Room Code | FLUOC-I |
Net Room Area Briefed | 12 |
Hours of Operation | Available 24 Hours |
Occupancy | Up to 2 staff |
Description / Special Requirements | Room adjacent to Fluoroscopy Room/s with direct visibility to the patient's full body for remote control of equipment, and review and reporting of procedure images. The separate Control Room may be required depending on the procedure to be performed in the Fluoroscopy Room. Acoustics: Acoustic privacy is required Additional Design Considerations: - Radiation shielding as advised by Radiation Consultant - Cable ducts from Fluoroscopy room may be required |
Amendment | 25.06.2019 First Draft 26.05.2023 RDS reviewed |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
1219 | Door Protection | Composite | Prefinished PVC | Kickplate, 300mm high | ||
4159 | Cornice | Aluminium | Powdercoat | Angle flush against wall, in line with ceiling grid | ||
7025 | Observation | Lead glass | Clear | Internal window | to Fluoroscopy Room | |
5062 | Ceiling | Acoustic | Prefinished | Drop-in tiles, 600x600 mm | or set plasterboard ceiling if Fluoroscopy Room is provided within an operating environment | |
9001 | Doors | Solid Core | Paint | Single leaf | staff entry/ exit; 920mm clear opening |
ID | Description | Category | Group | Qty | Selection / Remarks |
2100 | Chair: ergonomic, office | Furniture/ Fitting | 3 | 2 | |
5598 | Shelving unit: adjustable, full height | Furniture/ Fittings | 1 | 1 | manuals, educational material |
9100 | Hook: heavy duty | Metalwork | 1 | 2 | for lead aprons |
1050 | Bench: laminate | Furniture/ Fitting | 1 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
11400 | Computer: PC & monitor | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
54510 | Telephone: handset, standard | 3 | 1 | ___ | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
9092 | Control console | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | fluoroscopy control console |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 3 | to control console and computers |
1040 | Intercom | Communications | 1 | with handsfree microphone to Fluoroscopy room |
5000 | Airconditioning | HVAC | ||
2189 | General LED | Lighting | ||
12011 | Radiation shielding | Shielding | to wall, door & glazing shared with Fluoroscopy Room as specified by Radiation Consultant | |
6076 | Special: 'X-ray In Use' lights | Lighting | 1 | over door to Fluoroscopy Room |
2578 | PO: Emergency power, double | Power | 1 | to wall |
2726 | PO: UPS, double | Power | 6 | to control console and computers |