Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
![]() |
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
![]() |
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
![]() |
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. | $64.99 |
Online Room Data Sheet |
---|
Room Code | SHD-I |
Net Room Area Briefed | 4 |
Hours of Operation | 24 Hours |
Occupancy | 1 patient; 1-2 staff assisting as required |
Description / Special Requirements | The Shower - Accessible is a room containing a shower for use by disabled persons or patients, either independently or with nurse assistance. Acoustics: Sound attenuation level - high; Acoustic privacy required. Body Protected electrical area Additional Design Considerations: - Access is required for commode chairs - The floor must not have a raised hob - The door will require escape hardware to allow staff access in an emergency |
Amendment | 24.10.2010 First Draft 26.05.2011 Fabric modified 03.09.2023 RDS updated |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
3795 | Ceiling | Plasterboard | Prefinished | Water resistant, drop-in tiles, 600x600mm | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
9001 | Doors | Solid Core | Paint | Single leaf | 920mm clear; outward opening; privacy latch; emergency release | |
3000 | Wall finish | Paint | Acrylic, washable | |||
4159 | Cornice | Aluminium | Powdercoat | Angle flush against wall, in line with ceiling grid | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | or other coved skirting to match floor | |
3035 | Wall finish | Vinyl | Prefinished | Wall vinyl full height | other smooth impervious finish also acceptable; to wet areas | |
1020 | Floor finish | Vinyl, non-slip | Safety | Seamless, coved | other non-slip impervious floor finish suitable for barefeet also acceptable |
ID | Description | Category | Group | Qty | Selection / Remarks |
1002 | Bench seat: fold up/down | Furniture/ Fitting | 1 | 1 | |
3400 | Coathook | Metalwork | 1 | 2 | 1 at 1200H for wheelchair users |
4800 | Curtain track: shower | Metalwork | 1 | 1 | |
5300 | Curtain: shower | Furniture/ Fitting | 3 | 1 | |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
8450 | Grab rail: Shower | Metalwork | 1 | 1 | L shaped, optional |
8450 | Grab rail: Shower | Metalwork | 1 | 1 | T bar |
20603 | Soap/ shampoo holder: recessed | Furniture/ Fitting | 1 | 1 | |
23700 | Towel rail | Metalwork | 1 | 1 | with grab rail strength/ fixings |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
40406 | Tapware: shower mixer | 1 | 1 | ___ | ___ | yes | yes | yes | ___ | ___ | ___ | |
47400 | Shower: hand-held | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ |
ID | Description | Service Category | Qty | Selection / Remarks |
4033 | Floor waste | Hydraulics | 1 | |
5019 | Exhaust | HVAC | ||
2189 | General LED | Lighting | ||
8000 | Patient to Staff call | Nurse Call | 1 | + indicator button & light, water proof |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light, water proof |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
5015 | Ventilation | HVAC |