Waiting, 25m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. $64.99
Online Room Data Sheet
Room Code WAIT-25-I
Net Room Area Briefed 25
Hours of Operation 24 Hours
Occupancy Up to 20
Description / Special Requirements An area for visitors and patients to wait in comfort prior to or during visits to a Unit. The Waiting area may be used by the public, patients, families and other visitors to a facility. The Waiting area should be easily observed by staff. The Waiting area will require facilities for a range of occupants including adults and children, both able-bodied and disabled; the waiting area must provide access for visitors in wheelchairs. An external outlook is desirable. Waiting areas may be shared between Units. Public amenities, including parenting rooms, should be located nearby. Separate areas may be allocated for Female and Family waiting. Additional Design Considerations: - Sound absorbant materials may be required to reduce noise disturbances in adjacent areas - Waiting areas may require ready access to drinking water - Public waiting areas should include public comunications services - Room elements and furniture should provide capacity for obese patients and visitors interspersed with traditional furnishings - Additional area will be reuqired if Play Area provided. Parents should be able to observe the Play Area from the Waiting Area
Amendment 24.10.2010 - First Draft 21.04.2011 - Room Fabric, FF and Services modified 07.07.2015 - FF and Services remarks and Room description modified
ID Fabric Material Finish Specification Selection Remarks
3000 Wall finish Paint Acrylic, washable
5060 Ceiling Acoustic Prefinished Drop-in tiles, 600x1200
7001 Windows desirable
6025 Cornice Aluminium Powdercoat shadow line
949496 Skirting Timber Paint 150mmH x 20mm thick, nominal or floor vinyl coved skirting if vinyl is used
1149 Floor finish Carpet 90/10 Wool/ Nylon Broadloom, 48 oz. vinyl also acceptable
5005 Ceiling Plasterboard Paint Coffered, special optional
3029 Wall finish Glass Prefinished Decorative glass wall/partition for privacy screening
ID Description Category Group Qty Selection / Remarks
1260 Blind: holland Metalwork 3 2 provide if window provided; curtain also acceptable
2700 Chair: waiting Furniture/ Fitting 3 16 some with arms; space required for a minimum of 2 wheelchairs
13120 Rack: magazine/ pamphlet Furniture/ Fitting 3 1
17360 Pinboard: fabric covered Furniture/ Fitting 2 1 or artwork, optional
22800 Table: low Furniture/ Fitting 3 3
23295 Stand: public telephone Furniture/ Fitting 3 1 provide if public telephone provided and not wall mounted
23410 Bracket: television, wall mount Metalwork 1 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
41900 Telephone: public 3 1 yes yes ___ ___ ___ ___ ___ ___ optional; on a stand or wall mount
56800 Television: large screen 3 1 yes ___ ___ ___ ___ ___ ___ ___
ID Description Service Category Qty Selection / Remarks
1011 Telephone: public phone Communications 1 optional
1090 TV: MATV Communications 1
5000 Airconditioning HVAC
2189 General LED Lighting
2576 PO: Cleaner Power 1 as required
2587 PO: Special: for equipment Power 1 public phone, optional
2587 PO: Special: for equipment Power 1 TV
0 0