Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. | $64.99 |
Online Room Data Sheet |
---|
Room Code | OR-TR-I |
Net Room Area Briefed | 55 |
Hours of Operation | 24 Hours |
Occupancy | 1 patient; 5 - 12 staff |
Description / Special Requirements | The Operating Room - Large is a digital operating room which provides a fully digital integrated aseptic environment in which to carry out surgical procedures under local, regional or general anaesthetic. This operating room will include an integration system that will centralize the information from difference equipments, softwares and video sources and enable the routing of videos to different displays located within the room and optionally to locations outside of the operating theatre for video conferencing. The Operating Room - Large may be used for a range of surgical procedures including specialty surgery. The Operating Room will have direct access to a Scrub-up Room, exit bay and sterile stock/set-up area. Cardiac Protected electrical area Special Air Conditioning - HEPA filtration Additional Design Considerations: - Minimum critical dimension 6000mm on at least 1 side. - Associated rooms and layout to be considered in total - Square room shape preferable - 'Laser in Use' warning lights may be required outside exit doors to room if laser is to be used - Lead shielding may be required depending on use of X-ray equipment - to be assessed by Radiation consultant |
Amendment | 10.03.2023 RDS updated 16.05.2024 Fabrics & Services updated |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
6015 | Cornice | Plasterboard | Paint | Flush coved between wall & ceiling | ||
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
9245 | Doors | Solid Core/ Safety glass | Paint | Double leaf, observation panel | 1600mm clear opening to patient entry/exit and scrub room; obs panel with sliding cover or internal venetians | |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
5020 | Ceiling | Plasterboard | Paint, scrub resistant | Flush set, suspended | 3000mm min height AFFL | |
9127 | Doors | Solid Core/ Safety glass | Paint | 1 1/2 leaf, observation panel | 1600mm clear opening to induction room; obs panel with sliding cover or integral venetians | |
9001 | Doors | Solid Core | Paint | Single leaf | Optional; 1100mm clear opening to clean-up room | |
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
2313 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 300mmH | ||
3010 | Wall finish | Paint | Scrub resistant | epoxy paint or full height wall vinyl also acceptable | ||
9006 | Doors | Solid Core/ Safety glass | Paint | Single leaf, observation panel | 920mm clear opening to sterile stock room/ setup room, obs panel with sliding cover or integral venetians |
ID | Description | Category | Group | Qty | Selection / Remarks |
1030 | Bench: resinate | Furniture/ Fitting | 1 | 1 | documentation station: computers, write-up |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
8291 | Air flowmeter | MEQ - General | 3 | 2 | to services pendants |
8296 | Bowl stand: single | MEQ - General | 3 | 2 | |
8297 | Bracket: suction bottle | MEQ - General | 2 | 4 | |
8306 | IV pole: mobile | MEQ - General | 3 | 2 | |
8309 | Oxygen flowmeter | MEQ - General | 3 | 4 | to services pendants |
8318 | Suction adapter | MEQ - General | 3 | 4 | to services pendants |
8321 | Suction bottle | MEQ - General | 3 | 4 | |
8343 | Cabinet: storage, instrument, OR, double door, recessed | MEQ - Furniture | 2 | 2 | |
8385 | Carrier stand, suction canisters | MEQ - General | 3 | 1 | |
8398 | Trolley: resuscitation | MEQ - Furniture | 3 | 1 | |
8408 | Kick bucket | MEQ - General | 3 | 2 | |
8411 | Stool: adjustable, OR | MEQ - Furniture | 3 | 2 | |
8412 | Stool: adjustable, OR, with backrest | MEQ - Furniture | 3 | 1 | for anaesthetist |
8593 | Bracket: patient monitor | MEQ - General | 2 | 1 | for cardiac monitor, mounted on anaesthesia pendant |
8594 | Linen carrier: dirty, single | MEQ - Furniture | 3 | 2 | |
8603 | Headlight: surgical | MEQ - General | 3 | 1 | |
8620 | Trolley: instrument | MEQ - Furniture | 3 | 3 | |
8622 | Trolley: gowns | MEQ - Furniture | 3 | 1 | |
8627 | Trolley: anaesthetic | MEQ - Furniture | 3 | 1 | |
8630 | Table: mayo | MEQ - Furniture | 3 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
6468 | Camera: in room | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | PTZ, optional part of integration system |
8472 | Infusion pump: syringe | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | Qty TBC by project |
8473 | Infusion pump: rapid, blood/ solution warming, on stand | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | Qty TBC by project |
8714 | Anaesthesia unit: standard | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
8548 | Light: surgical, single, ceiling, with two monitor arms & camera | 2 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | light configurations may change depending on OR integration system requirements |
8767 | Defibrillator: with monitor | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
8941 | Integration system: OR, HD | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, includes 2 display monitors and 1 control monitor in the surgical field, 2 display monitor on the wall, and 1 control monitor on the nurse workstation |
8786 | Supply unit: ceiling, double arm | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | surgical pendant |
8822 | Warming cabinet: dual compartment, freestanding, 500L | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional |
8953 | Hypo-hyperthermia unit: general | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
8966 | Monitor: video, medical grade, HD, 19-inch | 3 | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, control monitors part of integration system |
8967 | Monitor: video, medical grade, HD, 26-inch | 3 | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, display monitors part of integration system |
8970 | Monitor: video, medical grade, HD, 55-inch | 3 | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, wall mounted part of integration system |
8973 | Pump: suction/ aspirator, portable | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
8989 | Infusion pump: single channel | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | Qty TBC by project |
9023 | Tracking system: instrument tray | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, workstation part of CSSD instrument tracking system |
9222 | Control panel: surgical, recessed | 2 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | includes slave analogue clock, elapsed time clock, temperature and humidity indicators and controls, IPS and UPS systems alarms, medical gas alarms, AGSS controls, theatre lamp controls, general lighting controls and power sockets as required |
9597 | Supply unit: ceiling, anaesthesia, tandem, double arm | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | anaesthesia pendant |
10173 | Cabinet: server, OR integration | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional, part of integration system |
11400 | Computer: PC & monitor | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | for nursing & medical staff documentation |
54520 | Telephone: handset, handsfree | 3 | 1 | ___ | yes | ___ | ___ | ___ | ___ | ___ | ___ | on bench |
8779 | Monitor: physiologic, operating theatre/ cardiac | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | on anaesthesia pendant |
8924 | Electrosurgical unit: monopolar/ bipolar | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
8952 | Smoke evacuation system, surgical | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
9067 | Operating table: mobile, electric, general | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
9547 | Medication dispensing system: automated, anaesthesia | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, quantity and modules depend on service requirements; with this option anaesthetic trolley may not be required |
10389 | Light: surgical, single, ceiling, with monitor arm | 2 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | light configurations may change depending on OR integration system requirements |
13363 | Pump: suction/ aspirator, surgical, mobile | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 2 | to nurse documentation station |
1005 | Voice / Data outlet: single | Communications | 2 | 1- telephone; 1- anaesthesia medication dispensing unit (optional) |
1379 | Audio/ Video outlet | Communications | 8 | for services pendants; 2- per anaesthetic arm, 4- surgical pendant |
1006 | Voice / Data outlet: double | Communications | 2 | for walls |
6005 | Dimmable | Lighting | ||
2726 | PO: UPS, double | Power | 3 | optional (part of integration system); for 1- 19" control monitor and 2- 26" display monitors within the surgical field (1 each) |
2726 | PO: UPS, double | Power | 3 | optional (part of integration system); 1- 19" wall mounted control monitor, 2- 55" wall monitors (1 each) |
1006 | Voice / Data outlet: double | Communications | 3 | optional (part of integration system); for 1- 19" control monitor and 2- 26" display monitors within the surgical field (1 each) |
1006 | Voice / Data outlet: double | Communications | 3 | optional (part of integration system); 1- 19" wall mounted control monitor, 2- 55" wall monitors (1 each) |
12011 | Radiation shielding | Shielding | for walls, floor, ceiling, doors & glazing as specified by Radiation Consultant | |
2726 | PO: UPS, double | Power | 1 | optional; anaesthesia medication dispensing unit |
2726 | PO: UPS, double | Power | 2 | optional (part of integration system); for integration system server cabinet |
2726 | PO: UPS, double | Power | 2 | for nurse documentation station |
2757 | Direct connection: Uninterrupted power | Power | 1 | optional (part of integration system) ; for in room camera |
2757 | Direct connection: Uninterrupted power | Power | 3 | 1- surgical control panel, 2- operating lights (1 each) |
2761 | Direct connection: Tool Air | Medical Gases | 2 | 1 per pendant (for brakes) |
2760 | Direct connection: Voice/ Data | Communications | 1 | for surgical control panel (to be integrated with BMS & lighting controls) |
2760 | Direct connection: Voice/ Data | Communications | 2 | 1- in room camera (optional, part of integration system), 1 - operating light camera attachment |
2726 | PO: UPS, double | Power | 2 | for walls |
2578 | PO: Emergency power, double | Power | 2 | 1- resuscitation trolley; 1- warming cabinet (optional) |
2578 | PO: Emergency power, double | Power | 2 | for walls |
2756 | Cable conduit | Electrical | 1 | optional (part of integration system); for integration system server cabinet |
1006 | Voice / Data outlet: double | Communications | 8 | to services pendants; 2- per anaesthetic arm, 4- surgical pendant |
2728 | PO: Single phase, high current, 32 Amp | Power | 1 | optional; for laser on wall |
2724 | Direct connection: Emergency power | Power | 2 | for pendants |
2723 | PO: Cardiac Protected/IPS, single | Power | 24 | for services pendants; 6- per anaesthetic arm, 12- surgical arm |
9030 | Cardiac protected/ IPS | Power | ||
2576 | PO: Cleaner | Power | 1 | |
8090 | Orderly/ Porter call | Nurse Call | 1 | optional; to anaesthesia pendant |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light; to anaesthesia pendant |
7070 | Scavenge | Medical Gases | 2 | 1- per anaesthetic pendant arm |
7040 | Suction | Medical Gases | 4 | 1- per anaesthetic pendant arm; 2- surgical pendant |
7020 | Medical Air (MA) | Medical Gases | 2 | 1- anaesthesia pendant; 1- surgical pendant |
7010 | Nitrous Oxide (N2O) | Medical Gases | 2 | 1- per anaesthetic pendant arm |
7000 | Oxygen (O2) | Medical Gases | 4 | 1- per anaesthetic pendant arm; 2- surgical pendant |
6074 | Special: 'Laser In Use' lights | Lighting | outside room entries, if laser to be used (optional) | |
2242 | General LED: colour corrected | Lighting | variable lighting level | |
5040 | Pressure: positive | HVAC | ||
5005 | Air conditioning: special | HVAC | HEPA filtered | |
2024 | Music system | Communications | 1 | optional |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light; to anaesthesia pendant |
1947 | Carbon Dioxide (CO2) | Medical Gases | 1 | 1- surgical pendant (optional) |
2694 | PO: UPS, single | Power | 2 | optional; to loudspeaker and on-air lamp (part of integration system - refer to manufacturer's specifications) |
1379 | Audio/ Video outlet | Communications | 3 | optional (part of integration system); for 1- 19" control monitor and 2- 26" display monitors within the surgical field (1 each) |
1379 | Audio/ Video outlet | Communications | 3 | optional (part of integration system); 1- 19" wall mounted control monitor, 2- 55" wall monitors (1 each) |
6870 | Surgical Air (SA7) | Medical Gases | 2 | 2- surgical pendant |
6909 | Wave pad access | Security | 4 | 2- patient entry door; 2- anaesthetic induction door (if provided) |