Neonatal Bay - Resuscitation

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an editable Revit Room Layout Sheet (RLS) for this standard component. $64.99
Online Room Data Sheet
Room Code NB-R-I
Net Room Area Briefed 4
Hours of Operation 24 Hours
Occupancy 1 baby; up to 4 staff
Description / Special Requirements The Neontal Resuscitation Bay is a bay for assessment, resuscitation, treatment and transfer preparation of Neonates with critical conditions. A scrub basin must be located in close proximity. Resuscitation diagnostic equipment such as infant resuscitation trolley, and ventilator must be provided. Isolated power (IPS) must be provided. Cardiac Protected electrical area
Amendment
ID Fabric Material Finish Specification Selection Remarks
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
4031 Wall protection Composite Prefinished PVC Corner guards to 1500mm AFFL as required, other heights also acceptable as per project standardisation
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
3092 Wall protection MDF Laminate Bed protection wall panel
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
6025 Cornice Aluminium Powdercoat shadow line
ID Description Category Group Qty Selection / Remarks
4600 Curtain track: bed screen Metalwork 1 1
5000 Curtain: bed screen Furniture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
8291 Air flowmeter MEQ - General 3 1
8321 Suction bottle MEQ - General 3 1
8297 Bracket: suction bottle MEQ - General 2 1
8311 Oxygen flowmeter: low flow MEQ - General 3 1
8319 Suction adapter: low flow MEQ - General 3 1 to baby
8404 Bracket: sharps disposal MEQ - General 2 1 mounted to trolley
8406 Sharps disposal: on trolley, 11L MEQ - General 3 1
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1 to basin
8399 Trolley: resuscitation, neonatal MEQ - Furniture 3 1 or in a nearby resuscitation bay
8593 Bracket: patient monitor MEQ - General 2 1 optional
8594 Linen carrier: dirty, single MEQ - Furniture 3 1
8922 Laryngoscope set: fiber optic, neonatal MEQ - General 3 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3100 Basin: scrub, Type A 1 1 ___ ___ yes ___ yes yes yes ___ in close proximity
8954 Warmer unit: neonatal, with resuscitation 3 1 yes opt ___ ___ ___ ___ ___ ___
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout
8778 Monitor: physiologic, critical care, neonatal 3 1 yes yes ___ ___ ___ ___ ___ ___ optional
8973 Pump: suction/ aspirator, portable 3 1 yes ___ ___ ___ ___ ___ ___ ___ or in a nearby resuscitation bay
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 per cot space
5000 Airconditioning HVAC
2242 General LED: colour corrected Lighting
7000 Oxygen (O2) Medical Gases 1 per cot space
7020 Medical Air (MA) Medical Gases 1 per cot space
7040 Suction Medical Gases 1 per cot space
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
9040 Body protected Power
2724 Direct connection: Emergency power Power 1 sensor operated tapware
6829 PO: Isolated Power Suppy (IPS), single Power 6 per cot space
11000 Wall panel Services Panels 1 patient services
1005 Voice / Data outlet: single Communications 1 to patient monitor (optional)
2579 PO: Emergency power, single Power 1 to patient monitor (optional)
0 0