| Edit it in Health Facility Briefing System (HFBS) | |||
|---|---|---|---|
|
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing | |
| Online Room Data Sheet |
|---|
| Room Code | ENS-BR-I-B |
| Net Room Area Briefed | 5 |
| Hours of Operation | 24 Hours |
| Occupancy | 1 patient; 1 staff assisting |
| Description / Special Requirements | An Ensuite, Birthing Room is for the patient to wash, shower and use the toilet, either independently or with assistance. The area and layout must accommodate an assisting nurse, and wheelchair access. The Ensuite will have direct access from the Birthing Room. Acoustics: Sound attenuation level - High. Acoustic privacy required. Body Protected Electrical Area Additional Design Requirements: - The shower floor must not have a raised hob - The entrance is to be flush with the adjoining flooring - The door is to be fitted with escape hardware |
| Amendment | 24.10.10, - First Draft 05.05.11, - Services modified |
| ID | Fabric | Material | Finish | Specification | Selection | Remarks |
| 5023 | Ceiling | Plasterboard | Prefinished | Water resistant, drop in tiles, 600x1200 | ||
| 8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900 AFFL | ||
| 9001 | Doors | Solid Core | Paint | Single leaf | 920 clear outward opening, privacy latch, emergency release | |
| 8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
| 1175 | Floor finish | Tiles | Non-slip | Ceramic | vinyl also acceptable | |
| 2145 | Skirting | Tiles | To match floor | Coved | or coved floor vinyl skirting | |
| 3080 | Wall finish | Tiles | Glazed | Full height | to wet areas; vinyl also acceptable | |
| 3000 | Wall finish | Paint | Acrylic, washable | |||
| 6025 | Cornice | Aluminium | Powdercoat | shadow line |
| ID | Description | Category | Group | Qty | Selection / Remarks |
| 2300 | Chair: shower | Furniture/ Fitting | 3 | 1 | optional |
| 3400 | Coathook | Metalwork | 1 | 2 | 1 @ 1200 AFFL for wheelchair users |
| 4800 | Curtain track: shower | Metalwork | 1 | 1 | |
| 5300 | Curtain: shower | Furniture/ Fitting | 3 | 1 | |
| 6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | |
| 6156 | Dispenser: soap | Furniture/ Fitting | 2 | 1 | |
| 6160 | Dispenser: toilet paper | Furniture/ Fitting | 1 | 1 | |
| 8400 | Grab rail: WC | Metalwork | 1 | 2 | 1 behind toilet, 1 to side |
| 8450 | Grab rail: Shower | Metalwork | 1 | 1 | |
| 8500 | Grab rail: WC, hinged | Metalwork | 1 | 1 | optional |
| 9200 | Hook: for catheter bag | Metalwork | 1 | 2 | |
| 10800 | Hook: for IV flasks | Metalwork | 1 | 2 | |
| 13700 | Mirror | Metalwork | 1 | 1 | over basin |
| 19100 | Waste bin: sanitary | Furniture/ Fitting | 3 | 1 | |
| 20650 | Soap/ shampoo holder | Furniture/ Fitting | 1 | 1 | |
| 23700 | Towel rail | Metalwork | 1 | 1 | with grab rail strength and fixings |
| 24100 | Waste bin: paper, 20 Litre | Furniture/ Fitting | 3 | 1 | to hand basin |
| ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
| 2850 | Basin: handwash, Type C | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | refer to BHWS-C (sim) |
| 3003 | Bidet handset | 1 | 1 | ___ | ___ | ___ | ___ | yes | yes | ___ | ___ | near toilet |
| 47400 | Shower: hand-held | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | |
| 55605 | Toilet suite: patient | 1 | 1 | ___ | ___ | yes | ___ | ___ | yes | yes | ___ |
| ID | Description | Service Category | Qty | Selection / Remarks |
| 4033 | Floor waste | Hydraulics | 1 | |
| 5000 | Airconditioning | HVAC | ||
| 5019 | Exhaust | HVAC | for steam/ heat | |
| 2189 | General LED | Lighting | ||
| 8000 | Patient/ Staff call | Nurse Call | 2 | + indicator button & light |
| 8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
| 8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
| 2577 | PO: Double | Power | 1 | locate near door outside room |
| 9040 | Body protected | Power | ||
| 2587 | PO: Special: for equipment | Power | 1 | for hair dryer & shaver use only; to comply with relevant electric safety guidelines |