Room Code DENI-16-I
Net Room Area Briefed 16
Hours of Operation 8am to 6 pm daily
Occupancy 1 - 2
Description / Special Requirements The Dental Imaging room will be used to provide intraoral imaging such as Orthopantomogram (OPG) or Cone Beam Computed Tomography (CBCT). Radiation shielding as per Radiation Consultant
Amendment 14.06.2019 First Draft 06.09.2022 Cornice updated to aluminium shadow line 19.09.2022 General updates done
ID Fabric Material Finish Specification Selection Remarks
3000 Wall finish Paint Acrylic, washable
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
5007 Ceiling Plasterboard Paint Bulkhead
8040 Door protection Composite Prefinished PVC To door frame
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
9005 Doors Solid Core/ Lead glass Paint Single leaf, observation panel, lead shielding 920mm clear opening
5062 Ceiling Acoustic Prefinished Drop-in tiles, 600x600 mm
6025 Cornice Aluminium Powdercoat shadow line
ID Description Category Group Qty Selection / Remarks
2150 Chair: patient Furniture/ Fitting 3 1
2100 Chair: ergonomic, office Furniture/ Fitting 3 1
5900 Desk Furniture/ Fitting 3 1
8313 Rack: lead apron MEQ - Imaging 1 1
11800 Lead apron Furniture/ Fitting 3 1
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
8902 Dental: X-ray unit, 3D 2 1 yes opt ___ ___ ___ ___ ___ ___
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ wall mounted
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
6110 Downlights: dimmable Lighting
2577 PO: Double Power 2 bench
9040 Body protected Power
12030 Lead lining Shielding to walls and doors as specified
1408 Emergency Stop switch Power 1
2478 Cable conduit Communications 1 between remote control & distribution box
2478 Cable conduit Communications 1 between emergency stop switch & distribution box
2478 Cable conduit Communications 1 for ethernet cable between computer & dental x-ray
2722 Distribution box Power 1 for x-ray & emergency stop switch
2233 Direct connection: Emergency power Power 1 sensor tap
1006 Voice / Data outlet: double Communications 2 1- dental xray unit ; 1-bench
8080 Emergency call Nurse Call 1
1005 Voice / Data outlet: single Communications 1 Wall telephone
2578 PO: Emergency power, double Power 1 1- dental xray unit