Room Code | BMEQ-6-I |
Net Room Area Briefed | 6 |
Hours of Operation | 24 Hours |
Occupancy | N/A |
Description / Special Requirements | An open storage bay for one or more items of mobile equipment in frequent use which may include mobile X-ray equipment, wheelchairs, mobile scales, commode chairs, patient lifting devices, or other mobile equipment. Special Design Requirements: The Bay should be deep enough to ensure equipment stored does not impede corridor circulation; bay depth 800 -1200mm depending on equiption to be stored. Electrical equipment that requires recharging may be stored in this space whilst recharging, therefore provision of appropriately located power outlets will be required. |
Amendment | 24.10.10, - First Draft 05.05.11, - FF modified |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
4020 | Wall protection | Composite | Prefinished PVC | Crash rail at 900 AFFL | ||
5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | ||
4031 | Wall protection | Composite | Prefinished PVC | Corner guards to 1500 AFFL | ||
4022 | Wall protection | Composite | Prefinished PVC | Crash rail at 350AFFL | optional | |
3000 | Wall finish | Paint | Acrylic, washable | |||
6025 | Cornice | Aluminium | Powdercoat | shadow line |
ID | Description | Category | Group | Qty | Selection / Remarks |
7400 | Trolley: equipment | Furniture/ Fitting | 3 | 1 | as required |
24200 | Wheelchair | Furniture/ Fitting | 3 | 2 | as required |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
35700 | IMG: X-ray machine, mobile | 3 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | spatial provision only |
ID | Description | Service Category | Qty | Selection / Remarks |
5000 | Airconditioning | HVAC | ||
2189 | General LED | Lighting | ||
2577 | PO: Double | Power | 2 | For recharging of electrical equipment |