1 Bed Room - Mental Health, 20m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. $64.99
Online Room Data Sheet
Room Code 1BR-MH-20-I
Net Room Area Briefed 20
Hours of Operation 24 Hours
Occupancy 1 patient; 1-2 staff; 1-2 visitors
Description / Special Requirements Single bed room for general mental health patients; natural light and outlook is essential; The room is to be internally lockable with a master keyed lock from the outside; All fittings are to have a breaking strain of not more than 15kg. All glazing (including external windows) is to comply with relevant Standards for Mental Health Facilities. The 1 Bed Room - Mental Health may vary in configuration to suit different Ensuite options including: - 1 BR-MH-A Inboard Ensuite - 1 BR-MH-B Shared Ensuite, access from corridor - 1 BR-MH-C Back-to-Back Ensuites Additional Design Considerations: - Fittings and Furniture: . removable drawers must not to be installed . hooks are not recommended, however if hooks are required, they must be collapsible with a breaking strain of not more than 15kg - Door & Joinery Hardware . door hardware and joinery hardware must not provide ligature points -Windows and frames . windows must comply with relevant glazing safety standards . window frames must ensure that glazing will stay in place in the event of an attack; the window must prevent escape after being broken Acoustics: Acoustic privacy is required. Body Protected Electrical Area Body Protected Electrical Area
Amendment 20.07.2011 First Draft 14.10.2015 Description, FF modified 26.06.2023 RDS reviewed 03.01.2025 Area revised from 18m2 to 20m2. Description, Fabrics, FF modified
ID Fabric Material Finish Specification Selection Remarks
7001 Windows natural light & outlook essential
3067 Wall finish Laminate Prefinished for TV where required
3092 Wall protection MDF Laminate Bed protection wall panel
3000 Wall finish Paint Acrylic, washable
2767 Cornice Plasterboard Paint Square set
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel 1200mm clear inward & outward opening; lockable; glazing with integral venetians, control to corridor side; sensor to top of door; no ligature points
5040 Ceiling Fibre cement Paint, washable Flush set, suspended
1475 Ceiling Laminate Prefinished Bulkhead
1010 Floor finish Vinyl Cushioned Seamless, coved carpet also acceptable
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH MDF skirting if carpet used
ID Description Category Group Qty Selection / Remarks
690 Bed: domestic, single Furniture/ Fitting 3 1 heavy
1252 Blind: Venetian integral Furniture/ Fitting 1 2 to external window & door glazing; blind control to door glazing outside the room
2150 Chair: patient Furniture/ Fitting 3 1 suitable for mental health use
5910 Desk: built in Furniture/ Fitting 1 1 laminate
23410 Bracket: television, wall mount Metalwork 2 1 vandal proof
9814 Chair Funiture/ Fitting 3 1 suitable for mental health use
22690 Table: bedside Furniture/ Fitting 3 1 fixed to wall
20012 Shelving unit: fixed shelves Furniture/ Fitting 1 1 door height
2972 Velcro board Furniture/ Fitting 2 1 or frameless fixed artwork; optional
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3031 Television: flat screen 3 1 yes ___ ___ ___ ___ ___ ___ ___ TV should be inside a recessed vandal proof cabinet
ID Description Service Category Qty Selection / Remarks
9040 Body protected Power
2576 PO: Cleaner Power 1
2582 PO: Single Power 4 2 to each side of bed
2582 PO: Single Power 2 1 - over desk; 1 - TV
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8000 Patient to Staff call Nurse Call 1 + indicator button & light
6060 Special: night lights Lighting vandal proof
5000 Airconditioning HVAC with vandal proof outlet
2559 IPTV Communications 1
8080 Emergency call Nurse Call 1 + indicator button & light; may be a duress call system
2738 General LED: vandal proof Lighting
1087 Special: reading, vandal proof Lighting 1 may be ceiling recessed
0 0