| Room Code | PRAR-20-I |
| Net Room Area Briefed | 20 |
| Hours of Operation | Available 24 Hours |
| Occupancy | Up to 8 |
| Description / Special Requirements | The Prayer Room is provided for use by visitors, patients and staff. Recommended to have an Ablution area located immediately outside. Acoustics: Sound attenuation level high; Acoustic privacy required. Special Design Considerations: - where possible, alignment of room shall be directed towards the Kaaba direction. |
| Amendment | 24.10.2010 First Draft 03.09.2023 RDS updated |
| ID | Fabric | Material | Finish | Specification | Selection | Remarks |
| 1088 | Skirting | Timber | Paint | 150mmH x 20mm thick nominal | MDF also acceptable | |
| 1161 | Floor finish | Carpet | 90/10 Wool/ Nylon | Broadloom, decorative feature | ||
| 4159 | Cornice | Aluminium | Powdercoat | Angle flush against wall, in line with ceiling grid | ||
| 1219 | Door Protection | Composite | Prefinished PVC | Kickplate, 300mm high | ||
| 3000 | Wall finish | Paint | Acrylic, washable | |||
| 9001 | Doors | Solid Core | Paint | Single leaf | 920mm clear opening | |
| 5062 | Ceiling | Acoustic | Prefinished | Drop-in tiles, 600x600 mm | ||
| 3067 | Wall finish | Laminate | Prefinished | wall panel | ||
| 3057 | Wall finish | Vinyl | Prefinished | Vinyl wall paper full height |
| ID | Description | Category | Group | Qty | Selection / Remarks |
| 2400 | Chair: stackable | Furniture/ Fitting | 3 | 6 | as required |
| 20010 | Shelving unit | Furniture/ Fitting | 1 | 1 | wall mounted |
| 23410 | Bracket: television, wall mount | Metalwork | 2 | 1 | for TV, if provided |
| ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
| 3031 | Television: flat screen | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional |
| 10132 | Clock: master clock | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ |
| ID | Description | Service Category | Qty | Selection / Remarks |
| 1006 | Voice / Data outlet: double | Communications | 1 | |
| 2559 | IPTV | Communications | 1 | for TV, if provided |
| 5000 | Airconditioning | HVAC | ||
| 2189 | General LED | Lighting | ||
| 2577 | PO: Double | Power | 1 | wall |
| 1080 | Clock: master clock | Communications | 1 | battery/ POE/ electrical connection TBC |
| 2582 | PO: Single | Power | 1 | TV (optional) |
| 2576 | PO: Cleaner | Power | 1 |