Echocardiography

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. $64.99
Online Room Data Sheet
Room Code ECHO-I
Net Room Area Briefed 30
Hours of Operation Available 24 Hours
Occupancy 1 patient; 1 - 2 staff
Description / Special Requirements Room for diagnostic echocardiography procedures including trans-oesophageal echocardiography. Echocardiography procedures may be performed under local anaesthesia. The Echocardiography room should be located close to patient toilet and change rooms. Acoustics: Acoustic privacy required Body Protected electrical area
Amendment 24.10.2010 First Draft 02.05.2011 Description, & services updated 06.09.2022 Cornice changed to aluminium shadow line 18.09.2022 General updates done
ID Fabric Material Finish Specification Selection Remarks
9110 Doors Solid Core Paint 1 1/2 leaf 1400mm clear opening; single leaf to achieve 920mm clear opening
3000 Wall finish Paint Acrylic, washable
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin, other smooth impervious finish also acceptable
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
8040 Door protection Composite Prefinished PVC To door frame
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
5062 Ceiling Acoustic Prefinished Drop-in tiles, 600x600 mm
6025 Cornice Aluminium Powdercoat shadow line
ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1
2150 Chair: patient Furniture/ Fitting 3 2
2100 Chair: ergonomic, office Furniture/ Fitting 3 2
3400 Coathook Metalwork 1 1
4360 Cupboard: door ht adj. shelves Furniture/ Fitting 1 1
4410 Cupboard: under bench Furniture/ Fitting 1 1 adjustable shelves
4460 Cupboard: wall mounted Furniture/ Fitting 1 1 over bench
4700 Curtain track: privacy screen Metalwork 1 1 to entry door
5250 Curtain: privacy screen Furniture/ Fitting 3 1 to entry door
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
8402 Footstool: 2-step MEQ - Furniture 3 1
8309 Oxygen flowmeter MEQ - General 3 1 patient services panel
8318 Suction adapter MEQ - General 3 1 patient services panel
8297 Bracket: suction bottle MEQ - General 2 1
8404 Bracket: sharps disposal MEQ - General 2 1
8593 Bracket: patient monitor MEQ - General 3 1
8321 Suction bottle MEQ - General 3 1
5900 Desk Furniture/ Fitting 3 1
8605 Waste bin: clinical, 20 litres MEQ - Furniture 3 1
8626 Trolley: dressing, 2 drawer MEQ - Furniture 3 1
9117 Sharps disposal: wall mounted, 7L MEQ - General 2 1
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1
21680 Stool: adjustable, mobile Furniture/ Fitting 3 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___
10132 Clock: master clock 3 1 yes opt ___ ___ ___ ___ ___ ___
9090 Ultrasound scanning unit: cardiac/ echo 3 1 yes yes ___ ___ ___ ___ ___ ___
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ to bench
8542 Light: examination, single, ceiling mounted 1 1 yes ___ ___ ___ ___ ___ ___ ___
9043 Warmer: gel 3 1 yes ___ ___ ___ ___ ___ ___ ___
8781 Monitor: physiologic, vital signs, wall mounted 3 1 yes yes ___ ___ ___ ___ ___ ___
8811 Table: examination, echocardiography 3 1 yes ___ ___ ___ ___ ___ ___ ___
11400 Computer: PC & monitor 3 1 yes yes ___ ___ ___ ___ ___ ___
ID Description Service Category Qty Selection / Remarks
1080 Clock: master clock Communications 1 battery/ POE/ electrical connection TBC
2724 Direct connection: Emergency power Power 2 1 - sensor operated tapware, 1 - exam light
9040 Body protected Power
2579 PO: Emergency power, single Power 5 4- patient services panel; 1- patient monitor
2577 PO: Double Power 4 2- computer; 2- bench
2582 PO: Single Power 1 at low level to exam table
8080 Emergency call Nurse Call 1
8010 Staff/ Nurse assist call Nurse Call 1
8005 Patient call handset Nurse Call 1
8000 Patient to Staff call Nurse Call 1
6005 Dimmable Lighting
6055 Special: task light, built in Lighting under O/H cupboards
2242 General LED: colour corrected Lighting
5000 Airconditioning HVAC
1006 Voice / Data outlet: double Communications 4 1- bench; 1- service panel; 1- at low level for ultrasound unit; 1- computer
1005 Voice / Data outlet: single Communications 1 to patient monitor
7000 Oxygen (O2) Medical Gases 1
7040 Suction Medical Gases 1
2578 PO: Emergency power, double Power 1 at low level for ultrasound unit
11000 Wall panel Services Panels 1
2576 PO: Cleaner Power 1
0 0