Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
![]() |
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Online Room Data Sheet |
---|
Room Code | ENS-BA-7-I |
Net Room Area Briefed | 7 |
Hours of Operation | 24 Hours |
Occupancy | 1 patient; 1-2 staff assisting |
Description / Special Requirements | The Bariatric Ensuite is designed to meet the needs of bariatric (obsese or morbidly obese) patients allowing the patient to wash, shave, groom themselves, shower and use the toilet, either independently or with assistance. The Ensuite - Bariatric is associated with the 1 Bed Room - Bariatric: the additional area and layout will facilitate two assisting nurses and a shower commode with bariatric capacity. The Ensuite and Bedroom should be planned as an integral suite to optimise the use of a ceiling mounted hoist between the two rooms. Acoustics: sound attenuation level - High. Acoustic privacy required. Additional Design Requirements: - The shower floor must not have a raised hob - The entrance is to be flush with the adjoining floor - The door is to be fitted with escape hardware. Body protected electrical area. |
Amendment | 02.07.2015 First Draft 03.09.2023 RDS reviewed |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
9110 | Doors | Solid Core | Paint | 1 1/2 leaf | 1200mm clear outward opening, privacy latch, emergency release | |
4159 | Cornice | Aluminium | Powdercoat | Angle flush against wall, in line with ceiling grid | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
3795 | Ceiling | Plasterboard | Prefinished | Water resistant, drop-in tiles, 600x600mm | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | or other coved skirting to match floor | |
3035 | Wall finish | Vinyl | Prefinished | Wall vinyl full height | other smooth impervious finish also acceptable | |
1020 | Floor finish | Vinyl, non-slip | Safety | Seamless, coved | other non-slip impervious floor finish suitable for barefeet also acceptable |
ID | Description | Category | Group | Qty | Selection / Remarks |
3400 | Coathook | Metalwork | 1 | 2 | |
4800 | Curtain track: shower | Metalwork | 1 | 1 | |
5300 | Curtain: shower | Furniture/ Fitting | 3 | 1 | |
5673 | Chair: shower, bariatric | Furniture/ Fitting | 3 | 1 | or commode chair, bariatric capacity |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to basin |
6156 | Dispenser: soap | Furniture/ Fitting | 2 | 2 | 1 - to basin; 1 - to shower (optional) |
6160 | Dispenser: toilet paper | Furniture/ Fitting | 2 | 1 | locate on drop down rail |
8309 | Oxygen flowmeter | MEQ - General | 3 | 1 | optional |
8400 | Grab rail: WC | Metalwork | 1 | 2 | both sides of toilet, fixings to support bariatric capacity |
8450 | Grab rail: Shower | Metalwork | 1 | 1 | combined with hand held shower; fixings to support bariatric capacity |
8500 | Grab rail: WC, hinged | Metalwork | 1 | 2 | drop down rails both sides of toilet; 1 side with toilet paper dispenser; 1 side with patient to staff call; fixings to support bariatric capacity |
10800 | Hook: for IV flasks | Metalwork | 1 | 2 | |
13700 | Mirror | Metalwork | 1 | 1 | over basin |
19100 | Waste bin: sanitary | Furniture/ Fitting | 3 | 1 | optional |
20603 | Soap/ shampoo holder: recessed | Furniture/ Fitting | 1 | 1 | |
23700 | Towel rail | Metalwork | 1 | 1 | with grab rail strength and fixings to support bariatric capacity |
24100 | Waste bin: paper, 20 Litre | Furniture/ Fitting | 3 | 1 | to basin |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
3003 | Bidet handset | 1 | 1 | ___ | ___ | ___ | ___ | yes | yes | ___ | ___ | near toilet; optional |
5603 | Basin: ensuite | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | or floor basin with a separate shelf; fixings to support bariatric capacity |
8978 | Patient lift: overhead track, bariatric, w sling | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional; track from bedroom; provide track only if track continuous from bedroom |
5602 | Toilet suite: bariatric | 1 | 1 | ___ | ___ | yes | ___ | ___ | yes | yes | ___ | concealed cistern optional |
40402 | Tapware: basin mixer | 1 | 1 | ___ | ___ | yes | yes | yes | ___ | ___ | ___ | fixture mounted |
40406 | Tapware: shower mixer | 1 | 1 | ___ | ___ | yes | yes | yes | ___ | ___ | ___ | |
47400 | Shower: hand-held | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | fixings to support bariatric capacity |
ID | Description | Service Category | Qty | Selection / Remarks |
4033 | Floor waste | Hydraulics | 1 | |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
5019 | Exhaust | HVAC | for heat/ steam | |
2189 | General LED | Lighting | ||
9040 | Body protected | Power | ||
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
8000 | Patient to Staff call | Nurse Call | 2 | + indicator button & light; 1 - shower & 1 - toilet (may be located on drop down rail beside toilet) |
7000 | Oxygen (O2) | Medical Gases | 1 | optional |
5015 | Ventilation | HVAC | ||
2587 | PO: Special: for equipment | Power | 1 | for hair dryer & shaver use only; to comply with relevant electric safety guidelines |