 19" control monitor and 2- 26" display monitors within the surgical field (1 each) |
6005 | Dimmable | Lighting | ||
1006 | Voice / Data outlet: double | Communications | 2 | for walls |
2694 | PO: UPS, single | Power | 2 | optional; to loudspeaker and on-air lamp (part of integration system - refer to manufacturer's specifications) |
1379 | Audio/ Video outlet | Communications | 3 | optional (part of integration system); 1- 19" wall mounted control monitor, 2- 55" wall monitors (1 each) |
1379 | Audio/ Video outlet | Communications | 3 | optional (part of integration system); for 1- 19" control monitor and 2- 26" display monitors within the surgical field (1 each) |
6870 | Surgical Air (SA7) | Medical Gases | 2 | 2- surgical pendant |
6909 | Wave pad access | Security | 4 | 2- patient entry door, 2- anaesthetic induction door (if provided) |