Room Code | FLUO-I |
Net Room Area Briefed | 36 |
Hours of Operation | Available 24 Hours |
Occupancy | 1 patient; 1 - 2 staff |
Description / Special Requirements | Fluoroscopy Room is a room for undertaking radiographic procedures involving contrast media. Patient Change, Toilets and Shower should be lcoated in close proximity. The room may include a preparation area with sink. Additional Design Requirements: - Radiation sheilding to walls and glazing as advised by Radiation Consultant - Unistrut type ceiling may be required, depending on equipment to be installed - Cable ducting between the X-ray table, vertical bucky and control area may be required, depending on equipment type and layout - 'X-ray in Use' warning lights will be required outside each entry door Body Protected electrical area |
Amendment | 24.10.2010 First Draft 21.04.2011 Outline specifications, FF and Services modified 21.06.2019 Room name and room code updated 03.09.2023 RDS reviewed |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
9130 | Doors | Solid Core | Paint | 1 1/2 leaf, with lead shielding | Patient entry/exit 1400mm clear opening | |
7025 | Observation | Lead glass | Clear | Internal window | to control booth | |
9001 | Doors | Solid Core | Paint | Single leaf | to Patient Change/ Toilet and Staff Entry | |
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
4159 | Cornice | Aluminium | Powdercoat | Angle flush against wall, in line with ceiling grid | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
3022 | Wall finish | Resinate, 6mm | Prefinished | Splashback | to basin & sink, other smooth impervious finish also acceptable | |
5062 | Ceiling | Acoustic | Prefinished | Drop-in tiles, 600x600 mm | at 3000mm AFFL |
ID | Description | Category | Group | Qty | Selection / Remarks |
1010 | Bench: stainless steel | Metalwork | 1 | 1 | with wet edge |
1090 | Bench: laminate, free standing | Furniture/ Fitting | 3 | 1 | workstation |
2150 | Chair: patient | Furniture/ Fitting | 3 | 1 | |
4410 | Cupboard: under bench | Furniture/ Fitting | 1 | 1 | adjustable shelf |
4460 | Cupboard: wall mounted | Furniture/ Fitting | 1 | 1 | over bench |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to basin |
6158 | Dispenser: soap antiseptic | Furniture/ Fitting | 2 | 1 | to basin |
8291 | Air flowmeter | MEQ - General | 3 | 1 | to services panel |
8309 | Oxygen flowmeter | MEQ - General | 3 | 1 | to services panel |
8321 | Suction bottle | MEQ - General | 3 | 1 | |
8313 | Rack: lead apron | MEQ - Imaging | 1 | 1 | |
24450 | Workstation: laminated | Furniture/ Fitting | 3 | 1 | pull-out shelf for keyboard |
8297 | Bracket: suction bottle | MEQ - General | 2 | 1 | |
8318 | Suction adapter | MEQ - General | 3 | 1 | |
2100 | Chair: ergonomic, office | Furniture/ Fitting | 3 | 1 | |
8402 | Footstool: 2-step | MEQ - Furniture | 3 | 1 | |
10061 | Waste bin: General, 20 Litres | Furniture/ Fitting | 3 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
2800 | Basin: handwash, Type B | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | |
11400 | Computer: PC & monitor | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | flat screen |
40404 | Tapware: sensor | 1 | 1 | yes | ___ | yes | yes | yes | ___ | ___ | ___ | straight spout |
40405 | Tapware: sink mixer | 1 | 1 | ___ | ___ | yes | yes | yes | ___ | ___ | ___ | warm water, to sink |
47800 | Sink, SS: single in bench | 1 | 1 | ___ | ___ | yes | opt | opt | yes | yes | ___ | |
9092 | Control console | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | inside booth; may be located in separate Control Room |
9095 | X-ray unit: chest | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional |
9099 | X-ray table | 2 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
9643 | X-ray unit: radiography/ fluoroscopy, digital | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
54510 | Telephone: handset, standard | 3 | 1 | ___ | yes | ___ | ___ | ___ | ___ | ___ | ___ | wall mounted |
62400 | IMG: control booth | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | with lead glazing; not required if separate Control Room provided |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 3 | 1- control console; 1- computer; 1- bench |
1040 | Intercom | Communications | 1 | |
5000 | Airconditioning | HVAC | ||
2242 | General LED: colour corrected | Lighting | ||
6055 | Special: task light, built in | Lighting | under O/H cupboards | |
6005 | Dimmable | Lighting | ||
7000 | Oxygen (O2) | Medical Gases | 1 | patient services panel |
7020 | Medical Air (MA) | Medical Gases | 1 | patient services panel |
7040 | Suction | Medical Gases | 1 | patient services panel |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | |
8080 | Emergency call | Nurse Call | 1 | patient services panel |
2582 | PO: Single | Power | 2 | patient services panel |
2579 | PO: Emergency power, single | Power | 2 | patient services panel |
9040 | Body protected | Power | ||
11000 | Wall panel | Services Panels | 1 | flush mounted |
12011 | Radiation shielding | Shielding | to walls, floor, ceiling, doors & glazing as specified by Radiation Consultant | |
2724 | Direct connection: Emergency power | Power | 1 | sensor operated tapware |
6826 | Trunking: 150mm x 70mm | Electrical Installations | 1 | between x-ray fluoroscopy equipment, chest bucky, patient table and control console |
6076 | Special: 'X-ray In Use' lights | Lighting | 1 | |
6827 | Cabinet: generator | Power | 1 | to power fluoroscopy system and chest bucky, supplied by imaging vendor |
2791 | PO: Special: 3 phase | Power | 1 | to fluoroscopy system equipment generator |
2726 | PO: UPS, double | Power | 4 | 2- control console; 2- computer |
2578 | PO: Emergency power, double | Power | 4 | 1- bench; 3- walls |
11505 | Floor duct for power & data | Services Ducts | 1 | between x-ray fluoroscopy equipment, chest bucky, patient table and control console |
1005 | Voice / Data outlet: single | Communications | 1 | to telephone |