Patient Bay - Acute Treatment, 12m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. $64.99
Online Room Data Sheet
Room Code PBTR-A12-I
Net Room Area Briefed 12
Hours of Operation 24 Hours
Occupancy 1 patient; 1 - 2 staff
Description / Special Requirements The Patient Bed Bay Acute Treatment may be used for assessment and treatment of patients with acute conditions and will be located within the Emergency Unit. The Bay may have partition side walls; glazing is recommended. The Patient Bay will have close access to a staff handwashing basin. Body Protected electrical area
Amendment 24.10.2010 First Draft 01.09.2022 FF, FE & Services updated 19.09.2022 General updates done 03.09.2023 RDS updated
ID Fabric Material Finish Specification Selection Remarks
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
4031 Wall protection Composite Prefinished PVC Corner guards to 1500mm AFFL as required; other heights also acceptable as per project standardisation
3000 Wall finish Paint Acrylic, washable
3092 Wall protection MDF Laminate Bed protection wall panel
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
4020 Wall protection Composite Prefinished PVC Crash rail at 900mm AFFL as required
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2767 Cornice Plasterboard Paint Square set
1253 Observation Alum/ Toughened glass Powdercoat Internal window, double glazed to partition walls if provided
ID Description Category Group Qty Selection / Remarks
8291 Air flowmeter MEQ - General 3 1
1090 Bench: laminate, free standing Furniture/ Fitting 3 1 optional
1252 Blind: Venetian integral Furniture/ Fitting 1 2 to internal windows if provided
8297 Bracket: suction bottle MEQ - General 2 2
8404 Bracket: sharps disposal MEQ - General 2 1
2650 Chair: visitor, patient Furniture/ Fitting 3 1
4600 Curtain track: bed screen Metalwork 1 1
5000 Curtain: bed screen Furniture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
10700 IV hanger for ceiling track Metalwork 1 1 optional
11200 IV track: ceiling mounted Metalwork 1 1 optional
8593 Bracket: patient monitor MEQ - General 3 1 optional, may have ergonomic arm
8309 Oxygen flowmeter MEQ - General 3 2
19800 Shelf: laminate Furniture/ Fitting 1 1 above services panel, optional
8982 Stretcher: procedure/ recovery MEQ - Furniture 3 1
8306 IV pole: mobile MEQ - General 3 1
8616 Trolley: procedure MEQ - Furniture 3 1
8318 Suction adapter MEQ - General 3 2
8321 Suction bottle MEQ - General 3 2
8594 Linen carrier: dirty, single MEQ - Furniture 3 1
8605 Waste bin: clinical, 20 litres MEQ - Furniture 3 1
8626 Trolley: dressing, 2 drawer MEQ - Furniture 3 1
9117 Sharps disposal: wall mounted, 7L MEQ - General 2 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
9456 Light: procedure, single, ceiling mounted 1 1 yes ___ ___ ___ ___ ___ ___ ___
8746 Diagnostic set: wall mounted 3 1 yes ___ ___ ___ ___ ___ ___ ___ optional
8989 Infusion pump: single channel 3 1 yes opt ___ ___ ___ ___ ___ ___
8776 Monitor: physiologic, acute care 3 1 yes yes ___ ___ ___ ___ ___ ___ optional
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 1- patient services panel; 1- bench
5000 Airconditioning HVAC
6001 General: colour corrected Lighting
7000 Oxygen (O2) Medical Gases 2 patient services panel
7010 Nitrous Oxide (N2O) Medical Gases 1 patient services panel, optional
7020 Medical Air (MA) Medical Gases 1 patient services panel
7040 Suction Medical Gases 2 patient services panel
7070 Scavenge Medical Gases 1 patient services panel, if N2O provided
8000 Patient to Staff call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
2582 PO: Single Power 3 patient services panel
2582 PO: Single Power 2 1- diagnostic set; 1- at low level next to stretcher
9040 Body protected Power
11000 Wall panel Services Panels 1
1005 Voice / Data outlet: single Communications 1 1- patient monitor
2233 Direct connection: Emergency power Power 1 to procedure light
2578 PO: Emergency power, double Power 2 to bench
2579 PO: Emergency power, single Power 3 patient services panel
2579 PO: Emergency power, single Power 1 to patient monitor
0 0