Online Room Data Sheet |
---|
Room Code | CHPT-12-I |
Net Room Area Briefed | 12 |
Hours of Operation | 24 Hours |
Occupancy | Up to 3 |
Description / Special Requirements | The Patient Change areas are provided for ambulant patients to change into gowns, to store their street clothing and to perform personal ablutions prior to and after examination or treatment. Change Rooms should be divided into Male and Female areas on a proportional basis and will include a changing area, toilet, shower, handbasin and lockers for secure storage of personal property. The changing area should include a bench seat or the patient to sit on whilst changing. The provision of a separate, enclosed change cubicle is optional. Design Considerations: - Waiting areas for gowned patients should be provided adjacent to the change cubicles with adequate privacy screening - Gowned patients should have access to toilet facilities without passing through public areas Acoustics: Sound attenuation level - medium; acoustic privacy required Body Protected Electrical Area |
Amendment | 24.10.2010 First Draft 05.05.2011 Services modified 03.09.2015 Description, Fabric and FF modified |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
9001 | Doors | Solid Core | Paint | Single leaf | 920mm clear opening | |
3000 | Wall finish | Paint | Acrylic, washable | |||
4159 | Cornice | Aluminium | Powdercoat | Angle flush against wall, in line with ceiling grid | ||
3795 | Ceiling | Plasterboard | Prefinished | Water resistant, drop-in tiles, 600x600mm | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
3060 | Wall finish | Vinyl | Prefinished | Splashback | to basin, other smooth impervious finish also acceptable | |
3035 | Wall finish | Vinyl | Prefinished | Wall vinyl full height | to wet areas, other full height smooth impervious finish also acceptable | |
1219 | Door Protection | Composite | Prefinished PVC | Kickplate, 300mm high | ||
1020 | Floor finish | Vinyl, non-slip | Safety | Seamless, coved | other non-slip impervious floor finish suitable for barefeet also acceptable |
ID | Description | Category | Group | Qty | Selection / Remarks |
1000 | Bench seat | Furniture/ Fitting | 1 | 1 | under lockers |
3400 | Coathook | Metalwork | 1 | 2 | 1 - to WC cubicle; 1 - to shower cubicle |
4800 | Curtain track: shower | Metalwork | 1 | 1 | |
5300 | Curtain: shower | Furniture/ Fitting | 3 | 1 | |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to basin |
6156 | Dispenser: soap | Furniture/ Fitting | 2 | 1 | to basin |
6160 | Dispenser: toilet paper | Furniture/ Fitting | 2 | 1 | |
7118 | Bench seat: shower | Furniture/ Fitting | 1 | 1 | to shower cubicle |
8400 | Grab rail: WC | Metalwork | 1 | 1 | to toilet cubicle |
8450 | Grab rail: Shower | Metalwork | 1 | 1 | to shower cubicle |
8594 | Linen carrier: dirty, single | MEQ - Furniture | 3 | 1 | |
8622 | Trolley: gowns | MEQ - Furniture | 3 | 1 | |
9813 | Mirror: full-height dressing | Funiture/ Fitting | 1 | 1 | |
12509 | Locker: 2 tier | Furniture/ Fitting | 3 | 4 | 8 1/2 size lockers |
12600 | Locker: 4 tier (1/4 size) | Furniture/ Fitting | 3 | 2 | 8 1/4 size lockers |
13700 | Mirror | Metalwork | 1 | 1 | above basin |
19100 | Waste bin: sanitary | Furniture/ Fitting | 3 | 1 | to WC in female change rooms |
19910 | Shelf: vanity | Furniture/ Fitting | 1 | 1 | above basin |
10061 | Waste bin: General, 20 Litres | Furniture/ Fitting | 3 | 1 | |
20055 | Partitions: shower | Furniture/ Fitting | 1 | 1 | |
20603 | Soap/ shampoo holder: recessed | Furniture/ Fitting | 1 | 1 | |
23610 | Partitions: toilet | Furniture/ Fitting | 1 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
2850 | Basin: handwash, Type C | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | |
3003 | Bidet handset | 1 | 1 | ___ | ___ | ___ | ___ | yes | yes | ___ | ___ | near toilet; optional |
40402 | Tapware: basin mixer | 1 | 1 | ___ | ___ | yes | yes | yes | ___ | ___ | ___ | |
40406 | Tapware: shower mixer | 1 | 1 | ___ | ___ | yes | yes | yes | ___ | ___ | ___ | |
47400 | Shower: hand-held | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | |
55605 | Toilet suite: patient | 1 | 1 | ___ | ___ | yes | ___ | ___ | yes | yes | ___ |
ID | Description | Service Category | Qty | Selection / Remarks |
4033 | Floor waste | Hydraulics | 3 | |
5000 | Airconditioning | HVAC | ||
5019 | Exhaust | HVAC | ||
2189 | General LED | Lighting | ||
8000 | Patient to Staff call | Nurse Call | 2 | WC & Shower Cubicles |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | |
8080 | Emergency call | Nurse Call | 1 | |
2577 | PO: Double | Power | 1 | locate near door outside room |
9040 | Body protected | Power | ||
2587 | PO: Special: for equipment | Power | 1 | for hair dryer & shaver use only; to comply with relevant electric safety guidelines |