Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. | $2.99 |
Online Room Data Sheet |
---|
Room Code | COMM-20-I |
Net Room Area Briefed | 20 |
Hours of Operation | 24 Hours |
Occupancy | 1 - 2 intermittently |
Description / Special Requirements | A secure room also known as the Computer Server room or Technology Equipment Centre to accommodate communications racks, servers, data storage devices, interface control panels for communication systems which may include patient entertainment systems, Nurse Call and Fire/EWIS system and voice/ data backbone cabling. The room may include a small workstation area for technicians to access and maintain equipment. Room temperature should be maintained for heat generating equipment. Equipment located in this room will require uninterruptible power. Special Design Requirements: - Computer equipment will require protection from power surges and spikes - Provision of an uninterruptible power supply is required for electronic health records servers and centralised storage to prevent data loss - The room should be sized to accommodate the equipment required including space for future growth - The room should be protected from fire, potential water damage, gas pipes and located away from sources of interference such as vibration, electromagnetic interference, radio and radar sytems, transformers, motors, heaters & X-ray equipment |
Amendment | 19.10.2015 First issue 18.05.2016 Fabric, FE and services modified 30.03.2017 Description & Services updated |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1030 | Floor finish | Vinyl | Anti-static | Seamless, coved | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
5030 | Ceiling | Plasterboard | Prefinished | Drop-in tiles, 600x1200 mm | ||
1219 | Door Protection | Composite | Prefinished PVC | Kickplate, 300mm high | ||
6025 | Cornice | Aluminium | Powdercoat | shadow line | ||
9110 | Doors | Solid Core | Paint | 1 1/2 leaf | 1400mm/920mm clear opening; small leaf optional; lockable, card access recommended |
ID | Description | Category | Group | Qty | Selection / Remarks |
1050 | Bench: laminate | Furniture/ Fitting | 1 | 1 | optional; proprietary desk may be used |
2100 | Chair: ergonomic, office | Furniture/ Fitting | 3 | 1 | optional |
6114 | Cable tray | Furiture/fitting | 1 | 1 | for services, as required |
24405 | Whiteboard: magnetic | Furniture/ Fitting | 2 | 1 | 900 x 900, optional |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
8760 | Control panel: fire & EWIS | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | as required |
10890 | Rack: communications | 1 | 6 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | as required |
10895 | Rack: voice, IDF | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | as required |
11200 | Computer: mainframe | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | as required |
10655 | Communications board | 1 | 4 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | as required |
11400 | Computer: PC & monitor | 3 | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | flat screen; as required |
11900 | Computer: server | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | as required |
17100 | Distribution Board | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | UPS, single phase, as required |
54510 | Telephone: handset, standard | 3 | 1 | ___ | yes | ___ | ___ | ___ | ___ | ___ | ___ |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 5 | 1 outlet for telephone; quantity to suit functional requirements |
5000 | Airconditioning | HVAC | adequate for equipment & personnel heat load; temperature alarm may be required for heat generating equipment | |
2189 | General LED | Lighting | sensor light optional | |
2577 | PO: Double | Power | 7 | quantity to suit functional requirements |
9020 | UPS (uninterruptible power) | Power | as required | |
2587 | PO: Special: for equipment | Power | 10 | quantity to suit functional requirements; comms/ IDF racks may require 15amp power |
3040 | EWIS | Fire Services | 1 | as required |
10020 | Card access | Security | 1 | recommended |
10000 | Motion detector / alarm | Security | 1 | as required |