Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. | $64.99 |
Online Room Data Sheet |
---|
Room Code | TRMT-14-I |
Net Room Area Briefed | 14 |
Hours of Operation | 24 Hours |
Occupancy | 1 patient; 1-2 staff |
Description / Special Requirements | The Treatment Room provides a controlled environment, privacy and facilities for carrying out consultations, examinations and treatments which may include wound dressings. Special Design Consideration - Sensor taps, if installed, should be connected to essential power supply Acoustics: Sound attenuation level - high; Acoustic privacy is required. Body Protected electrical area |
Amendment | 24.10.2010 First Draft 21.04.2011 Room Fabric, FF and FE modified 03.09.2014 Fabric, FF, FE and Services updated 31.10.2014 Modification to Room Fabric and FF 01.09.2022 FF, FE & Services updated 05.09.2022 Cornice changed to aluminium shadow line 03.09.2023 RDS updated |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
9127 | Doors | Solid Core/ Safety glass | Paint | 1 1/2 leaf, observation panel | 1400mm clear opening; lockable; observation panel optional | |
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
3022 | Wall finish | Resinate, 6mm | Prefinished | Splashback | to basin, other smooth impervious finish also acceptable | |
5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | ||
6025 | Cornice | Aluminium | Powdercoat | shadow line |
ID | Description | Category | Group | Qty | Selection / Remarks |
8291 | Air flowmeter | MEQ - General | 3 | 1 | to services panel |
1050 | Bench: laminate | Furniture/ Fitting | 1 | 1 | optional |
8297 | Bracket: suction bottle | MEQ - General | 2 | 1 | |
8404 | Bracket: sharps disposal | MEQ - General | 2 | 1 | on trolley |
3350 | Clock: battery operated | Furniture/ Fitting | 3 | 1 | |
4410 | Cupboard: under bench | Furniture/ Fitting | 1 | 1 | adjustable shelf, optional |
4470 | Cupboard: wall mounted, lockable | Furniture/ Fitting | 1 | 1 | over bench, adjustable shelf, optional |
4600 | Curtain track: bed screen | Metalwork | 1 | 1 | to door opening |
5000 | Curtain: bed screen | Furniture/ Fitting | 3 | 1 | |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | 3 compartments |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to basin |
6156 | Dispenser: soap | Furniture/ Fitting | 2 | 1 | to basin |
2926 | Dispenser: hand sanitiser | Furniture/ Fitting | 2 | 1 | |
6158 | Dispenser: soap antiseptic | Furniture/ Fitting | 2 | 1 | to basin |
8626 | Trolley: dressing, 2 drawer | MEQ - Furniture | 3 | 1 | |
8309 | Oxygen flowmeter | MEQ - General | 3 | 2 | to services panel |
8306 | IV pole: mobile | MEQ - General | 3 | 1 | |
8982 | Stretcher: procedure/ recovery | MEQ - Furniture | 3 | 1 | or patient bed |
8593 | Bracket: patient monitor | MEQ - General | 3 | 1 | |
8318 | Suction adapter | MEQ - General | 3 | 1 | to services panel |
8321 | Suction bottle | MEQ - General | 3 | 1 | |
8406 | Sharps disposal: on trolley, 11L | MEQ - General | 3 | 1 | |
8607 | Waste bin: clinical, 50 litres | MEQ - Furniture | 3 | 1 | |
10061 | Waste bin: General, 20 Litres | Furniture/ Fitting | 3 | 1 | |
21680 | Stool: adjustable, mobile | Furniture/ Fitting | 3 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
3100 | Basin: scrub, Type A | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | refer to BHWS-A (sim) |
8542 | Light: examination, single, ceiling mounted | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
54510 | Telephone: handset, standard | 3 | 1 | ___ | yes | ___ | ___ | ___ | ___ | ___ | ___ | to bench, optional |
8989 | Infusion pump: single channel | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
8746 | Diagnostic set: wall mounted | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional |
9056 | Refrigerator: drugs, under-bench, 150L | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional |
8776 | Monitor: physiologic, acute care | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, or vital signs monitor depending on operational requirements |
40404 | Tapware: sensor | 1 | 1 | yes | ___ | yes | yes | yes | ___ | ___ | ___ |
ID | Description | Service Category | Qty | Selection / Remarks |
11000 | Wall panel | Services Panels | 1 | |
9040 | Body protected | Power | ||
2576 | PO: Cleaner | Power | 1 | |
2579 | PO: Emergency power, single | Power | 5 | 4- patient services panel; 1- patient monitor |
2577 | PO: Double | Power | 1 | to bench |
2582 | PO: Single | Power | 4 | 4- patient services panel |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
8005 | Patient call handset | Nurse Call | 1 | call button on the handset |
8000 | Patient to Staff call | Nurse Call | 1 | + indicator button & light |
7040 | Suction | Medical Gases | 1 | patient services panel |
7020 | Medical Air (MA) | Medical Gases | 1 | patient services panel |
7000 | Oxygen (O2) | Medical Gases | 2 | patient services panel |
6055 | Special: task light, built in | Lighting | under O/H cupboards | |
6001 | General: colour corrected | Lighting | ||
5000 | Airconditioning | HVAC | ||
1006 | Voice / Data outlet: double | Communications | 2 | 1- patient services panel; 1- bench |
2233 | Direct connection: Emergency power | Power | 2 | 1- exam light; 1-sensor tap |
1005 | Voice / Data outlet: single | Communications | 3 | 1- telephone; 1- under-bench refrigerator; 1- patient monitor |
2582 | PO: Single | Power | 2 | 1- diagnostic set; 1- at low level next to stretcher |
2578 | PO: Emergency power, double | Power | 1 | to under-bench refrigerator |