Patient Bay - Recovery Stage 1, 12m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. $2.99
Online Room Data Sheet
Room Code PBTR-RS1-12-I
Net Room Area Briefed 12
Hours of Operation 24 Hours
Occupancy 1 patient; 1 staff
Description / Special Requirements A Patient Bed Bay used for the recovery of stage 1, patients from anaesthetic, located within the Operating Unit or Day Procedures Unit. A clinical handwashing basin will be provided for each 4 Recovery Bed Bays. Recovery Bed Bays will require direct observation from the Staff Station. Cardiac Protected electrical area
Amendment 24.10.2010 First Draft 02.09.2022 Cornice updated to Aluminium shadow line 03.09.2023 RDS updated
ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
3092 Wall protection MDF Laminate Bed protection wall panel
3000 Wall finish Paint Acrylic, washable
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
7001 Windows desirable
6025 Cornice Aluminium Powdercoat shadow line
ID Description Category Group Qty Selection / Remarks
1252 Blind: Venetian integral Furniture/ Fitting 1 1 to external window
4600 Curtain track: bed screen Metalwork 1 1
5000 Curtain: bed screen Furniture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
8291 Air flowmeter MEQ - General 3 2
8297 Bracket: suction bottle MEQ - General 2 2
8309 Oxygen flowmeter MEQ - General 3 2
8318 Suction adapter MEQ - General 3 2
8321 Suction bottle MEQ - General 3 2
8593 Bracket: patient monitor MEQ - General 3 1
8404 Bracket: sharps disposal MEQ - General 2 1
8306 IV pole: mobile MEQ - General 3 1
8982 Stretcher: procedure/ recovery MEQ - Furniture 3 1
8405 Sharps disposal: wall mounted, 11L MEQ - General 2 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
8989 Infusion pump: single channel 3 1 yes opt ___ ___ ___ ___ ___ ___ on IV pole
8472 Infusion pump: syringe 3 1 yes opt ___ ___ ___ ___ ___ ___ on IV pole
9456 Light: procedure, single, ceiling mounted 1 1 yes ___ ___ ___ ___ ___ ___ ___
8485 Monitor: physiologic, critical care 3 1 yes yes ___ ___ ___ ___ ___ ___ on bracket
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 to services panel
5000 Airconditioning HVAC
2242 General LED: colour corrected Lighting
7000 Oxygen (O2) Medical Gases 2 services panel
7020 Medical Air (MA) Medical Gases 2 services panel
7040 Suction Medical Gases 2 services panel
8000 Patient to Staff call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
2579 PO: Emergency power, single Power 4 3 - services panel, 1- patient monitor
2576 PO: Cleaner Power 1 may serve a group of beds
9030 Cardiac protected/ IPS Power
11000 Wall panel Services Panels 1
2724 Direct connection: Emergency power Power 1 to procedure light
2723 PO: Cardiac Protected/IPS, single Power 3 to services panel
1005 Voice / Data outlet: single Communications 1 to patient monitor
2582 PO: Single Power 1 at low level for stretcher/ bed
0 0