Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
![]() |
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
![]() |
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
![]() |
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. | $64.99 |
Online Room Data Sheet |
---|
Room Code | OR-ROB-80-I |
Net Room Area Briefed | 80 |
Hours of Operation | 24 Hours |
Occupancy | 1 patient; 5 - 12 staff |
Description / Special Requirements | The Operating Room - Robotic provides an aseptic environment in which to carry out surgical procedures under local, regional or general anaesthetic. The Robotic OR will include robotic surgical equipment. Cardiac Protected electrical area Special Air Conditioning - HEPA filtration Additional Design Considerations: - Minimum critical dimension 6000mm on at least 1 side. - 'Laser In Use' warning lights may be required outside all exit doors to room if laser equipment is to be used - Lead shielding will be required; to be assessed by Radiation Consultant - External windows are desirable - double glazed with integral Venetian blinds - Provide isolated power supply individually to each large Operating Room, together with its associated line isolation and overload monitors |
Amendment | 23.12.2024 First Draft |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
2269 | Doors | Solid Core/ Lead glass | Paint | Double leaf, observation panel, lead shielding | 1600 min clear opening to patient entry/exit; obs panel with integral venetian or intelligent glass, double action hinge | |
6015 | Cornice | Plasterboard | Paint | Flush coved between wall & ceiling | ||
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
5020 | Ceiling | Plasterboard | Paint, scrub resistant | Flush set, suspended | ||
2269 | Doors | Solid Core/ Lead glass | Paint | Double leaf, observation panel, lead shielding | Optional; 1600mm clear opening to anaesthetic room; obs panel with integral venetian or intelligent glass | |
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
2313 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 300mmH | ||
6364 | Wall finish | Stainless steel | Powdercoat | or approved alternate | ||
9005 | Doors | Solid Core/ Lead glass | Paint | Single leaf, observation panel, lead shielding | 920mm clear opening to sterile stock/ setup room, sliding door optional |
ID | Description | Category | Group | Qty | Selection / Remarks |
1030 | Bench: resinate | Furniture/ Fitting | 1 | 1 | documentation station: computers, write-up |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
8291 | Air flowmeter | MEQ - General | 3 | 2 | to services pendants |
8296 | Bowl stand: single | MEQ - General | 3 | 2 | |
8297 | Bracket: suction bottle | MEQ - General | 2 | 4 | |
8306 | IV pole: mobile | MEQ - General | 3 | 2 | |
8309 | Oxygen flowmeter | MEQ - General | 3 | 4 | to services pendants |
8318 | Suction adapter | MEQ - General | 3 | 4 | to services pendants |
8321 | Suction bottle | MEQ - General | 3 | 4 | |
8343 | Cabinet: storage, instrument, OR, double door, recessed | MEQ - Furniture | 2 | 2 | |
8385 | Carrier stand, suction canisters | MEQ - General | 3 | 1 | |
8398 | Trolley: resuscitation | MEQ - Furniture | 3 | 1 | |
8408 | Kick bucket | MEQ - General | 3 | 2 | |
8411 | Stool: adjustable, OR | MEQ - Furniture | 3 | 2 | |
8412 | Stool: adjustable, OR, with backrest | MEQ - Furniture | 3 | 1 | for anaesthetist |
8593 | Bracket: patient monitor | MEQ - General | 2 | 1 | for cardiac monitor, mounted on anaesthesia pendant |
8594 | Linen carrier: dirty, single | MEQ - Furniture | 3 | 2 | |
8603 | Headlight: surgical | MEQ - General | 3 | 1 | |
8620 | Trolley: instrument | MEQ - Furniture | 3 | 3 | |
8622 | Trolley: gowns | MEQ - Furniture | 3 | 1 | |
8627 | Trolley: anaesthetic | MEQ - Furniture | 3 | 1 | |
8630 | Table: mayo | MEQ - Furniture | 3 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
6468 | Camera: in room | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | PTZ, part of integration system |
8472 | Infusion pump: syringe | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | Qty TBC by project |
8473 | Infusion pump: rapid, blood/ solution warming, on stand | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | Qty TBC by project |
8548 | Light: surgical, single, ceiling, with two monitor arms & camera | 2 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
8714 | Anaesthesia unit: standard | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
8786 | Supply unit: ceiling, double arm | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | surgical pendant |
8767 | Defibrillator: with monitor | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
8779 | Monitor: physiologic, operating theatre/ cardiac | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | on anaesthesia pendant |
8822 | Warming cabinet: dual compartment, freestanding, 500L | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional |
8939 | Endoscopy tower: laparoscopy | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | includes video processor, light source, insufflator, suction/ irrigator, high frequency generator (electrosurgical unit), smoke evacuator, monitor, endoscopes, and optional equipment cart |
8941 | Integration system: OR, HD | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | includes 2 display monitors and 1 control monitor in the surgical field, 2 display monitor on the wall, and 1 control monitor on the nurse workstation |
8953 | Hypo-hyperthermia unit: general | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
8966 | Monitor: video, medical grade, HD, 19-inch | 3 | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | control monitors part of integration system |
8967 | Monitor: video, medical grade, HD, 26-inch | 3 | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | display monitors part of integration system |
8970 | Monitor: video, medical grade, HD, 55-inch | 3 | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | wall mounted part of integration system |
8973 | Pump: suction/ aspirator, portable | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
8989 | Infusion pump: single channel | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | Qty TBC by project |
9023 | Tracking system: instrument tray | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | workstation part of CSSD instrument tracking system |
9067 | Operating table: mobile, electric, general | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
9222 | Control panel: surgical, recessed | 2 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | includes slave analogue clock, elapsed time clock, temperature and humidity indicators and controls, IPS and UPS systems alarms, medical gas alarms, AGSS controls, theatre lamp controls, general lighting controls and power sockets as required |
9547 | Medication dispensing system: automated, anaesthesia | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, quantity and modules depend on service requirements; with this option anaesthetic trolley may not be required |
9597 | Supply unit: ceiling, anaesthesia, tandem, double arm | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | anaesthesia pendant |
10173 | Cabinet: server, OR integration | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | part of integration system |
10389 | Light: surgical, single, ceiling, with monitor arm | 2 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
10393 | Surgical system: robotic | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
11400 | Computer: PC & monitor | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | for nursing & medical staff documentation |
13363 | Pump: suction/ aspirator, surgical, mobile | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
54520 | Telephone: handset, handsfree | 3 | 1 | ___ | yes | ___ | ___ | ___ | ___ | ___ | ___ | on bench |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 2 | to nurse documentation station |
1005 | Voice / Data outlet: single | Communications | 2 | 1- telephone; 1- anaesthesia medication dispensing unit (optional) |
1379 | Audio/ Video outlet | Communications | 8 | for services pendants; 2- per anaesthetic arm, 4- surgical pendant |
1947 | Carbon Dioxide (CO2) | Medical Gases | 1 | 1- surgical pendant (optional) |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light; to anaesthesia pendant |
2024 | Music system | Communications | 1 | optional |
5005 | Air conditioning: special | HVAC | HEPA filtered | |
5040 | Pressure: positive | HVAC | ||
2242 | General LED: colour corrected | Lighting | variable lighting level | |
6074 | Special: 'Laser In Use' lights | Lighting | outside room entries, if laser to be used (optional) | |
7000 | Oxygen (O2) | Medical Gases | 4 | 1- per anaesthetic pendant arm; 2- surgical pendant |
7010 | Nitrous Oxide (N2O) | Medical Gases | 2 | 1- per anaesthetic pendant arm |
7020 | Medical Air (MA) | Medical Gases | 2 | 1- anaesthesia pendant; 1- surgical pendant |
7040 | Suction | Medical Gases | 4 | 1- per anaesthetic pendant arm; 2- surgical pendant |
7070 | Scavenge | Medical Gases | 2 | 1- per anaesthetic pendant arm |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light; to anaesthesia pendant |
8090 | Orderly/ Porter call | Nurse Call | 1 | optional; to wall |
2576 | PO: Cleaner | Power | 1 | |
9030 | Cardiac protected/ IPS | Power | ||
2723 | PO: Cardiac Protected/IPS, single | Power | 24 | for services pendants; 6- per anaesthetic arm, 12- surgical arm |
2724 | Direct connection: Emergency power | Power | 2 | for pendants |
2728 | PO: Single phase, high current, 32 Amp | Power | 1 | optional; for laser on wall |
1006 | Voice / Data outlet: double | Communications | 8 | to services pendants; 2- per anaesthetic arm, 4- surgical pendant |
2756 | Cable conduit | Electrical | 1 | part of integration system; for integration system server cabinet |
2578 | PO: Emergency power, double | Power | 2 | for walls |
2578 | PO: Emergency power, double | Power | 2 | 1- resuscitation trolley; 1- warming cabinet (optional) |
2726 | PO: UPS, double | Power | 2 | for walls |
2760 | Direct connection: Voice/ Data | Communications | 2 | 1- in room camera (part of integration system), 1 - operating light camera attachment |
2760 | Direct connection: Voice/ Data | Communications | 1 | for surgical control panel (to be integrated with BMS & lighting controls) |
2761 | Direct connection: Tool Air | Medical Gases | 2 | 1 per pendant (for brakes) |
2757 | Direct connection: Uninterrupted power | Power | 3 | 1- surgical control panel, 2- operating lights (1 each) |
2757 | Direct connection: Uninterrupted power | Power | 1 | part of integration system ; for in room camera |
2726 | PO: UPS, double | Power | 2 | for nurse documentation station |
2726 | PO: UPS, double | Power | 2 | part of integration system; for integration system server cabinet |
2726 | PO: UPS, double | Power | 1 | optional; anaesthesia medication dispensing unit |
12011 | Radiation shielding | Shielding | 1 | for walls, floor, ceiling, doors & glazing as specified by Radiation Consultant |
1006 | Voice / Data outlet: double | Communications | 3 | part of integration system; 1- 19" wall mounted control monitor, 2- 55" wall monitors (1 each) |
1006 | Voice / Data outlet: double | Communications | 3 | part of integration system; for 1- 19" control monitor and 2- 26" display monitors within the surgical field (1 each) |
2726 | PO: UPS, double | Power | 3 | part of integration system; 1- 19" wall mounted control monitor, 2- 55" wall monitors (1 each) |
2726 | PO: UPS, double | Power | 3 | part of integration system; for 1- 19" control monitor and 2- 26" display monitors within the surgical field (1 each) |
6005 | Dimmable | Lighting | ||
1006 | Voice / Data outlet: double | Communications | 2 | for walls |
2723 | PO: Cardiac Protected/IPS, single | Power | 5 | for surgical robot control station |
1379 | Audio/ Video outlet | Communications | 1 | for surgical robot control station (optional) |
2694 | PO: UPS, single | Power | 2 | optional; to loudspeaker and on-air lamp (part of integration system - refer to manufacturer's specifications) |
1379 | Audio/ Video outlet | Communications | 3 | part of integration system; for 1- 19" control monitor and 2- 26" display monitors within the surgical field (1 each) |
1379 | Audio/ Video outlet | Communications | 3 | part of integration system; 1- 19" wall mounted control monitor, 2- 55" wall monitors (1 each) |
6870 | Surgical Air (SA7) | Medical Gases | 2 | 2- surgical pendant |
1006 | Voice / Data outlet: double | Communications | 1 | for surgical robot control station |
6909 | Wave pad access | Security | 4 | 2- to patient entry door, 2- anaesthetic induction door (if provided) |