Bay - Pathology, 3m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. $64.99
Online Room Data Sheet
Room Code BPATH-3-I
Net Room Area Briefed 3
Hours of Operation 24 Hours
Occupancy 1-2 staff
Description / Special Requirements A Pathology Bay provides for point of care laboratory analyses in critical care areas. Staff use this space for specimen preparation and testing. The workspace will suit a staff member who is standing. This bay may need to accommodate a fridge for temporary storage of specimens before delivery to the main pathology laboratory. This bay may be collocated with a pneumatic tube bay. The pneumatic tube bay can be used for sending specimens to the main pathology laboratory for comprehensive analysis. Additional Design Considerations: - Staff should have ready access to a handwashing bay - Bay should be supervised by staff at all times - Spatial arrangment will depend on devices required in each clinical setting - devices to be deterimed at project level - In a multi-device bay, a 300mm gap between each device is recommended - Consider height clearances required over devices if over head joinery is installed - Consider the weight of devices and reinforce joinery as required - Demineralised water may be required to the sink depending on device requirements
Amendment 28.04.2015 First draft 22.06.2015 Description and Services modified 04.07.2016 Document amended to match RLS. 01.09.2022 FF, FE and Services updated
ID Fabric Material Finish Specification Selection Remarks
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
5010 Ceiling Plasterboard Paint, washable Flush set, suspended or consistent with adjacent area
5007 Ceiling Plasterboard Paint Bulkhead
3060 Wall finish Vinyl Prefinished Splashback to sink, other smooth impervious finish also acceptable
4031 Wall protection Composite Prefinished PVC Corner guards to 1500mm AFFL other heights also acceptable as per project standardisation
2767 Cornice Plasterboard Paint Square set or consistent with adjacent area
6025 Cornice Aluminium Powdercoat shadow line
ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1 with optional inset sink; length to suit layout, refer to RLS or project specific requirements
8404 Bracket: sharps disposal MEQ - General 2 1 optional
4410 Cupboard: under bench Furniture/ Fitting 1 2 with adjustable shelf; number to suit layout, refer to RLS or project specific requirements
4470 Cupboard: wall mounted, lockable Furniture/ Fitting 1 4 over bench; number to suit layout, refer to RLS or project specific requirements
2926 Dispenser: hand sanitiser Furniture/ Fitting 2 1 may not be required if hand hygiene bay colocated
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
21680 Stool: adjustable, mobile Furniture/ Fitting 3 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1
19930 Shelving: adjustable Furniture/ Fitting 1 1
8405 Sharps disposal: wall mounted, 11L MEQ - General 2 1 optional
8607 Waste bin: clinical, 50 litres MEQ - Furniture 3 1
8304 Glucometer MEQ - General 3 1 number and type to be project specific
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
47800 Sink, SS: single in bench 1 1 ___ ___ yes opt opt yes yes ___
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ bench or wall mounted; optional
9013 Printer: label/ barcode 3 1 yes yes ___ ___ ___ ___ ___ ___
40405 Tapware: sink mixer 1 1 ___ ___ yes yes yes ___ ___ ___
9017 Analyser: blood gas, point-of-care, 30 samples/hr 3 1 opt opt ___ ___ ___ ___ ___ ___ number and type to be project specific
9057 Refrigerator: laboratory, under-bench, 150L 3 1 yes yes ___ ___ ___ ___ ___ ___ local temperature monitoring; optional, depends on frequency of collection
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 number depends on project specific requirements
5000 Airconditioning HVAC consistent with adjacent area
2577 PO: Double Power 1 number depends on project specific requirements
2578 PO: Emergency power, double Power 2 number depends on project specific requirements
6055 Special: task light, built in Lighting under O/H cupboards
2189 General LED Lighting consistent with adjacent area
1005 Voice / Data outlet: single Communications 1 to under-bench refrigerator
2578 PO: Emergency power, double Power 1 to under-bench refrigerator
0 0