Preparation Room - Unit Dose

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an editable Revit Room Layout Sheet (RLS) for this standard component. $64.99
Online Room Data Sheet
Room Code PREP-UNIT-I
Net Room Area Briefed 30
Hours of Operation 8am to 8pm, daily
Occupancy Up to 5
Description / Special Requirements The Unit Dose Preparation Area is a dedicated space where individual doses of medications are packaged, labelled, stored, and prepared for patient administration using unit dose packaging systems, quality control measures, and strict organizational protocols to ensure accurate dispensing, minimize medication errors, and enhance efficiency in healthcare settings.
Amendment
ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
5062 Ceiling Acoustic Prefinished Drop-in tiles, 600x600 mm
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin & sink bench, other smooth impervious finish also acceptable
4159 Cornice Aluminium Powdercoat Angle flush against wall, in line with ceiling grid
5007 Ceiling Plasterboard Paint Bulkhead
ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 3 one with inset sink
1950 Chair: ergonomic, high Furniture/ Fitting 3 2
4410 Cupboard: under bench Furniture/ Fitting 1 1 under sink, adjustable shelves
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 2 to basin & sink
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
19968 Shelving: pharmacy stock flow Furniture/ Fitting 3 4 under and above preparation bench
20000 Shelving unit: adjustable Furniture/ Fitting 1 1 over sink bench
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1 to basin
4460 Cupboard: wall mounted Furniture/ Fitting 1 1 over sink, adjustable shelves
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___
11400 Computer: PC & monitor 3 2 yes yes ___ ___ ___ ___ ___ ___
40405 Tapware: sink mixer 1 1 ___ ___ yes yes yes ___ ___ ___ provide hot water
47890 Sink & drainer: single, 930mmL 1 1 ___ ___ yes opt opt yes yes ___
54500 Telephone: cordless 3 1 yes yes ___ ___ ___ ___ ___ ___ mobile
9533 Packaging system: unit dose medication, fully automated 3 1 yes opt ___ ___ ___ ___ ___ ___ optional, depending on operational requirements
8938 Pill counter 3 1 yes ___ ___ ___ ___ ___ ___ ___
9404 Scale: pharmacy 3 1 yes ___ ___ ___ ___ ___ ___ ___
9013 Printer: label/ barcode 3 2 yes yes ___ ___ ___ ___ ___ ___
9403 Scanner: label/ barcode 3 2 yes yes ___ ___ ___ ___ ___ ___
9405 Packaging system: unit dose medication, oral liquids 3 1 yes ___ ___ ___ ___ ___ ___ ___
9406 Packaging system: unit dose medication, oral solids 3 1 yes ___ ___ ___ ___ ___ ___ ___
9532 Packaging system: unit dose medication, syringe 3 1 yes ___ ___ ___ ___ ___ ___ ___
9588 Deblistering machine 3 1 yes ___ ___ ___ ___ ___ ___ ___
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___
41100 Printer: networked 3 1 yes yes ___ ___ ___ ___ ___ ___ optional
ID Description Service Category Qty Selection / Remarks
6055 Special: task light, built in Lighting under O/H shelving
2189 General LED Lighting
5000 Airconditioning HVAC
1006 Voice / Data outlet: double Communications 7 to bench (including workstations), 1- sink bench
2576 PO: Cleaner Power 1
1006 Voice / Data outlet: double Communications 1 to unit dose packaging unit
2726 PO: UPS, double Power 1 to unit dose packaging units
2578 PO: Emergency power, double Power 12 to bench (including workstations)
2233 Direct connection: Emergency power Power 1 sensor operated tapware
2577 PO: Double Power 1 sink bench
0 0