Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
![]() |
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
![]() |
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
![]() |
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. | $2.99 |
Online Room Data Sheet |
---|
Room Code | PBTR-RS1-12-I |
Net Room Area Briefed | 12 |
Hours of Operation | 24 Hours |
Occupancy | 1 patient; 1 staff |
Description / Special Requirements | A Patient Bed Bay used for the recovery of stage 1, patients from anaesthetic, located within the Operating Unit or Day Procedures Unit. A clinical handwashing basin will be provided for each 4 Recovery Bed Bays. Recovery Bed Bays will require direct observation from the Staff Station. Cardiac Protected electrical area |
Amendment | 24.10.2010 First Draft 02.09.2022 Cornice updated to Aluminium shadow line 03.09.2023 RDS updated |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | ||
3092 | Wall protection | MDF | Laminate | Bed protection wall panel | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
7001 | Windows | desirable | ||||
6025 | Cornice | Aluminium | Powdercoat | shadow line |
ID | Description | Category | Group | Qty | Selection / Remarks |
1252 | Blind: Venetian integral | Furniture/ Fitting | 1 | 1 | to external window |
4600 | Curtain track: bed screen | Metalwork | 1 | 1 | |
5000 | Curtain: bed screen | Furniture/ Fitting | 3 | 1 | |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
8291 | Air flowmeter | MEQ - General | 3 | 2 | |
8297 | Bracket: suction bottle | MEQ - General | 2 | 2 | |
8309 | Oxygen flowmeter | MEQ - General | 3 | 2 | |
8318 | Suction adapter | MEQ - General | 3 | 2 | |
8321 | Suction bottle | MEQ - General | 3 | 2 | |
8593 | Bracket: patient monitor | MEQ - General | 3 | 1 | |
8404 | Bracket: sharps disposal | MEQ - General | 2 | 1 | |
8306 | IV pole: mobile | MEQ - General | 3 | 1 | |
8982 | Stretcher: procedure/ recovery | MEQ - Furniture | 3 | 1 | |
8405 | Sharps disposal: wall mounted, 11L | MEQ - General | 2 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
8989 | Infusion pump: single channel | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | on IV pole |
8472 | Infusion pump: syringe | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | on IV pole |
9456 | Light: procedure, single, ceiling mounted | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
8485 | Monitor: physiologic, critical care | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | on bracket |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 1 | to services panel |
5000 | Airconditioning | HVAC | ||
2242 | General LED: colour corrected | Lighting | ||
7000 | Oxygen (O2) | Medical Gases | 2 | services panel |
7020 | Medical Air (MA) | Medical Gases | 2 | services panel |
7040 | Suction | Medical Gases | 2 | services panel |
8000 | Patient to Staff call | Nurse Call | 1 | + indicator button & light |
8005 | Patient call handset | Nurse Call | 1 | call button on the handset |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
2579 | PO: Emergency power, single | Power | 4 | 3 - services panel, 1- patient monitor |
2576 | PO: Cleaner | Power | 1 | may serve a group of beds |
9030 | Cardiac protected/ IPS | Power | ||
11000 | Wall panel | Services Panels | 1 | |
2724 | Direct connection: Emergency power | Power | 1 | to procedure light |
2723 | PO: Cardiac Protected/IPS, single | Power | 3 | to services panel |
1005 | Voice / Data outlet: single | Communications | 1 | to patient monitor |
2582 | PO: Single | Power | 1 | at low level for stretcher/ bed |