Room Code PBHE-IS-N-I
Net Room Area Briefed 14
Hours of Operation 24 Hours
Occupancy 1 patient; 1 - 2 staff intermittently
Description / Special Requirements An enclosed Patient Bed Bay used for holding of patients prior to procedures, observation of patients following procedures or for assessment and treatment of patients with non acute conditions. The Enclosed Patient Bay may be used for isolation of patients and will contain a staff handwashing basin. The Negative Pressure Isolation room will have an adjoining Anteroom and Ensuite. Body Protected electrical area
Amendment 16.05.2023 First Draft 25.06.2023 Room area updated from 12 to 14m2 to fit the layout
ID Fabric Material Finish Specification Selection Remarks
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150 mmH
3000 Wall finish Paint Acrylic, washable
3092 Wall protection MDF Laminate Bed protection wall panel
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
6025 Cornice Aluminium Powdercoat shadow line
3022 Wall finish Resinate, 6mm Prefinished Splashback tiles also acceptable
4020 Wall protection Composite Prefinished PVC Crash rail at 900AFFL as required
9120 Doors Alum/ Safety glass Powdercoat/ paint 1 1/2 leaf, fully glazed 1400mm clear opening
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
7035 Observation Alum/ Glass Powdercoat Internal window optional to side walls
ID Description Category Group Qty Selection / Remarks
8291 Air flowmeter MEQ - General 3 2
8297 Bracket: suction bottle MEQ - General 2 2
2650 Chair: visitor, patient Furniture/ Fitting 3 1 optional
4600 Curtain track: bed screen Metalwork 1 1
5000 Curtain: bed screen Furniture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6156 Dispenser: soap Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
8309 Oxygen flowmeter MEQ - General 3 2
8318 Suction adapter MEQ - General 3 2
8321 Suction bottle MEQ - General 3 2
8593 Bracket: patient monitor MEQ - General 2 1
8404 Bracket: sharps disposal MEQ - General 2 1
8306 IV pole: mobile MEQ - General 3 1
8405 Sharps disposal: wall mounted, 11L MEQ - General 2 1
8982 Stretcher: procedure/ recovery MEQ - Furniture 3 1
8402 Footstool: 2-step MEQ - Furniture 3 1
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___
8989 Infusion pump: single channel 3 1 yes opt ___ ___ ___ ___ ___ ___ on IV pole
8472 Infusion pump: syringe 3 1 yes opt ___ ___ ___ ___ ___ ___ on IV pole
9456 Light: procedure, single, ceiling mounted 2 1 yes ___ ___ ___ ___ ___ ___ ___
8485 Monitor: physiologic, critical care 3 1 yes yes ___ ___ ___ ___ ___ ___ on bracket
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 to services panel
5000 Airconditioning HVAC
6030 Special: downlights Lighting over bed/ trolley
7000 Oxygen (O2) Medical Gases 2 to services panel
7020 Medical Air (MA) Medical Gases 2 to services panel
7040 Suction Medical Gases 2 to services panel
8000 Patient to Staff call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
2582 PO: Single Power 1 at low level for stretcher/ bed
2579 PO: Emergency power, single Power 3 to services panel
2576 PO: Cleaner Power 1 as required
9040 Body protected Power
11000 Wall panel Services Panels 1 flush mounted
5050 Pressure: negative HVAC Isolation room
2233 Direct connection: Emergency power Power 1 1- sensor tap; 1- procedure light
2242 General LED: colour corrected Lighting
1005 Voice / Data outlet: single Communications 1 to patient monitor
2723 PO: Cardiac Protected/IPS, single Power 3 to services panel
2579 PO: Emergency power, single Power 1 to patient monitor
0 0