Online Room Data Sheet
Room Code 1BR-CCU-30-I
Net Room Area Briefed 30
Hours of Operation 24 Hours
Occupancy 1 patient; 1-2 visitors, 1-2 staff intermittently
Description / Special Requirements A 1 Bed Room - Special, Coronary Care will accommodate one patient for the delivery of cardiac care treatment. Glazed partition along the corridor wall is recommended for patient visibility and monitoring. Natural light and outlook is essential; the room requires the ability to view out of the window from either the chair or bed. Ensuite is required but should be located on the external wall. Other design considerations may include: - ceiilng mounted patient lift for bariatric patients. This should be provided in accordance with the hospital's service plan. - a minimum number of rooms with provisions for dialysis station are highly recommended but not mandatory. Provisions should be in accordance with the hospital's service plan. Acoustics: Acoustic privacy is required. Body Protected Electrical Area
Amendment 24.10.2010 First Draft 13.04.2011 FF & Services modified 01.06.2016 Revisions to Briefed Area, Description, Fabric, FF, Services 30.04.2023 RDS reviewed
ID Fabric Material Finish Specification Selection Remarks
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
3092 Wall protection MDF Laminate Bed protection wall panel
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
8040 Door protection Composite Prefinished PVC To door frame
3067 Wall finish Laminate Prefinished wall panels
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
1045 Floor finish Vinyl, non slip Textured Seamless, coved under basin
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
7001 Windows natural light & outlook essential
1253 Observation Alum/ Toughened glass Powdercoat Internal window, double glazed with integral venetian
4031 Wall protection Composite Prefinished PVC Corner guards to 1500mm AFFL as required; other heights also acceptable as per project standardisation
2767 Cornice Plasterboard Paint Square set
9127 Doors Solid Core/ Safety glass Paint 1 1/2 leaf, observation panel Min. 1350mm clear opening; 1400mm clear opening ideal; latch set
ID Description Category Group Qty Selection / Remarks
1252 Blind: Venetian integral Furniture/ Fitting 1 1 to internal & external windows; internal observation window, 2-way control; roller or vertical blinds also acceptable to external window
2150 Chair: patient Furniture/ Fitting 3 1
2650 Chair: visitor, patient Furniture/ Fitting 3 2 1 to desk
2926 Dispenser: hand sanitiser Furniture/ Fitting 2 1
4330 Cupboard: wardrobe Furniture/ Fitting 1 1
5910 Desk: built in Furniture/ Fitting 1 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1 near basin
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
12755 Lounge: 2 seat, sofa bed Furniture/ Fitting 3 1 optional
19800 Shelf: laminate Furniture/ Fitting 1 1 for flowers
23410 Bracket: television, wall mount Metalwork 2 1
8291 Air flowmeter MEQ - General 3 2 for Medical Air
8297 Bracket: suction bottle MEQ - General 2 4
8309 Oxygen flowmeter MEQ - General 3 4 for Oxygen
8318 Suction adapter MEQ - General 3 4
8321 Suction bottle MEQ - General 3 4
8322 Locker: bedside MEQ - Furniture 3 1
4700 Curtain track: privacy screen Metalwork 1 1
5250 Curtain: privacy screen Furniture/ Fitting 3 1
8306 IV pole: mobile MEQ - General 3 1 may be deleted if supply unit is provided
8332 Table: overbed MEQ - Furniture 3 1
8404 Bracket: sharps disposal MEQ - General 2 1
8593 Bracket: patient monitor MEQ - General 2 1
8594 Linen carrier: dirty, single MEQ - Furniture 3 1
8608 Waste bin: clinical, 120 litres MEQ - Furniture 3 1
9117 Sharps disposal: wall mounted, 7L MEQ - General 2 1
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___
3031 Television: flat screen 3 1 yes ___ ___ ___ ___ ___ ___ ___
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___
8472 Infusion pump: syringe 3 1 yes opt ___ ___ ___ ___ ___ ___ optional, Qty TBC by project
8989 Infusion pump: single channel 3 1 yes opt ___ ___ ___ ___ ___ ___ optional, Qty TBC by project
8733 Bed: ICU, electric 3 1 yes opt ___ ___ ___ ___ ___ ___
8988 Infusion pump: enteral feeding 3 1 yes opt ___ ___ ___ ___ ___ ___ optional, Qty TBC by project
8485 Monitor: physiologic, critical care 3 1 yes yes ___ ___ ___ ___ ___ ___
8788 Supply unit: ceiling, tandem, double arm 2 yes yes ___ ___ ___ ___ ___ ___ optional, may be replaced with wall service panel depending on operational requirements
15985 Dialysis station 1 1 ___ ___ yes ___ ___ yes yes ___
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 to patient services wall panel
2559 IPTV Communications 1
5000 Airconditioning HVAC
2242 General LED: colour corrected Lighting
6050 Special: reading Lighting up/ down light
6060 Special: night lights Lighting
7000 Oxygen (O2) Medical Gases 4 to patient services wall panel
7020 Medical Air (MA) Medical Gases 2 to patient services wall panel
7040 Suction Medical Gases 4 to patient services wall panel
8000 Patient to Staff call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button & light switch on the handset
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
2582 PO: Single Power 3 1 - for patient chair; 1 - TV; 1 - at low level for patient bed
2579 PO: Emergency power, single Power 6 to patient services wall panel
2576 PO: Cleaner Power 1 as required
2724 Direct connection: Emergency power Power 2 1- sensor operated tapware; 1- patient services pendant (if provided)
1412 Special: examination downlight Lighting over bed
1005 Voice / Data outlet: single Communications 2 1-telephone; 1- patient monitor
2579 PO: Emergency power, single Power 1 to patient monitor
2723 PO: Cardiac Protected/IPS, single Power 8 to patient services wall panel
11000 Wall panel Services Panels 1 optional, may be replaced with services pendant depending on operational requirements
2506 Cardiac protected/ Isolated power Power 1
4045 Reverse osmosis (RO) water outlet Hydraulics 1 to dialysis station
4037 Tundish drain Hydraulics 1 to dialysis station
2761 Direct connection: Tool Air Medical Gases 1 to pendant (for brakes, if provided)optional
2578 PO: Emergency power, double Power 1 to dialysis station
0 0