Room Code RSIM-MRI-I
Net Room Area Briefed 47
Hours of Operation 8am to 10pm, daily
Occupancy 1 patient; up to 4 staff assisting
Description / Special Requirements The Radiotherapy Simulator Room - MRI will accommodate a simulator which will duplicate the beam geometry of the medical linear accelerator. The Simulator is used in treatment planning to localise the treatment field. Radiofrequency sheilding will be required. A Control Room will be located adjacent to the Simulator Room. A staff handwashin basin will be located outside the room in close proximity. Fixtures and fittings to be non magnetic. Body Protected electrical area Acoutsics: acoustic privacy required for ambient noise emitted by scanning equipment Special Design Requirements: - The MRI suite shall be planned to conform to staged access and control zones complying with local authority requirements to prevent unscreened persons accessing the 5-gauass volume around the MRI scanner and to minimise radiofrequency interference from other equipment - Electromagnetic sheilding (radio frequency enclosure) as advised by RF Shielding Consultant - Structural assessment may be required to ensure the floor is designed to acommodate the weight of the equipment - Floor to ceiling cable duct with removable covers may be required - Underfloor cable trays between Control area and MRI table and floor to ceiling duct may be required - Warning lights outside each entry door - Power to be on emergency supply - all power to MRI to pass through MRI isolation transformer - Installation of the MRI including services requirements such as cryogen venting, emergency exhaust, passive pressure relief systems, shall conform to local authority requirements and manufacturer's specifications
Amendment 01.02.2011 First Draft 15.03.2017 Description & services updated
ID Fabric Material Finish Specification Selection Remarks
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
7025 Observation Lead glass Clear Internal window to Control Room
9110 Doors Solid Core Paint 1 1/2 leaf patient entry/ exit; 1400mm clear opening
5010 Ceiling Plasterboard Paint, washable Flush set, suspended at 3000mm height
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
3000 Wall finish Paint Acrylic, washable
2767 Cornice Plasterboard Paint Square set
ID Description Category Group Qty Selection / Remarks
8321 Suction bottle MEQ - General 3 2 non-magnetic
8417 Air flowmeter: MRI MEQ - General 3 1 to patient services panel; non-magnetic
8642 Bracket: suction bottle, MRI MEQ - General 2 2 non-magnetic
9481 Board: patient transfer, MRI MEQ - General 3 1
8651 Cabinet: storage, MRI coils MEQ - Imaging 3 part of MRI system configurations
2926 Dispenser: hand sanitiser Furniture/ Fitting 2 1
8419 Footstool: MRI MEQ - Furniture 3 1
8423 IV pole: mobile, MRI MEQ - General 3 1
8418 Oxygen flowmeter: MRI MEQ - General 3 2 to patient services panel; non-magnetic
8424 Suction adapter: MRI MEQ - General 3 2 to patient services panel; non-magnetic
9183 Trolley: multi-purpose, MRI MEQ - Furniture 3 1
8421 Wheelchair: MRI MEQ - General 3 1 or can be kept in store
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
9105 Laser positioning lights 2 yes opt ___ ___ ___ ___ ___ ___ Qty (3), part of MRI system configurations; quantity as per manufacturer's recommendation
7300 Camera: CCTV security 1 yes ___ ___ ___ ___ ___ ___ ___ part of MRI system configurations; to view patient, optional
9079 Scanning unit: MRI, 1.5-tesla, RT 2 1 yes yes ___ ___ ___ ___ yes ___ with patient table and control console
9111 Injector: contrast media, mobile, dual head, MRI 3 1 yes yes ___ ___ ___ ___ ___ ___
8777 Monitor: physiologic, MRI, on stand 3 1 yes opt ___ ___ ___ ___ ___ ___
9007 Ventilator: adult/ paediatric, MRI, on stand 3 1 yes opt ___ ___ ___ ___ ___ ___ or can be kept in store
9052 Anaesthesia unit: MRI 3 1 yes opt ___ ___ ___ ___ ___ ___ or can be kept in store
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 1- patient services panel; 1- wall
1040 Intercom Communications 1 speakers and mic are mounted to the gantry
5000 Airconditioning HVAC
2242 General LED: colour corrected Lighting
6005 Dimmable Lighting
7000 Oxygen (O2) Medical Gases 2 patient services panel; non magnetic outlet
7010 Nitrous Oxide (N2O) Medical Gases 1 patient services panel; non magnetic outlet
7020 Medical Air (MA) Medical Gases 1 patient services panel; non magnetic outlet
7040 Suction Medical Gases 2 patient services panel; non magnetic outlet
7070 Scavenge Medical Gases 1 patient services panel; non magnetic outlet
12020 Faraday cage Shielding to walls, floor, ceiling, doors & glazing as specified by Radiation Consultant
11000 Wall panel Services Panels 1
9040 Body protected Power
2578 PO: Emergency power, double Power 3 walls
2579 PO: Emergency power, single Power 4 patient services panel
8080 Emergency call Nurse Call 1
8010 Staff/ Nurse assist call Nurse Call 1
2411 Special: "MRI In Use" light Lighting 1 to outside of room entry
2234 Direct connection: Uninterrupted power Power 3 laser positioning lights (qty as per manufacturer's recommendation)
2502 Clean Agent Gas Suppression System Fire Services 1 NOVEC 1230
2473 Power over Ethernet (PoE) Power 1 to CCTV camera (as applicable)