Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
![]() |
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
![]() |
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
![]() |
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. | $64.99 |
Online Room Data Sheet |
---|
Room Code | CHPT-2-I |
Net Room Area Briefed | 2 |
Hours of Operation | 24 Hours |
Occupancy | 1 patient |
Description / Special Requirements | A screened area for ambulant patients to change from street clothes into a hospital gown prior to examination or treatment. Following examination or treatment, the patient will use this type of space to change back into their street clothes. The Change Cubicle should provide facilities for hanging clothes and a bench or chair for the patient to sit on whilst changing. Design Considerations: - Provisions for hanging patients' clothing and securing valuables, if these are not to be kept with the patient, should be considered either within this room (if lockable) or in shared secure storage or dedicated patient lockers - Waiting areas for gowned patients should be provided adjacent to the change cubicles with adequate privacy screening - Gowned patients should have access to toilet facilities without passing through public areas. Acoustics: Sound attenuation level - medium; acoustic privacy required. |
Amendment | 24.10.2010 First Draft 05.05.2011 Description modified 02.09.2015 Description, Fabric & FF modified 04.07.2016 Document amended to match RLS. |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
4159 | Cornice | Aluminium | Powdercoat | Angle flush against wall, in line with ceiling grid | ||
5062 | Ceiling | Acoustic | Prefinished | Drop-in tiles, 600x600 mm | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
4031 | Wall protection | Composite | Prefinished PVC | Corner guards to 1500mm AFFL | as required; other heights also acceptable as per project standardisation | |
8040 | Door protection | Composite | Prefinished PVC | To door frame | if door is provided | |
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | if door is provided | |
9001 | Doors | Solid Core | Paint | Single leaf | optional, if provided 920mm clear outward opening, privacy latch; curtain privacy screen on track may be provided instead |
ID | Description | Category | Group | Qty | Selection / Remarks |
1000 | Bench seat | Furniture/ Fitting | 1 | 1 | a chair may be provided instead |
3400 | Coathook | Metalwork | 1 | 2 | |
4700 | Curtain track: privacy screen | Metalwork | 1 | 1 | door also acceptable |
5250 | Curtain: privacy screen | Furniture/ Fitting | 3 | 1 | door also acceptable |
9813 | Mirror: full-height dressing | Funiture/ Fitting | 1 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
ID | Description | Service Category | Qty | Selection / Remarks |
5000 | Airconditioning | HVAC | ||
2189 | General LED | Lighting | ||
8000 | Patient to Staff call | Nurse Call | 1 | + indicator button & light |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light, may be located outside cubicle entry |