| Room Code | PREP-CYT-I |
| Net Room Area Briefed | 15 |
| Hours of Operation | 24 Hours |
| Occupancy | 2 |
| Description / Special Requirements | The Cytotoxic Clean Room is a clean room designed for cytotoxic sterile medication manufacturing, including intravenous chemotherapy. The room should maintain negative relative pressure and must be accessed via an Anteroom and airlock. Body Protected electrical area Design Considerations include: - Electronic interlock door system should be provided to prevent the opening of both doors in the Anteroom at the same time - Handwashing facilities should be provided immediately outside the Aseptic (Clean) Rooms in the adjoining Anteroom. Hand basins are not to be located within the Clean Room - An intercom system should be provided between Clean Room and Anteroom - High-resolution CCTV cameras for remote monitoring should be provided - The facility must comply with the room requirements set forth in relevant International Clean Room standards for sterile and cytotoxic manufacturing - Work benches are to be freestanding and in stainless steel. Stainless steel trolleys can be provided for minimal storage |
| Amendment |
| ID | Fabric | Material | Finish | Specification | Selection | Remarks |
| 1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | 2-coat epoxy paint also acceptable | |
| 1708 | Doors | Solid Core | Laminate | Single leaf | 920mm clear opening, lockable | |
| 3000 | Wall finish | Paint | Acrylic, washable | 2-coat epoxy paint also acceptable | ||
| 2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
| 3052 | Wall finish | Vinyl | Prefinished | Wall vinyl to 1500mm AFFL | 2-coat epoxy paint also acceptable | |
| 5025 | Ceiling | Plasterboard | Paint, epoxy | Flush set, suspended |
| ID | Description | Category | Group | Qty | Selection / Remarks |
| 1010 | Bench: stainless steel | Metalwork | 1 | 1 | |
| 8407 | Sharps disposal: cytotoxic material, 7L | MEQ - General | 3 | 1 | |
| 8629 | Trolley: SS, multi-purpose | MEQ - Furniture | 3 | 1 | |
| 9199 | Waste bin: cytotoxic, 50 litres | MEQ - Furniture | 3 | 1 | |
| 21680 | Stool: adjustable, mobile | Furniture/ Fitting | 3 | 1 | |
| 9101 | Hatch: pass-through | MEQ - Pharmacy | 2 | 1 |
| ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
| 8837 | Cabinet: biological safety, cytotoxic | 2 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | biological safety cytotoxic cabinet or negative pressure cytotoxic isolator may be used. Quantity may change depending on operational requirements |
| ID | Description | Service Category | Qty | Selection / Remarks |
| 1006 | Voice / Data outlet: double | Communications | 1 | to cytotoxic cabinet (optional, refer to manufacturer's specifications) |
| 2189 | General LED | Lighting | ||
| 2726 | PO: UPS, double | Power | 1 | to cytotoxic cabinet |
| 5035 | Special exhaust: hood | HVAC | 1 | to cytotoxic cabinet |
| 5005 | Air conditioning: special | HVAC | HEPA filtered | |
| 3000 | Smoke detectors | Fire Services | and alarm inside room | |
| 5050 | Pressure: negative | HVAC | ||
| 1006 | Voice / Data outlet: double | Communications | 1 | to bench |
| 2578 | PO: Emergency power, double | Power | 1 | to bench |
| 2582 | PO: Single | Power | 1 | hatch (depending on the model) |