Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. | $64.99 |
Online Room Data Sheet |
---|
Room Code | 1BR-CCU-25-I |
Net Room Area Briefed | 25 |
Hours of Operation | 24 Hours |
Occupancy | 1 patient; 1-2 visitors, 1-2 staff intermittently |
Description / Special Requirements | A 1 Bed Room - Special, Coronary Care will accommodate one patient for the delivery of cardiac care treatment. Glazed partition along the corridor wall is recommended for patient visibility and monitoring. Natural light and outlook is essential; the room requires the ability to view out of the window from either the chair or bed. Ensuite is required but should be located on the external wall. Other design considerations may include: - ceiilng mounted patient lift for bariatric patients. This should be provided in accordance with the hospital's service plan. - a minimum number of rooms with provisions for dialysis station are highly recommended but not mandatory. Provisions should be in accordance with the hospital's service plan. Acoustics: Acoustic privacy is required. Cardiac Protected Electrical Area |
Amendment | 24.10.2010 First Draft 13.04.2011 FF & Services modified 01.06.2016 Revisions to Briefed Area, Description, Fabric, FF, Services 16.04.2023 RDS reviewed |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
3092 | Wall protection | MDF | Laminate | Bed protection wall panel | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
3067 | Wall finish | Laminate | Prefinished | wall panels | ||
5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | ||
1045 | Floor finish | Vinyl, non slip | Textured | Seamless, coved | under basin | |
3022 | Wall finish | Resinate, 6mm | Prefinished | Splashback | to basin | |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
7001 | Windows | natural light & outlook essential | ||||
1253 | Observation | Alum/ Toughened glass | Powdercoat | Internal window, double glazed | with integral venetian | |
4031 | Wall protection | Composite | Prefinished PVC | Corner guards to 1500mm AFFL | as required; other heights also acceptable as per project standardisation | |
2767 | Cornice | Plasterboard | Paint | Square set | ||
9127 | Doors | Solid Core/ Safety glass | Paint | 1 1/2 leaf, observation panel | Min. 1350mm clear opening; 1400mm clear opening ideal; latch set |
ID | Description | Category | Group | Qty | Selection / Remarks |
1252 | Blind: Venetian integral | Furniture/ Fitting | 1 | 1 | to internal & external windows; internal observation window, 2-way control; roller or vertical blinds also acceptable to external window |
2050 | Chair: lounge, sofa bed | Furniture/ Fitting | 3 | 1 | optional |
2150 | Chair: patient | Furniture/ Fitting | 3 | 1 | |
2650 | Chair: visitor, patient | Furniture/ Fitting | 3 | 1 | |
2926 | Dispenser: hand sanitiser | Furniture/ Fitting | 2 | 1 | |
4330 | Cupboard: wardrobe | Furniture/ Fitting | 1 | 1 | |
4600 | Curtain track: bed screen | Metalwork | 1 | 1 | |
5000 | Curtain: bed screen | Furniture/ Fitting | 3 | 1 | |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | near basin |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to basin |
6158 | Dispenser: soap antiseptic | Furniture/ Fitting | 2 | 1 | to basin |
8291 | Air flowmeter | MEQ - General | 3 | 2 | for Medical Air |
8297 | Bracket: suction bottle | MEQ - General | 2 | 4 | |
8309 | Oxygen flowmeter | MEQ - General | 3 | 4 | for Oxygen |
8318 | Suction adapter | MEQ - General | 3 | 4 | |
8321 | Suction bottle | MEQ - General | 3 | 4 | |
8322 | Locker: bedside | MEQ - Furniture | 3 | 1 | |
8332 | Table: overbed | MEQ - Furniture | 3 | 1 | |
8306 | IV pole: mobile | MEQ - General | 3 | 1 | may be deleted if supply unit is provided |
8404 | Bracket: sharps disposal | MEQ - General | 2 | 1 | |
8593 | Bracket: patient monitor | MEQ - General | 2 | 1 | |
8594 | Linen carrier: dirty, single | MEQ - Furniture | 3 | 1 | |
8608 | Waste bin: clinical, 120 litres | MEQ - Furniture | 3 | 1 | |
9117 | Sharps disposal: wall mounted, 7L | MEQ - General | 2 | 1 | |
10061 | Waste bin: General, 20 Litres | Furniture/ Fitting | 3 | 1 | |
19800 | Shelf: laminate | Furniture/ Fitting | 1 | 1 | for flowers |
23410 | Bracket: television, wall mount | Metalwork | 2 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
3031 | Television: flat screen | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
8472 | Infusion pump: syringe | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | optional, Qty TBC by project |
8989 | Infusion pump: single channel | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | optional, Qty TBC by project |
40404 | Tapware: sensor | 1 | 1 | yes | ___ | yes | yes | yes | ___ | ___ | ___ | straight spout |
54510 | Telephone: handset, standard | 3 | 1 | ___ | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
8733 | Bed: ICU, electric | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
8988 | Infusion pump: enteral feeding | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | optional, Qty TBC by project |
3100 | Basin: scrub, Type A | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | |
8485 | Monitor: physiologic, critical care | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
8788 | Supply unit: ceiling, tandem, double arm | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, may be replaced with wall service panel depending on operational requirements | |
15985 | Dialysis station | 1 | 1 | ___ | ___ | yes | ___ | ___ | yes | yes | ___ |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 2 | to patient services wall panel |
2559 | IPTV | Communications | 1 | |
5000 | Airconditioning | HVAC | ||
2242 | General LED: colour corrected | Lighting | ||
6050 | Special: reading | Lighting | up/ down light | |
6060 | Special: night lights | Lighting | ||
7000 | Oxygen (O2) | Medical Gases | 4 | to patient services wall panel |
7020 | Medical Air (MA) | Medical Gases | 2 | to patient services wall panel |
7040 | Suction | Medical Gases | 4 | to patient services wall panel |
8000 | Patient to Staff call | Nurse Call | 1 | + indicator button & light |
8005 | Patient call handset | Nurse Call | 1 | call button & light switch on the handset |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
2582 | PO: Single | Power | 3 | 1 - for patient chair; 1 - TV; 1 - at low level for patient bed |
2579 | PO: Emergency power, single | Power | 6 | to patient services wall panel |
2576 | PO: Cleaner | Power | 1 | as required |
2724 | Direct connection: Emergency power | Power | 2 | 1- sensor operated tapware; 1- patient services pendant (if provided) |
1412 | Special: examination downlight | Lighting | over bed | |
1005 | Voice / Data outlet: single | Communications | 2 | 1-telephone; 1- patient monitor |
2579 | PO: Emergency power, single | Power | 1 | to patient monitor |
2723 | PO: Cardiac Protected/IPS, single | Power | 8 | to patient services wall panel |
11000 | Wall panel | Services Panels | 1 | optional, may be replaced with services pendant depending on operational requirements |
2506 | Cardiac protected/ Isolated power | Power | 1 | |
4045 | Reverse osmosis (RO) water outlet | Hydraulics | 1 | to dialysis station |
4037 | Tundish drain | Hydraulics | 1 | to dialysis station |
2761 | Direct connection: Tool Air | Medical Gases | 1 | to pendant (for brakes, if provided) |
2578 | PO: Emergency power, double | Power | 1 | to dialysis station |