Room Code | CORR-PA-I |
Net Room Area Briefed | 0 |
Hours of Operation | 24 hours |
Occupancy | N/A |
Description / Special Requirements | Internal Corridor in Patient Areas that have standard air-conditioning including Emergency Unit, Inpatient Units, Intensive Care Units, Coronary Care Units, High Dependency Units. Corridor widths must be sized to allow for the safe movement and passing of trolleys, beds, wheelchairs and other mobile equipment, 2450mm clear width is recommended for standard Corridors; increase to 2600 mm clear if write-up/ observation bays are located in Corridor. Provision should also be made where oversized, additional equipment is used, ie, bed extensions or bariatric beds. Area (m2) included in HPU circulation which may be esitmated as a percentage added to the Net Briefed Area or measured off a plan. 1 x GPO-Cleaner should be provided per 10 metres or as per local authority requirements. Corridor lighting, where patients are transported on trolleys, positioned to prevent unnecessary glare to patient eyes. Light fittings shall be recessed, flush fitting and sealed to prevent dust ingress. |
Amendment | 24.04.2015 - First Draft. 28.08.2017 - Amendment to description & Fabric |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
5060 | Ceiling | Acoustic | Prefinished | Drop-in tiles, 600x1200 mm | to centre | |
2530 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL, minimum | ||
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
7001 | Windows | Desirable | ||||
8040 | Door protection | Composite | Prefinished PVC | To door frame | optional; to be decided at project level | |
6025 | Cornice | Aluminium | Powdercoat | shadow line | ||
9225 | Doors | Solid Core/ Glass | Paint | Double leaf, observation panel | to Corridor zones; 1500mm or 1800mm clear opening; doors widths to ensure ease of movement of beds/ trolleys and equipment; Hold open devices may be applied, magnetic hold open devices to fire doors must be connected to the fire alarm system | |
3000 | Wall finish | Paint | Acrylic, washable | |||
4010 | Wall protection | Composite | Prefinished PVC | Combined rail & crash bar at 900mm AFFL | ||
5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | to perimeter | |
4031 | Wall protection | Composite | Prefinished PVC | Corner guards to 1500mm AFFL | where required; align heights of corner guards with other corridor elements |
ID | Description | Category | Group | Qty | Selection / Remarks |
5828 | External window dressing | Furniture/ Fitting | 1 | 1 | Number to align with window configuration. Window dressing type to comply with Infection Control policy. |
5830 | Dispenser: antiseptic hand rub | Furniture/ Fitting | 2 | 1 | Number to suit corridor layout and Infection Control policies. |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
ID | Description | Service Category | Qty | Selection / Remarks |
5000 | Airconditioning | HVAC | ||
8040 | Annunciator | Nurse Call | 1 | Ceiling mounted; number to suit corridor layout |
9015 | GPO: Cleaner | Power | 1 | 1 every 10 metres recommended; number and location to comply with local authority requirements |
10020 | Card access | Security | 1 | To unit entry doors where required |
2189 | General LED | Lighting |