Store - Equipment, 16m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. $64.99
Online Room Data Sheet
Room Code STEQ-16-I
Net Room Area Briefed 16
Hours of Operation 24 Hours
Occupancy 1 - 2 intermittently
Description / Special Requirements The Equipment Store is used for the storage of medical equipment when not in use and recharging of electrical items. Space is required for parking of mobile equipment including IV poles, wheelchairs, lifting equipment, trolleys, cradles and commode chairs for the Unit. Hooks will be required for hanging equipment.
Amendment 24.10.10, - First Issue 21.04.11, - FF and Services modified
ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
5030 Ceiling Plasterboard Prefinished Drop-in tiles, 600x1200 mm
8010 Door protection Composite Prefinished PVC Protection plate to 900 AFFL
6025 Cornice Aluminium Powdercoat shadow line
8040 Door protection Composite Prefinished PVC To door frame
9110 Doors Solid Core Paint 1 1/2 leaf 1400mm clear opening; lockable
4020 Wall protection Composite Prefinished PVC Crash rail at 900 AFFL
ID Description Category Group Qty Selection / Remarks
7200 Hook: equipment Metalwork 1 4 on mounting plate
13660 Metal shelving: 900x400x2100 Furniture/ Fitting 3 4 heavy duty
24400 Whiteboard Furniture/ Fitting 2 1 900 x 900, optional
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
2189 General LED Lighting
2577 PO: Double Power 4 for equipment recharging
0 0