Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. | $64.99 |
Online Room Data Sheet |
---|
Room Code | PBC-6-I |
Net Room Area Briefed | 6 |
Hours of Operation | 0800 Hours to 1800 Hours, daily |
Occupancy | 1 patient, 1support person, 1 staff assisting |
Description / Special Requirements | The Patient Chair Bay - is used for treatment of patients that do not require a bed and may be located in Emergency Units, Recovery Stages 2/3 and Day Therapy units. Medical Gases may be shared between bays, depending on the patient profile. One staff handwashing basin should be provided to each of 4 bays (refer to Bay-Handwashing Type B). Body Protected electrical area |
Amendment | 27.05.2016 First Issue |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
7001 | Windows | External windows desirable | ||||
3092 | Wall protection | MDF | Laminate | Bed protection wall panel | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | ||
6030 | Cornice | Aluminium | Powdercoat | 24mm shadow angle |
ID | Description | Category | Group | Qty | Selection / Remarks |
150 | Air flowmeter | Furniture/ Fitting | 3 | 1 | |
1260 | Blind: holland | Metalwork | 3 | 1 | to external windows; cleanable |
1465 | Bracket: suction bottle | Furniture/ Fitting | 2 | 1 | |
2200 | Chair: recliner | Furniture/ Fitting | 3 | 1 | |
2650 | Chair: visitor, patient | Furniture/ Fitting | 3 | 1 | |
4600 | Curtain track: bed screen | Metalwork | 1 | 1 | |
5000 | Curtain: bed screen | Furniture/ Fitting | 3 | 1 | |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
6387 | Storage bins: for louvred panels | Furniture/ Fitting | 3 | 3 | |
6547 | Louvred panel: small for storage-bins | Furniture/ Fitting | 1 | 1 | |
6174 | Dispenser: hand gel | Furniture/ Fitting | 2 | 1 | |
16250 | Oxygen flowmeter | Furniture/ Fitting | 3 | 1 | |
21950 | Suction adapter | Furniture/ Fitting | 3 | 1 | |
22000 | Suction bottle | Furniture/ Fitting | 3 | 1 | |
23400 | Bracket: television, ceiling | Metalwork | 1 | 1 | optional: ceiling mounted |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
3031 | Television: flat screen | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional |
31700 | Light: examination, ceiling | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 1 | optional |
5000 | Airconditioning | HVAC | ||
2189 | General LED | Lighting | ||
6050 | Special: reading | Lighting | ||
7000 | Oxygen (O2) | Medical Gases | 1 | may be shared between 2 bays depending on use of the bay |
7020 | Medical Air (MA) | Medical Gases | 1 | may be shared between 2 bays depending on use of the bay |
7040 | Suction | Medical Gases | 1 | may be shared between 2 bays depending on use of the bay |
8000 | Patient/ Staff call | Nurse Call | 1 | + indicator button & light |
8005 | Patient call handset | Nurse Call | 1 | call button on the handset. |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
2582 | PO: Single | Power | 3 | to patient services panel |
2579 | PO: Emergency power, single | Power | 1 | to patient services panel |
9040 | Body protected | Power | ||
2587 | PO: Special: for equipment | Power | 1 | optional, to ceiling mounted TV |
1090 | TV: MATV | Communications | 1 | optional |
6200 | Light switches | Lighting | 1 | to reading light |