Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. | $2.99 |
Online Room Data Sheet |
---|
Room Code | RAD-SIM-I |
Net Room Area Briefed | 40 |
Hours of Operation | 8am to 8pm, daily |
Occupancy | 1 patient, up to 2 staff |
Description / Special Requirements | The Radiotherapy Simulator room will accommodate a simulator which will duplicate the beam geometry of the medical linear accelerator. The Simulator is used in treatment planning to localise the treatment field. The Simulator uses low level X-rays, and therefore radiation sheilding will be required. A Control Room will be located adjacent to the Simulator Room. Additional Design Requirements: - Radiation sheilding to walls and glazing as advised by Radiation Consultant - Laser positioning lights will be required to manufacturer's details - 'X-ray in Use' Warning lights will be required at room entrance Body Protected electrical area |
Amendment | 24.10.10, - First Draft |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
5030 | Ceiling | Plasterboard | Prefinished | Drop-in tiles, 600x1200 mm | allows access to in-ceiling services | |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900 AFFL | ||
7025 | Observation | Lead glass | Clear | Internal window | to Control Room | |
6025 | Cornice | Aluminium | Powdercoat | shadow line | ||
9052 | Doors | Solid core/ Lead glass | Paint | 1 1/2 leaf, observation panel, lead shielding | 1350mm clear opening; to Patient entry | |
9053 | Doors | Solid Core | Prefinished | Single leaf, radiation shielding | 920 clear opening; to Control room | |
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH |
ID | Description | Category | Group | Qty | Selection / Remarks |
150 | Air flowmeter | Furniture/ Fitting | 3 | 1 | if medical air is provided |
1050 | Bench: laminate | Furniture/ Fitting | 1 | 1 | with inset sink |
4365 | Cupboard: full ht, adj shelves | Furniture/ Fitting | 1 | 1 | |
4391 | Cupboard: special | Furniture/ Fitting | 1 | 1 | WedgeTrays & Compensator Tray storage |
4391 | Cupboard: special | Furniture/ Fitting | 1 | 1 | Electron Applicator storage |
4391 | Cupboard: special | Furniture/ Fitting | 1 | 1 | Block Tray storage |
4410 | Cupboard: under bench | Furniture/ Fitting | 1 | 1 | adjustable shelves |
4430 | Cupboard: drawer unit | Furniture/ Fitting | 1 | 1 | Full height, FFDA storage drawers |
4460 | Cupboard: wall mounted | Furniture/ Fitting | 1 | 1 | over sink bench, adjustable shelves |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to sink |
6156 | Dispenser: soap | Furniture/ Fitting | 2 | 1 | to sink |
16250 | Oxygen flowmeter | Furniture/ Fitting | 3 | 1 | if oxygen is provided |
21950 | Suction adapter | Furniture/ Fitting | 3 | 1 | if suction is provided |
22000 | Suction bottle | Furniture/ Fitting | 3 | 1 | if suction is provided |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
2022 | Positioning laser: radiotherapy | 3 | 3 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | component of CT simulator package; final quantity as per manufacturer's specifications |
2041 | CT Simulator | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | services according to manufacturer's specifications |
47800 | Sink, SS: single in bench | 1 | 1 | ___ | ___ | yes | opt | opt | yes | yes | ___ | sensor taps |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 1 | 1 outlet for telephone |
1040 | Intercom | Communications | 1 | handsfree, for patient communication |
5000 | Airconditioning | HVAC | ||
6001 | General: colour corrected | Lighting | ||
6110 | Downlights: dimmable | Lighting | ||
7000 | Oxygen (O2) | Medical Gases | 1 | optional |
7020 | Medical Air (MA) | Medical Gases | 1 | optional |
7040 | Suction | Medical Gases | 1 | optional |
2577 | PO: Double | Power | 2 | final qty according to manufacturer's specifications |
2579 | PO: Emergency power, single | Power | 2 | final qty according to manufacturer's specifications |
9040 | Body protected | Power | ||
2587 | PO: Special: for equipment | Power | 1 | simulator |
11000 | Wall panel | Services Panels | 1 | optional |
12030 | Lead lining | Shielding | to wall, floors & ceiling as per radiation consultant |