Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
![]() |
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
![]() |
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
![]() |
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. | $64.99 |
Online Room Data Sheet |
---|
Room Code | BMEQ-2.5-I |
Net Room Area Briefed | 2.5 |
Hours of Operation | 24 Hours |
Occupancy | N/A |
Description / Special Requirements | An open storage bay for one or more items of mobile equipment in frequent use which may include IV stands, trolleys or other mobile equipment. Special Design Requirements: The Bay should be deep enough to ensure equipment stored does not impede corridor circulation; minimum depth 1200mm. Electrical equipment that requires recharging may be stored in this space whilst recharging, therefore provision of appropriately located power outlets will be required. |
Amendment | 24.10.10, - First Draft 05.05.11, - Remarks modified |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | or consistent with the adjacent corridor | |
3000 | Wall finish | Paint | Acrylic, washable | |||
4020 | Wall protection | Composite | Prefinished PVC | Crash rail at 900 AFFL | ||
5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | ||
4031 | Wall protection | Composite | Prefinished PVC | Corner guards to 1500 AFFL | ||
6025 | Cornice | Aluminium | Powdercoat | shadow line | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | or consistent with the adjacent corridor | |
4022 | Wall protection | Composite | Prefinished PVC | Crash rail at 350 AFFL | optional |
ID | Description | Category | Group | Qty | Selection / Remarks |
7400 | Trolley: equipment | Furniture/ Fitting | 3 | 1 | as required |
11100 | IV stand: mobile | Furniture/ Fitting | 3 | 1 | as required |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
35700 | IMG: X-ray machine, mobile | 3 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ |
ID | Description | Service Category | Qty | Selection / Remarks |
5000 | Airconditioning | HVAC | ||
2189 | General LED | Lighting | ||
2577 | PO: Double | Power | 2 | For recharging of electrical equipment |