Room Code | TRSA-I |
Net Room Area Briefed | 14 |
Hours of Operation | 24 Hours |
Occupancy | 1 patient; 1 - 2 staff |
Description / Special Requirements | The Treatment Room - Secure Assessment provides a controlled environment, privacy and facilities for assessment and treatment of patients with acute conditions, suitable for mental health patients, and will be located within the Emergency Unit; Services will be enclosed for mental health patient use. The room will have close access to a staff handwashing basin. Acoustics: Sound attenuation level - high; Acoustic privacy is required. Body Protected electrical area |
Amendment | 24.10.10, - First Draft 21.04.11, - Room Fabric modified |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
3000 | Wall finish | Paint | Acrylic, washable | |||
3092 | Wall protection | MDF | Laminate | Bed protection wall panel | ||
7055 | Observation | Alum/ Glass | Powdercoat | Internal window, double glazed | safety glass with integral venetians | |
9006 | Doors | Solid Core/ Safety glass | Paint | Single leaf, observation panel | 850mm clear opening, with integral venetians, staff access | |
9127 | Doors | Solid Core/ Safety glass | Paint | 1 1/2 leaf, observation panel | 1400mm clear opening, with integral venetians | |
6025 | Cornice | Aluminium | Powdercoat | shadow line | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900AFFL | ||
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | ||
8040 | Door protection | Composite | Prefinished PVC | To door frame |
ID | Description | Category | Group | Qty | Selection / Remarks |
150 | Air flowmeter | Furniture/ Fitting | 3 | 1 | to services panel |
1252 | Blind: Venetian integral | Furniture/ Fitting | 1 | 3 | to observation window & door glazing, controls outside room |
1465 | Bracket: suction bottle | Furniture/ Fitting | 2 | 1 | |
16250 | Oxygen flowmeter | Furniture/ Fitting | 3 | 1 | to services panel |
21950 | Suction adapter | Furniture/ Fitting | 3 | 1 | to services panel |
22000 | Suction bottle | Furniture/ Fitting | 3 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
3700 | Bed: inpatient, electric | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
15900 | Diagnostic set: wall mounted | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional, behind roller shutter |
45575 | Roller shutter: automatic | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | enclosing bedhead services |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 1 | services panel, 1 outlet for telephone |
5000 | Airconditioning | HVAC | ||
6001 | General: colour corrected | Lighting | ||
6032 | Downlights: colour corrected | Lighting | 1 | over bed |
6110 | Downlights: dimmable | Lighting | ||
7000 | Oxygen (O2) | Medical Gases | 1 | services panel |
7020 | Medical Air (MA) | Medical Gases | 1 | services panel |
7040 | Suction | Medical Gases | 1 | services panel |
8000 | Patient/ Staff call | Nurse Call | 1 | + indicator button & light |
8005 | Patient call handset | Nurse Call | 1 | call button on the handset |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
9000 | GPO: Single | Power | 3 | services panel |
9010 | GPO: Emergency power, single | Power | 4 | services panel, 1 for monitor, if required |
9040 | Body protected | Power | ||
10005 | Duress alarm | Security | 2 | 1 each side of room |
11000 | Wall panel | Services Panels | 1 | recessed |