Room Code | BPATH-3-I |
Net Room Area Briefed | 3 |
Hours of Operation | 24 Hours |
Occupancy | 1-2 staff |
Description / Special Requirements | A Pathology Bay provides for point of care laboratory analyses in critical care areas. Staff use this space for specimen preparation and testing. The workspace will suit a staff member who is standing. This bay may need to accommodate a fridge for temporary storage of specimens before delivery to the main pathology laboratory. This bay may be collocated with a pneumatic tube bay. The pneumatic tube bay can be used for sending specimens to the main pathology laboratory for comprehensive analysis. Additional Design Considerations: - Staff should have ready access to a handwashing bay - Bay should be supervised by staff at all times - Spatial arrangment will depend on devices required in each clinical setting - devices to be deterimed at project level - In a multi-device bay, a 300mm gap between each device is recommended - Consider height clearances required over devices if over head joinery is installed - Consider the weight of devices and reinforce joinery as required - Demineralised water may be required to the sink depending on device requirements |
Amendment | 28.04.2015 First draft 22.06.2015 Description and Services modified 04.07.2016 Document amended to match RLS. 01.09.2022 FF, FE and Services updated |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | or consistent with adjacent area | |
5007 | Ceiling | Plasterboard | Paint | Bulkhead | ||
3060 | Wall finish | Vinyl | Prefinished | Splashback | to sink, other smooth impervious finish also acceptable | |
4031 | Wall protection | Composite | Prefinished PVC | Corner guards to 1500mm AFFL | other heights also acceptable as per project standardisation | |
2767 | Cornice | Plasterboard | Paint | Square set | or consistent with adjacent area | |
6025 | Cornice | Aluminium | Powdercoat | shadow line |
ID | Description | Category | Group | Qty | Selection / Remarks |
1050 | Bench: laminate | Furniture/ Fitting | 1 | 1 | with optional inset sink; length to suit layout, refer to RLS or project specific requirements |
8404 | Bracket: sharps disposal | MEQ - General | 2 | 1 | optional |
4410 | Cupboard: under bench | Furniture/ Fitting | 1 | 2 | with adjustable shelf; number to suit layout, refer to RLS or project specific requirements |
4470 | Cupboard: wall mounted, lockable | Furniture/ Fitting | 1 | 4 | over bench; number to suit layout, refer to RLS or project specific requirements |
2926 | Dispenser: hand sanitiser | Furniture/ Fitting | 2 | 1 | may not be required if hand hygiene bay colocated |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
21680 | Stool: adjustable, mobile | Furniture/ Fitting | 3 | 1 | |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | |
6158 | Dispenser: soap antiseptic | Furniture/ Fitting | 2 | 1 | |
19930 | Shelving: adjustable | Furniture/ Fitting | 1 | 1 | |
8405 | Sharps disposal: wall mounted, 11L | MEQ - General | 2 | 1 | optional |
8607 | Waste bin: clinical, 50 litres | MEQ - Furniture | 3 | 1 | |
8304 | Glucometer | MEQ - General | 3 | 1 | number and type to be project specific |
10061 | Waste bin: General, 20 Litres | Furniture/ Fitting | 3 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
47800 | Sink, SS: single in bench | 1 | 1 | ___ | ___ | yes | opt | opt | yes | yes | ___ | |
54510 | Telephone: handset, standard | 3 | 1 | ___ | yes | ___ | ___ | ___ | ___ | ___ | ___ | bench or wall mounted; optional |
9013 | Printer: label/ barcode | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
40405 | Tapware: sink mixer | 1 | 1 | ___ | ___ | yes | yes | yes | ___ | ___ | ___ | |
9017 | Analyser: blood gas, point-of-care, 30 samples/hr | 3 | 1 | opt | opt | ___ | ___ | ___ | ___ | ___ | ___ | number and type to be project specific |
9057 | Refrigerator: laboratory, under-bench, 150L | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | local temperature monitoring; optional, depends on frequency of collection |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 2 | number depends on project specific requirements |
5000 | Airconditioning | HVAC | consistent with adjacent area | |
2577 | PO: Double | Power | 1 | number depends on project specific requirements |
2578 | PO: Emergency power, double | Power | 2 | number depends on project specific requirements |
6055 | Special: task light, built in | Lighting | under O/H cupboards | |
2189 | General LED | Lighting | consistent with adjacent area | |
1005 | Voice / Data outlet: single | Communications | 1 | to under-bench refrigerator |
2578 | PO: Emergency power, double | Power | 1 | to under-bench refrigerator |