Scrub Up/ Gowning, 6m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. $2.99
Online Room Data Sheet
Room Code SCRB-6-I
Net Room Area Briefed 6
Hours of Operation 24 Hours
Occupancy Up to 2
Description / Special Requirements The Scrub-up/ Gowning 6m2 provides for pre-operative scrubbing and gowning/ gloving, located adjacent to a Procedures Room or Imaging Room. Additional Design Considerations: - A minimum of 800mm is required between scrub stations - Taps to be non touch - automatically operated or foot operated
Amendment 03.09.2023 RDS updated
ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
1020 Floor finish Vinyl, non-slip Safety Seamless, coved to wet zone
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
4031 Wall protection Composite Prefinished PVC Corner guards to 1500mm AFFL other heights also acceptable as per project standardisation
3052 Wall finish Vinyl Prefinished Wall vinyl to 1500mm AFFL
3010 Wall finish Paint Scrub resistant
5020 Ceiling Plasterboard Paint, scrub resistant Flush set, suspended
2767 Cornice Plasterboard Paint Square set
ID Description Category Group Qty Selection / Remarks
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 Qty (2), part of scrub sink
6164 Dispenser: scrub brush Furniture/ Fitting 2 Qty (2), part of scrub sink
8622 Trolley: gowns MEQ - Furniture 3 1 optional
8594 Linen carrier: dirty, single MEQ - Furniture 3 1
19810 Shelf: SS, over Metalwork 1 1 over scrub trough
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
10132 Clock: master clock 1 1 yes opt ___ ___ ___ ___ ___ ___
10335 Tapware: scrub, sensor 1 yes ___ yes yes yes ___ ___ ___ Qty (2), part of scrub sink; auto/ knee operated taps also acceptable
9234 Scrub sink: 1-bay, stainless steel 2 1 opt ___ yes yes ___ ___ yes ___
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
2189 General LED Lighting
2724 Direct connection: Emergency power Power 2 sensor operated tapware
1080 Clock: master clock Communications 1 battery/ POE/ electrical connection TBC
4010 Cold water: outlet Hydraulics 1 to scrub sink
4030 Drainage Hydraulics 1 to scrub sink
4000 Hot water: outlet Hydraulics 1 to scrub sink
0 0