Room Code RAD-SIM-I
Net Room Area Briefed 40
Hours of Operation 8am to 8pm, daily
Occupancy 1 patient, up to 2 staff
Description / Special Requirements The Radiotherapy Simulator room will accommodate a simulator which will duplicate the beam geometry of the medical linear accelerator. The Simulator is used in treatment planning to localise the treatment field. The Simulator uses low level X-rays, and therefore radiation sheilding will be required. A Control Room will be located adjacent to the Simulator Room. Additional Design Requirements: - Radiation sheilding to walls and glazing as advised by Radiation Consultant - Laser positioning lights will be required to manufacturer's details - 'X-ray in Use' Warning lights will be required at room entrance Body Protected electrical area
Amendment 24.10.10, - First Draft
ID Fabric Material Finish Specification Selection Remarks
5030 Ceiling Plasterboard Prefinished Drop-in tiles, 600x1200 mm allows access to in-ceiling services
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
3000 Wall finish Paint Acrylic, washable
8040 Door protection Composite Prefinished PVC To door frame
8010 Door protection Composite Prefinished PVC Protection plate to 900 AFFL
7025 Observation Lead glass Clear Internal window to Control Room
6025 Cornice Aluminium Powdercoat shadow line
9052 Doors Solid core/ Lead glass Paint 1 1/2 leaf, observation panel, lead shielding 1350mm clear opening; to Patient entry
9053 Doors Solid Core Prefinished Single leaf, radiation shielding 920 clear opening; to Control room
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
ID Description Category Group Qty Selection / Remarks
150 Air flowmeter Furniture/ Fitting 3 1 if medical air is provided
1050 Bench: laminate Furniture/ Fitting 1 1 with inset sink
4365 Cupboard: full ht, adj shelves Furniture/ Fitting 1 1
4391 Cupboard: special Furniture/ Fitting 1 1 WedgeTrays & Compensator Tray storage
4391 Cupboard: special Furniture/ Fitting 1 1 Electron Applicator storage
4391 Cupboard: special Furniture/ Fitting 1 1 Block Tray storage
4410 Cupboard: under bench Furniture/ Fitting 1 1 adjustable shelves
4430 Cupboard: drawer unit Furniture/ Fitting 1 1 Full height, FFDA storage drawers
4460 Cupboard: wall mounted Furniture/ Fitting 1 1 over sink bench, adjustable shelves
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to sink
6156 Dispenser: soap Furniture/ Fitting 2 1 to sink
16250 Oxygen flowmeter Furniture/ Fitting 3 1 if oxygen is provided
21950 Suction adapter Furniture/ Fitting 3 1 if suction is provided
22000 Suction bottle Furniture/ Fitting 3 1 if suction is provided
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2022 Positioning laser: radiotherapy 3 3 yes ___ ___ ___ ___ ___ ___ ___ component of CT simulator package; final quantity as per manufacturer's specifications
2041 CT Simulator 2 1 yes yes ___ ___ ___ ___ ___ ___ services according to manufacturer's specifications
47800 Sink, SS: single in bench 1 1 ___ ___ yes opt opt yes yes ___ sensor taps
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
1040 Intercom Communications 1 handsfree, for patient communication
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
6110 Downlights: dimmable Lighting
7000 Oxygen (O2) Medical Gases 1 optional
7020 Medical Air (MA) Medical Gases 1 optional
7040 Suction Medical Gases 1 optional
2577 PO: Double Power 2 final qty according to manufacturer's specifications
2579 PO: Emergency power, single Power 2 final qty according to manufacturer's specifications
9040 Body protected Power
2587 PO: Special: for equipment Power 1 simulator
11000 Wall panel Services Panels 1 optional
12030 Lead lining Shielding to wall, floors & ceiling as per radiation consultant