Online Room Data Sheet
Room Code 4BR-ST-42-I
Net Room Area Briefed 42
Hours of Operation 24 Hours
Occupancy Up to 4 patients; 1-2 visitors each; 1-2 staff
Description / Special Requirements A 4 Bed Room will accommodate four patients with similar nursing needs for the delivery of nursing and medical care and treatment. Each space will be individually curtained and allow for treatment of patients either in bed or sitting beside the bed in a comfortable chair; natural light and outlook is essential; patients require the ability to view out of the window from either the chair or bed. Each room is to have direct access to ensuite toilet and shower facilities, and a staff handwash basin, either within the room or immediately adjacent. The 4 Bed Room may vary in configuration to suit different Ensuite options including: - 4 BR-ST-A Inboard Ensuite - 4 BR-ST-B Outboard Ensuite - 4 BR-ST-C Inboard/ Outboard Ensuite Acoustics: Acoustic privacy is required. Body Protected electrical area
Amendment
ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved Carpet also acceptable
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH Feather edge vinyl skirting if carpeted
3000 Wall finish Paint Acrylic, washable
3092 Wall protection MDF Laminate Bed protection wall panel
6030 Cornice Aluminium Powdercoat 24mm shadow angle
7001 Windows Natural light & outlook essential.
3060 Wall finish Vinyl Prefinished Splashback to basin, tiles also acceptable
1045 Floor finish Vinyl, non slip Textured Seamless, coved under basin
4030 Wall protection Composite Prefinished PVC Corner guards to 900 AFFL Where required
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
7030 Observation Alum/ Glass Powdercoat Internal window, door height with integral venetian, optional in outboard ensuite rooms
ID Description Category Group Qty Selection / Remarks
150 Air flowmeter Furniture/ Fitting 3 4 Medical air
700 Bed: inpatient, manual Furniture/ Fitting 3 4
1252 Blind: Venetian integral Furniture/ Fitting 1 1 to internal window if provided
1465 Bracket: suction bottle Furniture/ Fitting 2 4
2150 Chair: patient Furniture/ Fitting 3 4
2650 Chair: visitor, patient Furniture/ Fitting 3 4
4330 Cupboard: wardrobe Furniture/ Fitting 1 4
4600 Curtain track: bed screen Metalwork 1 4
4900 Curtain track: window Metalwork 1 1
5000 Curtain: bed screen Furniture/ Fitting 3 4
5410 Curtain: window, drapes Furniture/ Fitting 3 1 set
6152 Dispenser: disposable glove Furniture/ Fitting 2 1 near entry
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6156 Dispenser: soap Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
12450 Locker: bedside Furniture/ Fitting 3 4 mobile, 2 lockable top drawers
16200 Table: overbed Furniture/ Fitting 3 4
16250 Oxygen flowmeter Furniture/ Fitting 3 4
19800 Shelf: laminate Furniture/ Fitting 1 4 for flowers
21950 Suction adapter Furniture/ Fitting 3 4
22000 Suction bottle Furniture/ Fitting 3 4
23400 Bracket: television, ceiling Metalwork 1 4
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 to basin
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___ elbow action levers
54510 Telephone: handset, standard 3 4 ___ yes ___ ___ ___ ___ ___ ___
54550 Television: 34 cm 3 4 yes ___ ___ ___ ___ ___ ___ ___
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 4 1 / bed; one outlet for telephone, each bed
1090 TV: MATV Communications 4 1 / bed
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
6050 Special: reading Lighting 4 Up/down lights
6060 Special: night lights Lighting
7000 Oxygen (O2) Medical Gases 4 1 / bed
7020 Medical Air (MA) Medical Gases 4 1 / bed
7040 Suction Medical Gases 4 1 / bed
8000 Patient/ Staff call Nurse Call 4 + indicator button & light
8005 Patient call handset Nurse Call 4 call button & light switch on the handset
8010 Staff/ Nurse assist call Nurse Call 4 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
2582 PO: Single Power 16 4 / bed
2582 PO: Single Power 4 1 adjacent to each patient chair (optional)
2582 PO: Single Power 4 Bedhead low level, for electric bed/s
2579 PO: Emergency power, single Power 16 4 / bed
2576 PO: Cleaner Power 1
9040 Body protected Power
2587 PO: Special: for equipment Power 4 TVs, ceiling
0 0