Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
![]() |
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
![]() |
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
![]() |
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. | $2.99 |
Online Room Data Sheet |
---|
Room Code | WTPL-I |
Net Room Area Briefed | 15 |
Hours of Operation | 24 Hours |
Occupancy | 1 - 2 |
Description / Special Requirements | The Water Treatment Plant Room is a lockable room for water treatment systems used in dialysis, including booster pumps, particle filters, water softeners, carbon filters and reverse osmosis systems. Refer to Manufacturer's Specifications for details of Reverse Osmosis (RO) Water Treatment Plant equipment. In particular this equipment will incorporate a heat disinfection function, and water saving features. The Water Treatment Plant Room should be located in close proximity to the Renal Dialysis Unit to permit short tubing runs to each Treatment Bay, and permit staff to monitor and service the water treatment systems. Special Design Requirements: - Ventilation, exhaust and/or airconditioning must be deisgned to accommodate the heat loads of the specified equipment. - High level sound isolation is required to ensure noise generated from this room does not invade Treatment spaces - Structural Engineer's assessment must be sought for floor load bearing capacity with respect to water treatment and pre- treatment plant equipment - Service access will be required aound the perimeter of all plant equipment - Pipework and components installed after the water inlet within this room shall not contain brass or copper |
Amendment | 24.10.2010 First Draft 03.09.2023 RDS updated |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1280 | Floor finish | Concrete | Trowel | Sealed | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
9110 | Doors | Solid Core | Paint | 1 1/2 leaf | 1600mm clear opening, lockable | |
5021 | Ceiling | Plasterboard | Paint, washable | Water resistant, flush set, suspended | min height 2400mm; water resistant drop in tile ceiling also acceptable | |
2155 | Skirting | Concrete | Sealed | Coved concrete to 150 AFFL | ||
2767 | Cornice | Plasterboard | Paint | Square set | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL |
ID | Description | Category | Group | Qty | Selection / Remarks |
1050 | Bench: laminate | Furniture/ Fitting | 1 | 1 | work bench |
21680 | Stool: adjustable, mobile | Furniture/ Fitting | 3 | 1 | under bench |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
42295 | Pump: pressure booster | 3 | 2 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | as needed to achieve required water pressure |
61295 | Water treatment plant | 3 | 3 | yes | ___ | yes | ___ | ___ | ___ | yes | ___ | RO Plant; details according to Manufacturer's Specifications |
ID | Description | Service Category | Qty | Selection / Remarks |
1002 | Alarm | Communications | 1 | to Staff Station - Renal Unit for Plant Equipment status/ malfunction |
4010 | Cold water: outlet | Hydraulics | 1 | inlet for RO Water Treatment Plant Equipment |
4033 | Floor waste | Hydraulics | 1 | floor waste must be capable of high flow rates and high temperature water (up to 95 degrees C) from the RO Water Plant |
5000 | Airconditioning | HVAC | A/C & exhaust system to accommodate heat loads generated by plant eqeuipment | |
5019 | Exhaust | HVAC | heat extraction will be required | |
2189 | General LED | Lighting | ||
2578 | PO: Emergency power, double | Power | 4 | for use of hand tools in the room, on a separate circuit |
2587 | PO: Special: for equipment | Power | 1 | 3 phase, according to Manufacturer's specifications |
2587 | PO: Special: for equipment | Power | 2 | pumps, as required |