| Room Code | SCRBS-I |
| Net Room Area Briefed | 10 |
| Hours of Operation | 24 Hours |
| Occupancy | Up to 4 |
| Description / Special Requirements | The Shared Scrub-up provides an enclosed area for pre-operative scrubbing of hands, shared between two Operating/ Procedure Rooms. Acoustics: Sound attenuation level - medium; acoustic privacy required Additional Design Considerations: - A minimum of 800mm is required between scrub stations - Taps to be non touch - automatically operated or foot operated |
| Amendment | 24.10.2010 First Draft 21.06.2019 Room name updated 03.09.2023 RDS updated |
| ID | Fabric | Material | Finish | Specification | Selection | Remarks |
| 1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
| 2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
| 4031 | Wall protection | Composite | Prefinished PVC | Corner guards to 1500mm AFFL | other heights also acceptable as per project standardisation | |
| 5020 | Ceiling | Plasterboard | Paint, scrub resistant | Flush set, suspended | ||
| 2767 | Cornice | Plasterboard | Paint | Square set | ||
| 1020 | Floor finish | Vinyl, non-slip | Safety | Seamless, coved | to wet zone | |
| 3035 | Wall finish | Vinyl | Prefinished | Wall vinyl full height |
| ID | Description | Category | Group | Qty | Selection / Remarks |
| 6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 2 | |
| 6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 2 | |
| 6158 | Dispenser: soap antiseptic | Furniture/ Fitting | 2 | Qty (4), part of scrub sinks | |
| 6164 | Dispenser: scrub brush | Furniture/ Fitting | 2 | Qty (4), part of scrub sinks | |
| 8594 | Linen carrier: dirty, single | MEQ - Furniture | 3 | 1 | |
| 13700 | Mirror | Metalwork | 1 | 2 | optional |
| 19810 | Shelf: SS, over | Metalwork | 1 | 2 | over scrub trough |
| 10061 | Waste bin: General, 20 Litres | Furniture/ Fitting | 3 | 1 |
| ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
| 10132 | Clock: master clock | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
| 10335 | Tapware: scrub, sensor | 1 | yes | ___ | yes | yes | yes | ___ | ___ | ___ | Qty (4), part of scrub sinks; auto/ knee operated taps also acceptable | |
| 9233 | Scrub sink: 2-bay, stainless steel | 2 | 2 | opt | ___ | yes | yes | ___ | ___ | yes | ___ |
| ID | Description | Service Category | Qty | Selection / Remarks |
| 5000 | Airconditioning | HVAC | ||
| 2189 | General LED | Lighting | ||
| 2724 | Direct connection: Emergency power | Power | 4 | to sensor operated tapware |
| 1080 | Clock: master clock | Communications | 1 | battery/ POE/ electrical connection TBC |
| 4010 | Cold water: outlet | Hydraulics | 2 | to scrub sink |
| 4030 | Drainage | Hydraulics | 2 | to scrub sink |
| 4000 | Hot water: outlet | Hydraulics | 2 | to scrub sink |