Online Room Data Sheet
Room Code WCAC-I
Net Room Area Briefed 6
Hours of Operation 24 Hours
Occupancy 1
Description / Special Requirements A toilet and handbasin for use by disabled persons with or without assistance. The room shall comply with relevant accessibility standards. Baby change facilities may also be located in this room. The room may be used by patients or visitors. If the Accessible Toilet is located in a patient care area the patient/ nurse call and emergency call points should be included. An Accessible toilet should be provided if it is the only toilet in the area. Additional Design Considerations: - Consideration may be given to installation of an additional small hand basin adajcent to the toilet that would allow wheelchair users to rinse and dry their hands from a seated position before transferring back onto their wheelchair, assisting with infection control. Ensure this basin does not impede wheelchair to toilet transfers or circulation space. - A shelf may be provided adjacent to the toilet for personal items. If provided, this shelf should be approximately 950mm AFFL and placed so that it will not be used as a support by semi ambulant users - WC design may be chosen to ensure flush controls are mounted on the open (transfer) side of the toilet to ensure they are reachable by a wheelchair user facing the toilet Acoustics: Sound attenuation level - High - Acoustic privacy.
Amendment 24.10.2010 First Draft 19.05.2011 Room area, Description, FE & Services Remarks modified 27.07.2015 Description and Fabric updated 18.01.2017 Fabric & Services amended 05.09.2022 Fabrics, FF, FE, Services updated 06.09.2022 Updated floor to vinyl and backsplash to resinate 03.09.2023 RDS updated
ID Fabric Material Finish Specification Selection Remarks
3000 Wall finish Paint Acrylic, washable
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL both sides
8040 Door protection Composite Prefinished PVC To door frame both sides
6025 Cornice Aluminium Powdercoat shadow line
9001 Doors Solid Core Paint Single leaf 920mm clear opening, privacy latch, emergency release
3795 Ceiling Plasterboard Prefinished Water resistant, drop-in tiles, 600x600mm set water resistant plasterboard ceiling also acceptable
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH or tile coved skirting if tile floor is used
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin, other smooth impervious finish also acceptable
1045 Floor finish Vinyl, non slip Textured Seamless, coved tiles also acceptable
ID Description Category Group Qty Selection / Remarks
390 Baby change table Furniture/ Fitting 1 1 optional
3400 Coathook Metalwork 1 2 1 @ 1200 AFFL for wheelchair users
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to handbasin
6156 Dispenser: soap Furniture/ Fitting 1 1 to handbasin
6160 Dispenser: toilet paper Furniture/ Fitting 1 1
8420 Grab rail: WC, disabled use Metalwork 1 2
13700 Mirror Metalwork 1 1
19100 Waste bin: sanitary Furniture/ Fitting 3 1
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3003 Bidet handset 1 1 ___ ___ ___ ___ yes yes ___ ___
55650 Toilet suite: accessible 1 1 ___ ___ yes ___ ___ yes yes ___ with backrest as required to comply with standards
40403 Tapware: accessible basin mixer 1 1 ___ ___ yes yes yes ___ ___ ___
3050 Basin: handwash, accessible 1 1 ___ ___ yes ___ yes yes yes ___
ID Description Service Category Qty Selection / Remarks
4033 Floor waste Hydraulics 1
5000 Airconditioning HVAC or ventilation
5019 Exhaust HVAC
2189 General LED Lighting light switch near door; may also use motion sensor
8000 Patient to Staff call Nurse Call 1 + indicator button & light, optional in public areas
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light, optional in public areas
8080 Emergency call Nurse Call 1 + indicator button & light, optional in public areas
2577 PO: Double Power 1 locate near door outside room
9040 Body protected Power
0 0