Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. | $64.99 |
Online Room Data Sheet |
---|
Room Code | ENS-ACC-I |
Net Room Area Briefed | 7 |
Hours of Operation | 24 Hours |
Occupancy | 1 patient; 1-2 staff assisting |
Description / Special Requirements | The Accessible Ensuite for use by a disabled patient to wash, shave, groom themselves, shower and use the toilet, either independently or with assistance. The room shall comply with local Authority requirements for wheelchair accessible rooms. The area and layout must accommodate an assisting nurse and a shower commode. The Ensuite should accommodate mobile lifting equipment in the event of a patient fall. Acoustics: sound attenuation level - High. Acoustic privacy required. Additional design requirements: - The shower floor must not have a raised hob - The entrance is to be flush with the adjoining floor - The door is to be fitted with escape hardware Body protected electrical area |
Amendment | 23.10.2014 First Draft |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
8040 | Door protection | Composite | Prefinished PVC | To door frame | optional | |
1175 | Floor finish | Tiles | Non-slip | Ceramic | vinyl also acceptable | |
2145 | Skirting | Tiles | To match floor | Coved | or coved floor vinyl skirting | |
3080 | Wall finish | Tiles | Glazed | Full height | vinyl also acceptable | |
5023 | Ceiling | Plasterboard | Prefinished | Water resistant, drop in tiles, 600x1200 mm | ||
6030 | Cornice | Aluminium | Powdercoat | 24mm shadow angle | ||
9110 | Doors | Solid Core | Paint | 1 1/2 leaf | 1200mm clear outward opening, privacy latch, emergency release; sliding door is acceptable |
ID | Description | Category | Group | Qty | Selection / Remarks |
3054 | Waste bin: general, 30 Litre | Furniture/ Fitting | 3 | 1 | to basin |
3400 | Coathook | Metalwork | 1 | 2 | |
4800 | Curtain track: shower | Metalwork | 1 | 1 | |
5300 | Curtain: shower | Furniture/ Fitting | 3 | 1 | |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to basin |
6156 | Dispenser: soap | Furniture/ Fitting | 2 | 2 | 1 to basin; 1 to shower (optional) |
6160 | Dispenser: toilet paper | Furniture/ Fitting | 1 | 1 | |
8420 | Grab rail: WC, disabled use | Metalwork | 1 | 1 | wrap around behind toilet |
8450 | Grab rail: Shower | Metalwork | 1 | 1 | combined with hand held shower |
13700 | Mirror | Metalwork | 1 | 1 | over basin |
19100 | Waste bin: sanitary | Furniture/ Fitting | 3 | 1 | optional |
20050 | Shower seat: fold up | Furniture/ Fitting | 1 | 1 | as required for accessible shower |
20650 | Soap/ shampoo holder | Furniture/ Fitting | 1 | 1 | |
23700 | Towel rail | Metalwork | 1 | 1 | with grab rail strength and fixings |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
3003 | Bidet handset | 1 | 1 | ___ | ___ | ___ | ___ | yes | yes | ___ | ___ | near toilet |
5604 | Toilet suite: accessible | 1 | 1 | ___ | ___ | yes | ___ | ___ | yes | yes | ___ | With backrest as required; concealed cistern optional |
5605 | Basin: handwash, accessible | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | With integral shelf for patient belongings or separate shelf; Tapware: mixer, fixture mounted |
47400 | Shower: hand-held | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | Tapware: mixer, wall mounted, shower |
ID | Description | Service Category | Qty | Selection / Remarks |
4033 | Floor waste | Hydraulics | 1 | |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
2577 | PO: Double | Power | 1 | |
5019 | Exhaust | HVAC | ||
2189 | General LED | Lighting | sensor light optional | |
9040 | Body protected | Power | ||
5015 | Ventilation | HVAC | ||
1951 | Staff assist call | Nurse Call | 1 | + indicator button & light |
8000 | Patient to Staff call | Nurse Call | 2 | + indicator button & light; 1-shower, 1-toilet |
1983 | General fluorescent: downlights | Lighting | over basin |