Room Code PBHE-12-I
Net Room Area Briefed 12
Hours of Operation 24 Hours
Occupancy 1 patient; 1 - 2 staff intermittently
Description / Special Requirements An enclosed Patient Bed Bay used for holding patients prior to procedures, observation of patients following procedures and/or assessment and treatment of patients with non acute conditions. Each bay must be large enough to accommodate an adult bed with additional space for monitoring equipment and to ensure access for staff in case of emergency. Each bay or cubicle shall have a minimum clearance of 91.44 centimeters (3 feet) between walls or partitions and the sides and foot of stretchers or patient beds. The Enclosed Patient Bay may be used for isolation of patients and will contain a staff handwashing basin. Patient toilets and emergency equipment should be readily accessible. Body Protected electrical area
Amendment 24.10.2010 First Draft 31.01.2017 Description, Fabric, FF, FE, Services updated 03.09.2023 RDS updated
ID Fabric Material Finish Specification Selection Remarks
4020 Wall protection Composite Prefinished PVC Crash rail at 900mm AFFL
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin, other smooth impervious finish also acceptable
3000 Wall finish Paint Acrylic, washable
3092 Wall protection MDF Laminate Bed protection wall panel
7001 Windows desirable
9010 Doors Alum/ Toughened glass Powdercoat/ paint Single leaf, fully glazed 1200mm clear opening, sliding, surface mounted
7035 Observation Alum/ Glass Powdercoat Internal window optional to front and side walls
2767 Cornice Plasterboard Paint Square set
ID Description Category Group Qty Selection / Remarks
1252 Blind: Venetian integral Furniture/ Fitting 1 2 to internal & external windows
2650 Chair: visitor, patient Furniture/ Fitting 3 1 optional
4600 Curtain track: bed screen Metalwork 1 1
5000 Curtain: bed screen Furniture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
8291 Air flowmeter MEQ - General 3 1 optional
8297 Bracket: suction bottle MEQ - General 2 1
8309 Oxygen flowmeter MEQ - General 3 1
8318 Suction adapter MEQ - General 3 1
8321 Suction bottle MEQ - General 3 1
8332 Table: overbed MEQ - Furniture 3 1 optional
8404 Bracket: sharps disposal MEQ - General 2 1
8982 Stretcher: procedure/ recovery MEQ - Furniture 3 spatial provision required
9117 Sharps disposal: wall mounted, 7L MEQ - General 2 1
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___
8542 Light: examination, single, ceiling mounted 1 1 yes ___ ___ ___ ___ ___ ___ ___ optional, depending on use of the bay
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 to bedhead
5000 Airconditioning HVAC
2242 General LED: colour corrected Lighting
7000 Oxygen (O2) Medical Gases 1
7020 Medical Air (MA) Medical Gases 1 optional
7040 Suction Medical Gases 1
8000 Patient to Staff call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
2582 PO: Single Power 3 to bedhead
2582 PO: Single Power 1 to bedhead, low level for bed
2579 PO: Emergency power, single Power 3 to bedhead
2576 PO: Cleaner Power 1
9040 Body protected Power
11000 Wall panel Services Panels 1 flush mounted, patient services
6030 Special: downlights Lighting over bed/ trolley
2724 Direct connection: Emergency power Power 2 1 - to sensor operated tapware, 1 - exam light (optional)
6005 Dimmable Lighting for night lighting