| Edit it in Health Facility Briefing System (HFBS) | |||
|---|---|---|---|
|
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing | |
| Room Layout Sheet | |||
|---|---|---|---|
|
|
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
| Other Files | |||
|---|---|---|---|
|
|
Buy an editable AutoCAD DWG Room Layout Sheet (RLS) for this standard component. | $2.99 | |
|
|
Buy an editable Revit Room Layout Sheet (RLS) for this standard component. | $64.99 | |
| Online Room Data Sheet |
|---|
| Room Code | SECL-I |
| Net Room Area Briefed | 14 |
| Hours of Operation | 24 Hours |
| Occupancy | 1 patient; 1-2 staff intermittently |
| Description / Special Requirements | A Seclusion Room provides for the sole confinement of a distressed or agitated person requiring separation for short periods at any hour of the day or night on an involuntary basis. The Seclusion Room will be observable from the Staff Station. An external outlook is desirable. All glazing (including external windows) must comply to relevant safety standard. Acoustics: Sound attenuation level high; Acoustic privacy is required Additional Design Considerations: - An internal observation window is required - A second room egress door is required - The room shall be lockable from the outside only and shall have a mental health compliant push/ pull handle from the inside. The door shall be unlocked from the inside by card access control for secure staff egress - If an ensuite is provided the door should be acrylic, double swing and with no lock or hardware |
| Amendment | 24.10.2010 First Draft 21.04.2011 Outline specifications and FF modified 21.06.2019 Room area updated 03.09.2023 RDS updated 26.02.2025 Description and services updated |
| ID | Fabric | Material | Finish | Specification | Selection | Remarks |
| 9006 | Doors | Solid Core/ Safety glass | Paint | Single leaf, observation panel | 1100mm clear opening, lockable from outside. with integral blinds | |
| 7001 | Windows | fixed laminated toughened glass if provided | ||||
| 8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
| 3072 | Wall finish | Vinyl | Cushioned | Wall vinyl full height | ||
| 1010 | Floor finish | Vinyl | Cushioned | Seamless, coved | ||
| 5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | 3000 mm height | |
| 9006 | Doors | Solid Core/ Safety glass | Paint | Single leaf, observation panel | 500mm clear outward opening, optional | |
| 8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
| 1253 | Observation | Alum/ Toughened glass | Powdercoat | Internal window, double glazed | with integral venetians; optional | |
| 2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
| 2767 | Cornice | Plasterboard | Paint | Square set | 90mm plasterboard cornice |
| ID | Description | Category | Group | Qty | Selection / Remarks |
| 1252 | Blind: Venetian integral | Furniture/ Fitting | 1 | 2 | to internal & external windows, controls outside room |
| 3930 | Mirror: convex | Metalwork | 1 | 1 | if CCTV not provided |
| 13350 | Mattress: foam | Furniture/ Fitting | 3 | 1 | foam, on floor |
| ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
| 7300 | Camera: CCTV security | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | recessed in ceiling dome |
| ID | Description | Service Category | Qty | Selection / Remarks |
| 5000 | Airconditioning | HVAC | with vandal proof outlet | |
| 6030 | Special: downlights | Lighting | vandal proof | |
| 6060 | Special: night lights | Lighting | vandal proof | |
| 2724 | Direct connection: Emergency power | Power | 1 | for CCTV camera (POE connection also acceptable) |
| 10005 | Duress alarm | Security | 1 | outside room near door |
| 6005 | Dimmable | Lighting | ||
| 10020 | Card access | Security | 2 | 1 per door for secure staff egress |