Bay - Utility, 1m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. $2.99
Online Room Data Sheet
Room Code BUT-1-I
Net Room Area Briefed 1
Hours of Operation 24 Hours
Occupancy 1
Description / Special Requirements The Utility Bay provides an area with a bench and sink for use as a preparation area. The bay may be located adjacent to patient treatment areas. The bay should be located in close proximity to a staff handwashing basin.
Amendment 24.10.2010 First Draft 06.05.2011 Room Fabric updated 18.08.2016 Services updated
ID Fabric Material Finish Specification Selection Remarks
4031 Wall protection Composite Prefinished PVC Corner guards to 1500mm AFFL other heights also acceptable as per project standardisation
3052 Wall finish Vinyl Prefinished Wall vinyl to 1500mm AFFL
3000 Wall finish Paint Acrylic, washable
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
5010 Ceiling Plasterboard Paint, washable Flush set, suspended minimum height 2400mm; or consistent with adjacent area
2767 Cornice Plasterboard Paint Square set or consistent with adjacent area
ID Description Category Group Qty Selection / Remarks
1010 Bench: stainless steel Metalwork 1 1 with wet edge and inset sink, open under
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to sink
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1
20000 Shelving unit: adjustable Furniture/ Fitting 1 1 over bench
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
4045 Tapware: elbow mixer 1 1 ___ ___ yes yes yes ___ ___ ___ provide warm instead of hot water if located in a patient accessible area
47800 Sink, SS: single in bench 1 1 ___ ___ yes opt opt yes yes ___
ID Description Service Category Qty Selection / Remarks
4033 Floor waste Hydraulics 1
5000 Airconditioning HVAC consistent with adjacent area
2467 Downlights: LED Lighting
0 0