| Edit it in Health Facility Briefing System (HFBS) | |||
|---|---|---|---|
|
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing | |
| Online Room Data Sheet |
|---|
| Room Code | ENS-BR-I-A |
| Net Room Area Briefed | 10 |
| Hours of Operation | 24 Hours |
| Occupancy | 1 patient; 1-2 staff assisting |
| Description / Special Requirements | The Birthing Room Ensuite is for the Birthing Room patient to wash, shower, use the toilet, and bath as desired for pain relief, either independently or with assistance. The area and layout must accommodate an assisting nurse. The Ensuite will include a shower, handbasin, toilet and an island bath. The island bath will include steps and a seating platform at the bath edge. Acoustics: Sound attenuation level - High. Acoustic privacy required. Body Protected Electrical Area Additional Design Requirements: - The shower floor must not have a raised hob - The entrance is to be flush with the adjoining flooring - The door is to be fitted with escape hardware |
| Amendment | 24.10.10, - First Draft 05.05.11, - Services modified |
| ID | Fabric | Material | Finish | Specification | Selection | Remarks |
| 5023 | Ceiling | Plasterboard | Prefinished | Water resistant, drop in tiles, 600x1200 | ||
| 8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900 AFFL | ||
| 8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
| 9001 | Doors | Solid Core | Paint | Single leaf | 920 clear outward opening, privacy latch, emergency release | |
| 7001 | Windows | optional, obscure glass | ||||
| 1175 | Floor finish | Tiles | Non-slip | Ceramic | vinyl also acceptable | |
| 2145 | Skirting | Tiles | To match floor | Coved | or coved tiled skirting | |
| 3080 | Wall finish | Tiles | Glazed | Full height | vinyl also acceptable | |
| 6025 | Cornice | Aluminium | Powdercoat | shadow line |
| ID | Description | Category | Group | Qty | Selection / Remarks |
| 2300 | Chair: shower | Furniture/ Fitting | 3 | 1 | |
| 3400 | Coathook | Metalwork | 1 | 2 | 1 @ 1200 AFFL for wheelchair users |
| 4800 | Curtain track: shower | Metalwork | 1 | 1 | |
| 5300 | Curtain: shower | Furniture/ Fitting | 3 | 1 | |
| 6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
| 6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | |
| 6156 | Dispenser: soap | Furniture/ Fitting | 2 | 1 | |
| 6160 | Dispenser: toilet paper | Furniture/ Fitting | 1 | 1 | |
| 8400 | Grab rail: WC | Metalwork | 1 | 2 | 1 behind toilet, 1 to side |
| 8430 | Grab rail: Bath | Metalwork | 1 | 1 | |
| 8450 | Grab rail: Shower | Metalwork | 1 | 1 | |
| 8500 | Grab rail: WC, hinged | Metalwork | 1 | 1 | optional, drop down rail |
| 9200 | Hook: for catheter bag | Metalwork | 1 | 3 | |
| 10800 | Hook: for IV flasks | Metalwork | 1 | 3 | |
| 13700 | Mirror | Metalwork | 1 | 1 | over basin |
| 20650 | Soap/ shampoo holder | Furniture/ Fitting | 1 | 1 | |
| 23700 | Towel rail | Metalwork | 1 | 1 | with grab rail strength and fixings |
| 24100 | Waste bin: paper, 20 Litre | Furniture/ Fitting | 3 | 1 | to hand basin |
| ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
| 2800 | Basin: handwash, Type B | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | refer to BHWS-B (sim) |
| 3003 | Bidet handset | 1 | 1 | ___ | ___ | ___ | ___ | yes | yes | ___ | ___ | near toilet |
| 3200 | Bath: patient | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | island, with steps & seating platform |
| 47400 | Shower: hand-held | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | |
| 47400 | Shower: hand-held | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | low level over bath |
| 55605 | Toilet suite: patient | 1 | 1 | ___ | ___ | yes | ___ | ___ | yes | yes | ___ |
| ID | Description | Service Category | Qty | Selection / Remarks |
| 4033 | Floor waste | Hydraulics | 2 | |
| 5000 | Airconditioning | HVAC | ||
| 5019 | Exhaust | HVAC | for steam/ heat | |
| 6001 | General: colour corrected | Lighting | ||
| 7000 | Oxygen (O2) | Medical Gases | 1 | Optional |
| 7010 | Nitrous Oxide (N2O) | Medical Gases | 1 | Optional |
| 7070 | Scavenge | Medical Gases | 1 | Optional |
| 8000 | Patient/ Staff call | Nurse Call | 3 | + indicator button & light |
| 8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
| 8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
| 2577 | PO: Double | Power | 1 | locate near door outside room |
| 9040 | Body protected | Power | ||
| 2587 | PO: Special: for equipment | Power | 1 | for hair dryer & shaver use only; to comply with relevant electric safety guidelines |