| Room Code | CORM-I |
| Net Room Area Briefed | 10 |
| Hours of Operation | 24 Hours |
| Occupancy | N/A |
| Description / Special Requirements | Refrigerated room for storage of goods requiring cool storage. Coolroom temperature should be monitored and alarmed. Essential power supply may be required. |
| Amendment | 24.10.2010 First Draft 16.03.2023 RDS reviewed |
| ID | Fabric | Material | Finish | Specification | Selection | Remarks |
| 9060 | Doors | Metal | Prefinished | Coolroom | Swing or sliding; lockable; escape access from inside | |
| 1315 | Floor finish | Metal | Prefinished | Coolroom panels | ||
| 2190 | Wall finish | Metal | Prefinished | Coolroom panels | ||
| 5000 | Ceiling | Metal | Prefinished | Coolroom panels |
| ID | Description | Category | Group | Qty | Selection / Remarks |
| 19950 | Shelving: stainless steel, coolroom | Metalwork | 1 | 7 | around all sides of room |
| ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
| ID | Description | Service Category | Qty | Selection / Remarks |
| 1085 | Temperature monitor & alarm | Communications | 1 | |
| 5021 | Special ventilation: cool room | HVAC | ||
| 2189 | General LED | Lighting | ||
| 2587 | PO: Special: for equipment | Power | essential supply to cool room plant |