Treatment Room - Secure Assessment

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. $64.99
Online Room Data Sheet
Room Code TRSA-I
Net Room Area Briefed 14
Hours of Operation 24 Hours
Occupancy 1 patient; 1 - 2 staff
Description / Special Requirements The Treatment Room - Secure Assessment provides a controlled environment, privacy and facilities for assessment and treatment of patients with acute conditions, suitable for mental health patients, and will be located within the Emergency Unit; Services will be enclosed for mental health patient use. The room will have close access to a staff handwashing basin. Acoustics: Sound attenuation level - high; Acoustic privacy is required. Body Protected electrical area
Amendment 24.10.2010 First Draft 21.04.2011 Room Fabric modified 01.09.2022 FF, FE & Services updated 05.09.2022 Cornice changed to aluminium shadow line 03.09.2023 RDS updated
ID Fabric Material Finish Specification Selection Remarks
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
8040 Door protection Composite Prefinished PVC To door frame
3092 Wall protection MDF Laminate Bed protection wall panel
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
1253 Observation Alum/ Toughened glass Powdercoat Internal window, double glazed with integral venetian
9110 Doors Solid Core Paint 1 1/2 leaf 1400mm clear opening
9001 Doors Solid Core Paint Single leaf 850mm clear opening, staff access
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
3000 Wall finish Paint Acrylic, washable
6025 Cornice Aluminium Powdercoat shadow line
ID Description Category Group Qty Selection / Remarks
8291 Air flowmeter MEQ - General 3 1 to services panel
1252 Blind: Venetian integral Furniture/ Fitting 1 1 to internal window, controls outside room
8297 Bracket: suction bottle MEQ - General 2 1
8309 Oxygen flowmeter MEQ - General 3 1 to services panel
8318 Suction adapter MEQ - General 3 1 to services panel
8321 Suction bottle MEQ - General 3 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
8734 Bed: inpatient, electric, with foam mattress 3 1 yes ___ ___ ___ ___ ___ ___ ___
8746 Diagnostic set: wall mounted 3 1 yes ___ ___ ___ ___ ___ ___ ___ optional, behind roller shutter
45575 Roller shutter: automatic 1 1 yes ___ ___ ___ ___ ___ ___ ___ enclosing bedhead services
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 services panel
5000 Airconditioning HVAC
6001 General: colour corrected Lighting variable lighting level
6032 Downlights: colour corrected Lighting over bed
7000 Oxygen (O2) Medical Gases 1 services panel
7020 Medical Air (MA) Medical Gases 1 services panel
7040 Suction Medical Gases 1 services panel
8000 Patient to Staff call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
2582 PO: Single Power 5 3- patient services panel; 1- diagnostic set; 1- at low level for bed
2579 PO: Emergency power, single Power 4 3- patient services panel, 1- monitor, if required
9040 Body protected Power
10005 Duress alarm Security 2 1 each side of room
11000 Wall panel Services Panels 1 recessed
2576 PO: Cleaner Power 1
0 0