Room Code TRMT-14-I
Net Room Area Briefed 14
Hours of Operation 24 Hours
Occupancy 1 patient; 1-2 staff
Description / Special Requirements The Treatment Room provides a controlled environment, privacy and facilities for carrying out consultations, examinations and treatments which may include wound dressings. Special Design Consideration - Sensor taps, if installed, should be connected to essential power supply Acoustics: Sound attenuation level - high; Acoustic privacy is required. Body Protected electrical area
Amendment 24.10.2010 First Draft 21.04.2011 Room Fabric, FF and FE modified 03.09.2014 Fabric, FF, FE and Services updated 31.10.2014 Modification to Room Fabric and FF 01.09.2022 FF, FE & Services updated 05.09.2022 Cornice changed to aluminium shadow line 03.09.2023 RDS updated
ID Fabric Material Finish Specification Selection Remarks
8040 Door protection Composite Prefinished PVC To door frame
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
9127 Doors Solid Core/ Safety glass Paint 1 1/2 leaf, observation panel 1400mm clear opening; lockable; observation panel optional
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin, other smooth impervious finish also acceptable
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
6025 Cornice Aluminium Powdercoat shadow line
ID Description Category Group Qty Selection / Remarks
8291 Air flowmeter MEQ - General 3 1 to services panel
1050 Bench: laminate Furniture/ Fitting 1 1 optional
8297 Bracket: suction bottle MEQ - General 2 1
8404 Bracket: sharps disposal MEQ - General 2 1 on trolley
3350 Clock: battery operated Furniture/ Fitting 3 1
4410 Cupboard: under bench Furniture/ Fitting 1 1 adjustable shelf, optional
4470 Cupboard: wall mounted, lockable Furniture/ Fitting 1 1 over bench, adjustable shelf, optional
4600 Curtain track: bed screen Metalwork 1 1 to door opening
5000 Curtain: bed screen Furniture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1 3 compartments
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6156 Dispenser: soap Furniture/ Fitting 2 1 to basin
2926 Dispenser: hand sanitiser Furniture/ Fitting 2 1
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
8626 Trolley: dressing, 2 drawer MEQ - Furniture 3 1
8309 Oxygen flowmeter MEQ - General 3 2 to services panel
8306 IV pole: mobile MEQ - General 3 1
8982 Stretcher: procedure/ recovery MEQ - Furniture 3 1 or patient bed
8593 Bracket: patient monitor MEQ - General 3 1
8318 Suction adapter MEQ - General 3 1 to services panel
8321 Suction bottle MEQ - General 3 1
8406 Sharps disposal: on trolley, 11L MEQ - General 3 1
8607 Waste bin: clinical, 50 litres MEQ - Furniture 3 1
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1
21680 Stool: adjustable, mobile Furniture/ Fitting 3 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3100 Basin: scrub, Type A 1 1 ___ ___ yes ___ yes yes yes ___ refer to BHWS-A (sim)
8542 Light: examination, single, ceiling mounted 1 1 yes ___ ___ ___ ___ ___ ___ ___
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ to bench, optional
8989 Infusion pump: single channel 3 1 yes opt ___ ___ ___ ___ ___ ___
8746 Diagnostic set: wall mounted 3 1 yes ___ ___ ___ ___ ___ ___ ___ optional
9056 Refrigerator: drugs, under-bench, 150L 3 1 yes yes ___ ___ ___ ___ ___ ___ optional
8776 Monitor: physiologic, acute care 3 1 yes yes ___ ___ ___ ___ ___ ___ optional, or vital signs monitor depending on operational requirements
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___
ID Description Service Category Qty Selection / Remarks
11000 Wall panel Services Panels 1
9040 Body protected Power
2576 PO: Cleaner Power 1
2579 PO: Emergency power, single Power 5 4- patient services panel; 1- patient monitor
2577 PO: Double Power 1 to bench
2582 PO: Single Power 4 4- patient services panel
8080 Emergency call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset
8000 Patient to Staff call Nurse Call 1 + indicator button & light
7040 Suction Medical Gases 1 patient services panel
7020 Medical Air (MA) Medical Gases 1 patient services panel
7000 Oxygen (O2) Medical Gases 2 patient services panel
6055 Special: task light, built in Lighting under O/H cupboards
6001 General: colour corrected Lighting
5000 Airconditioning HVAC
1006 Voice / Data outlet: double Communications 2 1- patient services panel; 1- bench
2233 Direct connection: Emergency power Power 2 1- exam light; 1-sensor tap
1005 Voice / Data outlet: single Communications 3 1- telephone; 1- under-bench refrigerator; 1- patient monitor
2582 PO: Single Power 2 1- diagnostic set; 1- at low level next to stretcher
2578 PO: Emergency power, double Power 1 to under-bench refrigerator
0 0