Room Code STFL-I
Net Room Area Briefed 9
Hours of Operation 24 Hours
Occupancy 1 intermittently
Description / Special Requirements The Flammable Liquid Store is a fire-rated room for the storage of flammable liquids, to comply with relevant standards for the storage and handling of flammable and combustibe liquids. Additional Design Requirements: - Walls and door to be constructed of fire rated materials - The floor will require bunding to contain spillage - The door will be outward opening - The room will require provisions for fire and smoke detection
Amendment 24.10.2010 First Draft 03.09.2023 RDS updated
ID Fabric Material Finish Specification Selection Remarks
5140 Ceiling Concrete Paint Acrylic
2155 Skirting Concrete Sealed Coved concrete to 150 AFFL
1280 Floor finish Concrete Trowel Sealed
9001 Doors Solid Core Paint Single leaf 920mm clear opening, lockable, fire rated, outward opening
3000 Wall finish Paint Acrylic, washable
ID Description Category Group Qty Selection / Remarks
13660 Metal shelving: 900x400x2100 Furniture/ Fitting 3 5 heavy duty
8339 Cabinet: storage, safety, flammable, 115L MEQ - Furniture 3 4
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
ID Description Service Category Qty Selection / Remarks
5015 Ventilation HVAC
5019 Exhaust HVAC
6135 Special: hazardous location Lighting switch outside the room
3018 Heat Detector Fire Services
3000 Smoke detectors Fire Services
0 0